Determining total cost of ownership and peak efficiency index of dynamically rated transformer at the PV-power plant

被引:1
作者
Calil, Wilerson Venceslau [1 ,2 ]
Morozovska, Kateryna [3 ]
Laneryd, Tor [1 ]
da Costa, Eduardo Coelho Marques [2 ,4 ]
Salles, Mauricio Barbosa de Camargo [2 ]
机构
[1] Hitachi Energy, Vasteras, Sweden
[2] Univ Sao Paulo, Polytech Sch, Sao Paulo, Brazil
[3] KTH Royal Inst Technol, Stockholm, Sweden
[4] Univ Sao Paulo, Polytech Sch, Ave Prof Luciano Gualberto,380 Butanta, BR-05508010 Sao Paulo, SP, Brazil
关键词
Dynamic transformer rating; Power transformers; Smart-grid; Solar power; CAPABILITY; DISPATCH;
D O I
10.1016/j.epsr.2023.110061
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Dynamic rating of the transformer is a promising technology, which is suitable for various applications. Using dynamic rating for connecting renewable energy is believed to be beneficial for the economy and flexibility of the power system. However, to safely deploy such operation strategies, it is important to have more precise estimates for the total costs of owning such units and determine how effective such operation method is for a solar power plant. This study proposes a method for calculating total ownership costs (TOC) of dynamically rated transformers used for the connection of the solar power plant to the grid as well as analyzes its efficiency. The sensitivity analysis looks into the change in TOC and peak efficiency index (PEI) after considering reactive power dispatch. Results of this study also show how TOC, PEI, and load and no-load losses change depending on the transformer size.
引用
收藏
页数:13
相关论文
共 39 条
[1]   Flexible and sustainable scheduling of electric power grids: A dynamic line and transformer rating based approach under uncertainty condition [J].
Akhlaghi, M. ;
Moravej, Z. ;
Bagheri, A. .
SUSTAINABLE ENERGY GRIDS & NETWORKS, 2023, 36
[2]  
[Anonymous], 2012, IEEE Guide for Loading Mineral-Oil-Immersed Transformers and Step-Voltage Regulators, IEEE Std C5791-2011 Revis, P1, DOI DOI 10.1109/IEEESTD.2012.6166928
[3]   LOADING OF SUBSTATION ELECTRICAL-EQUIPMENT WITH EMPHASIS ON THERMAL CAPABILITY .2. APPLICATION [J].
BENKO, IS ;
COOPER, DE ;
CRAGHEAD, DO ;
NELSON, PQ .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1979, 98 (04) :1403-1419
[4]  
Bracale Antonio, 2019, 2019 International Conference on Clean Electrical Power (ICCEP), P611, DOI 10.1109/ICCEP.2019.8890172
[5]   Probabilistic risk-based management of distribution transformers by dynamic transformer rating [J].
Bracale, Antonio ;
Carpinelli, Guido ;
De Falco, Pasquale .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2019, 113 :229-243
[6]  
Chittock L, 2016, 8 IET INT C POWER EL, P1, DOI DOI 10.1049/CP.2016.0296
[7]   Assessment of dynamic transformer rating, considering current and temperature limitations [J].
Daminov, Ildar ;
Prokhorov, Anton ;
Caire, Raphael ;
Alvarez-Herault, Marie-Cecile .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 129 (129)
[8]   Real-time monitoring and dynamic thermal rating of power transmission circuits [J].
Douglass, DA ;
Edris, AA .
IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (03) :1407-1418
[9]   Optimal sizing of the wind farm and wind farm transformer using MILP and dynamic transformer rating [J].
Gomez, Andrea Molina ;
Morozovska, Kateryna ;
Laneryd, Tor ;
Hilber, Patrik .
INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 136
[10]  
IEC, 2017, IEC 60076-7:2017 Power transformers - Part 7: Loading guide for oil-immersed power transformers 60076 (7)