Predictive direct power control with phase-locked loop technique of three-level neutral point clamped inverter based shunt active power filter for power quality improvement

被引:8
|
作者
Debdouche, Naamane [1 ]
Benbouhenni, Habib [2 ]
Deffaf, Brahim [3 ]
Anwar, Guessabi [4 ]
Zarour, Laid [1 ]
机构
[1] Bros Mentouri Univ, Dept Elect Engn, Lab Elect Constantine LEC, Constantine 25000, Algeria
[2] Nisantasi Univ, Fac Engn & Architecture, Dept Elect & Elect Engn, Istanbul, Turkiye
[3] Univ Bejaia, Fac Technol, Dept Elect Engn, Lab Renewable Energies Mastering, Bejaia 06000, Algeria
[4] Ferhat Abbas Univ Setif1, Dept Elect Engn, Lab Automat Setif LAS, Setif, Algeria
关键词
phase-locked loop; predictive direct power control; space vector modulation; three-level shunt active power filter; SPACE-VECTOR MODULATION; FED INDUCTION GENERATOR; SAPF; DFIG; PWM; ELIMINATION; HARMONICS; ALGORITHM; STRATEGY; VOLTAGES;
D O I
10.1002/cta.3871
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this study, an improved anti-windup proportional-integral predictive direct power control strategy with a phase-locked loop (PLL) is proposed and applied to a three-level shunt active power filter (SAPF) neutral point clamped (NPC) inverter using space vector modulation (SVM) technique. The SAPF has to ensure sinusoidal waveforms and unity power factor in the grid side, by eliminating harmonic currents and compensating reactive power of the nonlinear loads. Active and reactive powers as well as the DC bus voltage controls are performed using anti-windup proportional and integral actions with a predictive algorithm, without a need for an exhaustive mathematical model. The control law is modulated using the SVM technique allowing fixed switching frequency and low power ripples. The performances of the suggested control have been verified through an electronic STM32F407 card under diverse and severe conditions. The obtained results confirmed the expected objectives in terms of current and voltage quality, robustness, and dynamic response. Direct power control approach featuring Phase-Locked Loop (PLL), which is implemented in a three-level Shunt Active Power Filter (SAPF) neutral point clamped (NPC) inverter utilizing space vector modulation (SVM) technique. The SAPF's objective is to guarantee grid-side sinusoidal waveforms and unity power factor, while mitigating harmonic currents, compensating reactive power, reducing Total Harmonic Distortion (THD) in the current, enhancing the longevity of the filtration system, and refining the system's dynamic response.image
引用
收藏
页码:3306 / 3340
页数:35
相关论文
共 50 条
  • [1] Simulation and real time implementation of predictive direct power control for three phase shunt active power filter using robust phase-locked loop
    Ouchen, Sabir
    Betka, Achour
    Gaubert, Jean-Paul
    Abdeddaim, Sabrina
    SIMULATION MODELLING PRACTICE AND THEORY, 2017, 78 : 1 - 17
  • [2] Synergetic control for three-level voltage source inverter-based shunt active power filter to improve power quality
    Deffaf, Brahim
    Farid, Hamoudi
    Benbouhenni, Habib
    Medjmadj, Slimane
    Debdouche, Naamane
    ENERGY REPORTS, 2023, 10 : 1013 - 1027
  • [3] A Dual-Function Instantaneous Power Theory for Operation of Three-Level Neutral-Point-Clamped Inverter-Based Shunt Active Power Filter
    Hoon, Yap
    Radzi, Mohd Amran Mohd
    Hassan, Mohd Khair
    Mailah, Nashiren Farzilah
    ENERGIES, 2018, 11 (06):
  • [4] Analysis and experimental evaluation of shunt active power filter for power quality improvement based on predictive direct power control
    Aissa, Oualid
    Moulahoum, Samir
    Colak, Ilhami
    Babes, Badreddine
    Kabache, Nadir
    ENVIRONMENTAL SCIENCE AND POLLUTION RESEARCH, 2018, 25 (25) : 24548 - 24560
  • [5] Performance improvement of shunt active power filter based on indirect control with a new robust phase-locked loop
    Chemidi, A.
    Benhabib, M. C.
    Bourouis, M. A.
    ELECTRICAL ENGINEERING & ELECTROMECHANICS, 2022, (04) : 51 - 56
  • [6] Power Calculation for Direct Power Control of Single-Phase Three-Level Rectifiers Without Phase-Locked Loop
    Ma, Junpeng
    Song, Wensheng
    Jiao, Shilei
    Zhao, Junhui
    Feng, Xiaoyun
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2016, 63 (05) : 2871 - 2882
  • [7] Dynamic Performance Improvement of Three Phase Shunt Active Power Filter using Predictive Direct Power Control
    Ouchen, Sabir
    Steinhart, Heinrich
    Benbouzid, Mohamed
    Blaabjerg, Frede
    Betka, Achour
    2018 20TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE'18 ECCE EUROPE), 2018,
  • [8] Analysis and experimental evaluation of shunt active power filter for power quality improvement based on predictive direct power control
    Oualid Aissa
    Samir Moulahoum
    Ilhami Colak
    Badreddine Babes
    Nadir Kabache
    Environmental Science and Pollution Research, 2018, 25 : 24548 - 24560
  • [9] Three Phase Three Level Inverter Based Shunt Active Power Filter
    Ajay, Chandana
    Yasaswini, Jamma
    Indira, Komma
    Dinesh, L.
    2015 INTERNATIONAL CONFERENCE ON ELECTRICAL, ELECTRONICS, SIGNALS, COMMUNICATION AND OPTIMIZATION (EESCO), 2015,
  • [10] Improved Synchronized SVPWM Strategy for High-Power Three-Level Active Neutral Point Clamped Traction Inverter
    Zhao, Mutian
    Ge, Qiongxuan
    Zhu, Jinquan
    Wang, Ke
    Zhang, Bo
    Zhao, Lu
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2025, 40 (02) : 3189 - 3209