Response surface modeling and optimization scheme of an internally cooled liquid desiccant air conditioning system

被引:12
作者
Zhang, Yanling [1 ,2 ]
Zhang, Hao [1 ]
Yang, Hongxing [2 ]
Chen, Yi [3 ]
Leung, Chun Wah [1 ]
机构
[1] Hong Kong Polytech Univ, Sch Profess Educ & Execut Dev, Hong Kong, Peoples R China
[2] Hong Kong Polytech Univ, Dept Bldg Environm & Energy Engn, Renewable Energy Res Grp, Hong Kong, Peoples R China
[3] Jimei Univ, Coll Marine Equipment & Mech Engn, Xiamen, Peoples R China
关键词
Liquid desiccant dehumidification; Indirect evaporative cooling; Response surface method; System optimization; COOLING SYSTEM; PERFORMANCE; BUILDINGS; DESIGN;
D O I
10.1016/j.jobe.2023.107371
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Applying an internally cooled liquid desiccant air conditioning system (LDAC) is a promising energy-saving and emission-reduction scheme for hot and humid areas. This research investigates the application of an internally cooled LDAC for performance enhancement in hot and humid areas like Hong Kong. The combined system integrates liquid desiccant dehumidification (LDD) and regenerative indirect evaporative cooling (RIEC) without a power-intensive compressor. The internally cooled LDD removes latent heat from the hot and humid air before the RIEC cools it. To ensure efficient energy utilization, the LDD captures the exhaust air to assist in the dehumidification and initial cooling of the fresh air, which alleviates the efficiency deterioration of the desiccant. An all-fresh air system is used for better indoor air quality. To optimize the performance of a system with many influencing parameters, the response surface method (RSM) and multi-objective optimization are used to optimize and assess the potential and performance of the system. The system cooling capacity (C), latent heat removal rate (Qd), and dehumidification efficiency (& eta;d) are used as the optimization objectives. The response surface model and desirability function approach optimize six critical parameters, achieving a 7.6% improvement in dehumidification performance with low airspeed (1.5 m/s) and high desiccant concentration (40%) during high-humidity months. Increasing the extraction ratio of the RIEC by 20% in warmer months enhances the peak cooling capacity by 23.6%. This research contributes to implementing internally cooled LDAC systems and provides insights into optimizing monthly operation patterns in hot and humid regions.
引用
收藏
页数:16
相关论文
共 39 条
[1]   Numerical investigation of the heat and mass transfer process within a cross-flow indirect evaporative cooling system for hot and humid climates [J].
Adam, Abdalazeem ;
Han, Dong ;
He, Weifeng ;
Amidpour, Majid ;
Zhong, Hong .
JOURNAL OF BUILDING ENGINEERING, 2022, 45
[2]   Eco-driving: the role of feedback in reducing emissions from everyday driving behaviours [J].
Allison, Craig K. ;
Stanton, Neville A. .
THEORETICAL ISSUES IN ERGONOMICS SCIENCE, 2019, 20 (02) :85-104
[3]  
[Anonymous], 2017, AMVAREIVIZIA5E SIC 6, P122
[4]  
Ashrae, 2005, ASHRAE HDB FUND
[5]   A fresh (air) look at ventilation for COVID-19: Estimating the global energy savings potential of coupling natural ventilation with novel radiant cooling strategies [J].
Aviv, Dorit ;
Chen, Kian Wee ;
Teitelbaum, Eric ;
Sheppard, Denon ;
Pantelic, Jovan ;
Rysanek, Adam ;
Meggers, Forrest .
APPLIED ENERGY, 2021, 292
[6]   Building and environmental factors that influence bacterial and fungal loading on air conditioning cooling coils [J].
Bakker, A. ;
Siegel, J. A. ;
Mendell, M. J. ;
Peccia, J. .
INDOOR AIR, 2018, 28 (05) :689-696
[7]  
C.a.S. Department, 2021, HONG KONG EN STAT AN
[8]   Investigation on solar assisted liquid desiccant dehumidifier and evaporative cooling system for fresh air treatment [J].
Chen, Yi ;
Yang, Hongxing ;
Luo, Yimo .
ENERGY, 2018, 143 :114-127
[9]   Energy saving potential of hybrid liquid desiccant and evaporative cooling air-conditioning system in Hong Kong [J].
Chen, Yi ;
Luo, Yimo ;
Yang, Hongxing .
8TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY (ICAE2016), 2017, 105 :2125-2130
[10]   Parameter sensitivity analysis and configuration optimization of indirect evaporative cooler (IEC) considering condensation [J].
Chen, Yi ;
Yang, Hongxing ;
Luo, Yimo .
APPLIED ENERGY, 2017, 194 :440-453