Investigation of partial discharge characteristics in XLPE cable insulation under increasing electrical stress

被引:9
作者
Choudhary, Maninder [1 ]
Shafiq, Muhammad [2 ]
Kiitam, Ivar [1 ]
Palu, Ivo [1 ]
Hassan, Waqar [3 ]
Singh, Praveen Prakash [1 ]
机构
[1] Tallinn Univ Technol, Dept Elect Power Engn & Mechatron, Tallinn, Estonia
[2] Florida State Univ, Tallahassee, FL USA
[3] Univ Tenaga Nas, Inst Power Engn IPE, Kajang, Malaysia
关键词
XLPE cable; Partial discharge measurement; PD characteristics; Regression analysis; CLASSIFICATION;
D O I
10.1016/j.engfailanal.2024.108006
中图分类号
TH [机械、仪表工业];
学科分类号
0802 ;
摘要
Insulation degradation in power components is a looming issue that can have a significant impact on the reliability of power system if not attended timely. Partial discharge (PD) diagnostics is a key technique used for the condition monitoring and health assessment of insulation. Inception of PD is a primary indicator which shows degradation and decreased local dielectric strength of the insulation. PD magnitude can increase with time and level of stress, which may result in failure of insulation. This article investigates the behavior of PD characteristics in a medium voltage (MV) cross-linked polyethylene (XLPE) cable sample, containing a defect at the cable termination, under elevated electrical stresses. PD behavior is studied by investigating the key PD characteristics, such as partial discharge inception voltage (PDIV), phase of occurrence (phi), mean amplitude (V-mean), pulse repetition rate (PRR), and phase span (phi(span)). These quantities are extracted from a phase-resolved partial discharge (PRPD) pattern using a pulse detection algorithm. Later, these characteristics are analyzed in correlation with the electrical stress. Various regression models are implemented and compared to find the best fit model that represents trending attributes of major PD characteristics. The presented study can be used as an effective process to analyze the measured PD data for evaluation of the insulation condition in the power components.
引用
收藏
页数:14
相关论文
共 30 条
[1]  
[Anonymous], 1977, Wiley Series in Probability and Mathematical Statistics
[2]  
[Anonymous], 2015, Consolidated Version. High-Voltage Test Techniques-Partial Discharge Measurements
[3]   Partial discharges - Their mechanism, detection and measurement [J].
Bartnikas, R .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2002, 9 (05) :763-808
[4]   Fundamentals of partial discharge in the context of field cable testing [J].
Boggs, S ;
Densley, J .
IEEE ELECTRICAL INSULATION MAGAZINE, 2000, 16 (05) :13-18
[5]   Investigations on Leakage Current and Phase Angle Characteristics of Porcelain and Polymeric Insulator under Contaminated Conditions [J].
Chandrasekar, S. ;
Kalaivanan, C. ;
Cavallini, Andrea ;
Montanari, Gian Carlo .
IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2009, 16 (02) :574-583
[6]   The coefficient of determination R-squared is more informative than SMAPE, MAE, MAPE, MSE and RMSE in regression analysis evaluation [J].
Chicco, Davide ;
Warrens, Matthijs J. ;
Jurman, Giuseppe .
PEERJ COMPUTER SCIENCE, 2021,
[7]   Study on the Progression of Surface Partial Discharge in Power Cables [J].
Choudhary, Maninder ;
Shafiq, Muhammad ;
Kiitam, Ivar ;
Palu, Ivo ;
Taklaja, Paul .
2022 IEEE 63TH INTERNATIONAL SCIENTIFIC CONFERENCE ON POWER AND ELECTRICAL ENGINEERING OF RIGA TECHNICAL UNIVERSITY (RTUCON), 2022,
[8]   A Review of Aging Models for Electrical Insulation in Power Cables [J].
Choudhary, Maninder ;
Shafiq, Muhammad ;
Kiitam, Ivar ;
Hussain, Amjad ;
Palu, Ivo ;
Taklaja, Paul .
ENERGIES, 2022, 15 (09)
[9]  
Europacable, 2014, An Introduction to Medium and Low Voltage Cables in Distribution Networks as support of Smart Grids
[10]   Partial Discharge Experimental Study for Medium Voltage DC Cables [J].
Feng, Xianyong ;
Xiong, Qing ;
Gattozzi, Angelo L. ;
Hebner, Robert E. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (02) :1128-1136