Single-ended protection method for hybrid HVDC transmission line based on transient voltage characteristic frequency band

被引:14
|
作者
Shu, Hongchun [1 ]
Wang, Shixin [1 ]
Lei, Shunguang [2 ]
机构
[1] Kunming Univ Sci & Technol, Yunnan Key Lab Green Energy Elect Power Measureme, Kunming 650500, Yunnan, Peoples R China
[2] Harbin Inst Technol, Sch Elect Engn & Automat, Harbin 150001, Heilongjiang, Peoples R China
基金
中国国家自然科学基金;
关键词
Boundary frequency characteristics; Characteristic frequency band; Hybrid HVDC; Single-end protection; Transient voltage; IDENTIFICATION; CONVERTER; SCHEME;
D O I
10.1186/s41601-023-00301-1
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Hybrid high-voltage direct current (HVDC) transmission has the characteristic of long transmission distance, complex corridor environment, and rapid fault evolution of direct current (DC) lines. As high fault current can easily cause irreversible damage to power devices, rapid and reliable line protection and isolation are necessary to improve the security and reliability of hybrid HVDC transmission system. To address such requirement, this paper proposes a single-ended protection method based on transient voltage frequency band characteristics. First, the frequency characteristics of the smoothing reactor, DC filter, and DC line are analyzed, and the characteristic frequency band is defined. A fault criterion is then constructed based on the voltage characteristic frequency band energy, and faulty pole selection is performed according to the fault voltage characteristic frequency band energy ratio. The proposed protection method is verified by simulation, and the results show that it can rapidly and reliably identify internal and external faults, accurately select faulty poles without data communication synchronization, and has good fault-resistance and anti-interference performance.
引用
收藏
页数:11
相关论文
共 50 条
  • [31] Single-ended Fault Location of Hybrid MMC-HVDC System Based on Active Detection
    Song G.
    Hou J.
    Guo B.
    Dianwang Jishu/Power System Technology, 2021, 45 (02): : 730 - 740
  • [32] Research on Transient Protection of HVDC Transmission Line Based on Wavelet Energy
    Yang, Dongrui
    Han, Kunlun
    Dai, Yu
    2021 IEEE IAS INDUSTRIAL AND COMMERCIAL POWER SYSTEM ASIA (IEEE I&CPS ASIA 2021), 2021, : 1071 - 1074
  • [33] Study of Single-ended Traveling-wave Protection for Transmission Line Unsymmetrical Grounded Faults
    Duan Jiandong
    Wang Li
    Tong Xiangqian
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 1074 - 1077
  • [34] A single-ended traveling wave based fault location method using DWT in hybrid parallel HVAC/HVDC overhead transmission lines on the same tower
    Fayazi, Mohammad
    Joorabian, Mahmood
    Saffarian, Alireza
    Monadi, Mehdi
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 220
  • [35] Single-ended protection method of double-ended weak-infeed AC tie-line based on opposite-side voltage consistency analysis
    Li, Botong
    Li, Jianing
    Wang, Shuai
    Chen, Xiaolong
    Dong, Yuejin
    ENERGY REPORTS, 2024, 12 : 1109 - 1120
  • [36] The Half-Sine Method: A New Accurate Location Method Based on Wavelet Transform for Transmission-Line Protection from Single-Ended Measurements
    Martin Arroyo, Susana
    Garcia-Gracia, Miguel
    Montanes, Antonio
    ENERGIES, 2019, 12 (17)
  • [37] Computationally Effective Frequency Transient-Based Transmission Line Protection for Multiterminal VSC-HVdc
    Lan, Tongkun
    Xiao, Hao
    Li, Yinhong
    Chen, Jinfu
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2022, 18 (09) : 5925 - 5935
  • [38] Single-ended DC line protection scheme based on first peak time of current-limiting reactor voltage
    Wei, Xiuyan
    Zou, Guibin
    Chen, Chaochao
    Zhang, Shuo
    Zhou, Chenghan
    Song, Shenglan
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 150
  • [39] A Transient Power Protection Principle for Hybrid Bipolar DC Transmission Line Based on LCC-HVDC and VSC-HVDC
    Gao, Shuping
    Zhu, Hangjian
    Niu, Dan
    Zhang, Baohui
    Song, Guobing
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 2635 - 2641
  • [40] A Novel Segmented-COV-Based Single-Ended Line Protection Algorithm for the Multiterminal MMC-HVDC System With No Boundary Reactor
    He, Jiawei
    Sheng, Yaru
    Li, Bin
    Li, Ye
    Zhou, Bohao
    IEEE TRANSACTIONS ON INDUSTRIAL INFORMATICS, 2024, 20 (04) : 5658 - 5670