Experimental Investigation of Energy and Exergy Assessment of Vapor Compression Refrigeration Unit Enhanced via Encapsulated Phase Change Material

被引:3
作者
Ismail, Mohamed [1 ,2 ]
Hassan, Hamdy [1 ,3 ]
机构
[1] Suez Univ, Fac Engn, Mech Engn Dept, Suez 41522, Egypt
[2] Egypt Japan Univ Sci & Technol E JUST, Energy Resources Engn Dept, Borg Elarab Alexandria EJUST, Alexandria 21934, Egypt
[3] Assiut Univ, Fac Engn, Mech Power Engn Dept, Assiut 71515, Egypt
关键词
encapsulated phase change material; energy exergy; vapor compression refrigeration unit; NUMERICAL-ANALYSIS; STORAGE; PERFORMANCE; CONDENSER; SYSTEMS;
D O I
10.1002/ente.202300956
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Energy and exergy performance of simple vapor compression refrigeration unit is investigated experimentally with and without coupling heat exchanger of phase change material before the condenser. The hot outside air is cooled before entering the condenser throughout the day by flowing over the cooled phase change material structure that previously solidified during nighttime. Phase change material SP24 is employed because its melting/freezing range is suitable for most selected countries' climates. An experimental set-up of an air-phase change material heat exchanger coupled with the unit is constructed to examine its performance, including pressure-enthalpy curve, coefficient of performance, exergy performance, and power consumption including inflow air temperatures and flow rates impacts. Results affirm that the coefficient of performance, cooling capacity, power usage, and exergy destruction are improved by using phase change material. Compared to the unmodified unit, the maximum percentage of saved power and exergy destruction enhancement for the modified refrigeration unit with phase change material is about 8.8% and 10%, respectively. The maximum coefficient of performance and exergy efficiency rise is about 15.1% and 14.2%, respectively. Increasing the temperature differential across the phase change material heat exchanger, either by increasing inlet temperature or decreasing airflow, enhances the refrigeration unit power saving. Energy and exergy performance of simple vapor compression refrigeration unit (VCRU) is investigated experimentally with and without coupling heat exchanger of phase change material (PCM SP24) before the condenser. The study examines the VCRU performance, including pressure-enthalpy curve, COP, exergy analysis, and power consumption with and without the PCM.image (c) 2023 WILEY-VCH GmbH
引用
收藏
页数:11
相关论文
共 32 条
  • [1] Investigation on the effect of thermal properties by change in materials of the air conditioner condenser tube using simulation
    Abishai, L. Daniel
    Surejlal, M. E.
    Harish, S. Sri
    Prabu, S. Senthur
    [J]. MATERIALS TODAY-PROCEEDINGS, 2021, 45 : 2671 - 2677
  • [2] Heat transfer performance evaluation in circular tubes via internal repeated ribs with entropy and exergy analysis
    Ahmed, Sayed Ahmed E. Sayed
    Ibrahim, Emad Z.
    Ibrahim, Mostafa M.
    Essa, Mohamed A.
    Abdelatief, Mohamed A.
    El-Sayed, Mohamed N.
    [J]. APPLIED THERMAL ENGINEERING, 2018, 144 : 1056 - 1070
  • [3] New solution method for latent energy storage and thermoeconomic optimization for an air conditioning system
    Akbari, A. D.
    Talati, F.
    Mahmoudi, S. M. S.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 109 : 12 - 24
  • [4] Numerical analysis of an air condenser working with the refrigerant fluid R407C
    Aprea, Ciro
    Maiorino, Angelo
    [J]. APPLIED THERMAL ENGINEERING, 2007, 27 (14-15) : 2592 - 2599
  • [5] Optimum placement of condensing units of split-type air-conditioners by numerical simulation
    Avara, Abdollah
    Daneshgar, Ehsan
    [J]. ENERGY AND BUILDINGS, 2008, 40 (07) : 1268 - 1272
  • [6] Cengel Y.A., 2011, THERMODYNAMICS ENG A, V5
  • [7] Coleman HW, 1989, EXPT UNCERTAINTY ANA
  • [8] Energy, exergy, and economic assessment of thermal regulation of PV panel using hybrid heat pipe-phase change material cooling system
    Gad, Ramadan
    Mahmoud, Hatem
    Ookawara, Shinichi
    Hassan, Hamdy
    [J]. JOURNAL OF CLEANER PRODUCTION, 2022, 364
  • [9] Second law analysis of an automotive air conditioning system using HFO-1234yf, an environmentally friendly refrigerant
    Golzari, Soudabeh
    Kasaeian, Alibakhsh
    Daviran, Samaneh
    Mahian, Omid
    Wongwises, Somchai
    Sahin, Ahmet Z.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2017, 73 : 134 - 143
  • [10] The effect of using tubes filled with phase change materials in the air conditioning system of a residential building
    Hai, Tao
    Sajadi, S. Mohammad
    Zain, Jasni Mohamad
    El-Shafay, A. S.
    Sharifpur, Mohsen
    [J]. JOURNAL OF BUILDING ENGINEERING, 2022, 49