Energy and exergy analysis of a novel multi-pressure levels ejector absorption-recompression refrigeration system: Parametric study and optimization

被引:7
作者
Zarei, Ahmad [1 ]
Zamani, Javid [1 ]
Hooshyari, Liya [1 ]
Zaboli, Sohrab [1 ]
机构
[1] KN Toosi Univ Technol, Dept Mech Engn, Tehran, Iran
关键词
Absorption; recompression; Thermodynamics; COP; Optimization; Ejector; ORGANIC RANKINE-CYCLE; WORKING FLUIDS; PERFORMANCE EVALUATION; COOLING CYCLE; FLASH TANK; NH3-H2O; DESIGN; INTEGRATION; ENHANCEMENT; TEMPERATURE;
D O I
10.1016/j.tsep.2023.101904
中图分类号
O414.1 [热力学];
学科分类号
摘要
The world is facing a cooling crunch, and investing in the efficiency enhancement of cooling systems is the most straightforward strategy to mitigate greenhouse gas (GHG) emissions and reduce costs. To this end, this study primarily sought to enhance the efficiency of an absorption refrigeration cycle (ARC) and diminish energy consumption. For this, a vapor compression refrigeration cycle and an ejector-ARC were combined, using a turbo-expander to improve system efficiency. The ejector would be exploited to raise the absorber pressure and reduce pump power, the turbo-expander was employed in place of the expansion valve, and the compressor was partially used to supply generator heat. The proposed system has four pressure levels. The condenser and generator were assumed to be an integrated unit whose heat loss would be used to heat the generator. The effects of several parameters, e.g., generator temperature and pressure, compressor pressure ratio, and ejector parameters, on the coefficient of performance (COP) and exergetic efficiency (ECOP), were explored. The multiobjective optimization showed that the proposed system had much higher performance than the ARC, with up to 191.2% and 54.7% higher COP and ECOP, respectively. Furthermore, the maximum COP occurred at a generator pressure and temperature lower than the ARC. Thus, the proposed design could handle the high activation temperature and pressure challenges of ARCs with an NH3-H2O working fluid. It was also observed that COP was a function of the ejector mixing tube diameter and had a maximum level. The ejector reduced the circulation ratio and increased the absorber pressure above the evaporator pressure, reducing pump power.
引用
收藏
页数:15
相关论文
共 50 条
[21]   Advanced Cascaded Recompression Absorption System Equipped with Ejector and Vapor-Injection Enhanced Vapor Compression Refrigeration System: ANN based Multi-Objective Optimization [J].
Khan, Yasin ;
Naqib-Ul-Islam, S. M. ;
Faruque, Md Walid ;
Ehsan, M. Monjurul .
THERMAL SCIENCE AND ENGINEERING PROGRESS, 2024, 49
[22]   Energy and exergy analysis of vapor compression-triple effect absorption cascade refrigeration system [J].
Agarwal, Shyam ;
Arora, Akhilesh ;
Arora, B. B. .
ENGINEERING SCIENCE AND TECHNOLOGY-AN INTERNATIONAL JOURNAL-JESTECH, 2020, 23 (03) :625-641
[23]   Multi-objective optimization of vapor absorption refrigeration system for the minimization of annual operating cost and exergy destruction [J].
Nagraj, Swarna Makkitaya ;
Kommadath, Remya ;
Kotecha, Prakash ;
Anandalakshmi, R. .
JOURNAL OF BUILDING ENGINEERING, 2022, 49
[24]   Thermoeconomic Analysis and Multi-Objective Optimization of a LiBr-Water Absorption Refrigeration System [J].
Abbaspour, M. ;
Saraei, A. R. .
INTERNATIONAL JOURNAL OF ENVIRONMENTAL RESEARCH, 2015, 9 (01) :61-68
[25]   Energy, exergy, environment and economic analyses and optimization of two-stage absorption–compression combined refrigeration system [J].
Manoj Dixit ;
Akhilesh Arora ;
S. C. Kaushik .
Clean Technologies and Environmental Policy, 2017, 19 :2215-2229
[26]   Energy and exergy analysis of a novel dual-ejector booster transcritical CO2 refrigeration system for applications in warm climates [J].
Sengupta, Ayan ;
Dasgupta, Mani Sankar .
JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2023, 148 (07) :2749-2764
[27]   Energy and exergy analysis of a novel dual-ejector booster transcritical CO2 refrigeration system for applications in warm climates [J].
Ayan Sengupta ;
Mani Sankar Dasgupta .
Journal of Thermal Analysis and Calorimetry, 2023, 148 :2749-2764
[28]   Energy and exergy analysis of a novel two-stage ejector refrigeration cycle using binary zeotropic mixturesres [J].
Dai, Zhengshu ;
Chen, Xiaoluo ;
Chen, Qi ;
Zhang, Xuejun ;
Zhang, Hua .
INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 168 :178-189
[29]   Energy and exergy analysis of a novel multi-generation system producing cooling, heating, power and pure water [J].
Mehr, A. S. ;
Zare, V. .
INTERNATIONAL JOURNAL OF EXERGY, 2014, 15 (02) :233-255
[30]   Energy and exergy investigation of a novel double effect hybrid absorption refrigeration system for solar cooling [J].
Bouaziz, Nahla ;
Lounissi, D. .
INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2015, 40 (39) :13849-13856