Investigation on compatibility of insulating materials in on-load tap changer with insulating oil

被引:0
|
作者
Chen, Chen [1 ]
Li, Gang [2 ]
Zhao, Xuetong [1 ]
He, Binlang [1 ]
Gao, Yu [1 ]
Liao, Ruijin [1 ]
机构
[1] Chongqing Univ, State Key Lab Power Transmission Equipment & Syst, Chongqing, Peoples R China
[2] China Elect Power Res Inst, Beijing, Peoples R China
基金
国家重点研发计划;
关键词
On-load tap changer; Compatibility test; Solid insulating materials;
D O I
10.1109/CE/DP5414.2023.10410466
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The insulation system of On-load tap changer (OLTC) is composed of insulating oil and the solid insulating materials in OLTC. The compatibility of solid insulating materials in OLTC with mineral insulating oil is one of the most important factors to decide the long-term reliable operation of OLTC. However, the compatibility of OLTC insulating components with mineral insulating oil is seldom studied. In this work, the effect of insulating materials, such as Epoxy Phenolic Glass Cloth Laminates (EPGCL3248), Epoxy Glass Fiber (EGF), Reinforced Nylon (PA66), Polyformaldehyde (POM) on the electrical and physicochemical properties of insulating oil were analyzed. The solid insulating materials were immersed in 800 mL insulating oil separately, and aged at 90 degrees C, 100 degrees C, 110 degrees C, and 130 degrees C. The aging time is 20 h, 41 h, 82 h, and 164 h, respectively. After the thermal aging, the water content, breakdown voltage, dielectric loss and acidity of insulating oil samples were tested, and the compatibility between the insulating oil and the solid insulating materials was analyzed. Among the solid insulating materials used in OLTC, the Nylon PA66 exhibits poor compatibility with mineral oil. The research results provide useful advises for the selection, optimization and replacement of OLTC solid insulating materials.
引用
收藏
页数:4
相关论文
共 50 条
  • [31] On-Load Tap-Changer Control by a Fuzzy Logic Controller
    Choukri, Tarbi
    Chekenbah, Hamid
    Lasri, Rafik
    Bouhorma, Mohammed
    Maataoui, Yassir
    PROCEEDINGS OF 2019 IEEE 4TH WORLD CONFERENCE ON COMPLEX SYSTEMS (WCCS' 19), 2019, : 79 - 84
  • [32] A Segmented Preprocessing Method for the Vibration Signal of an On-Load Tap Changer
    Shang, Rongyan
    Peng, Changqing
    Fang, Ruiming
    ELECTRONICS, 2021, 10 (02) : 1 - 12
  • [33] Reverse action of on-load tap changer in association with voltage collapse
    Ohtsuki, Hiroshi
    Yokoyama, Akihiko
    Sekine, Yasuji
    IEEE Transactions on Power Systems, 1991, 6 (02) : 300 - 306
  • [34] Power system voltage stability affected by on-load tap changer
    Peng, Zhiwei
    Hu, Guogen
    Han, Zhenxiang
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 18 (06): : 408 - 412
  • [35] Improvement in the performance of on-load tap changer transformers operating in series
    Smith, CA
    Redfern, MA
    Potts, S
    2003 IEEE POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-4, CONFERENCE PROCEEDINGS, 2003, : 1905 - 1910
  • [36] Power system voltage stability affected by on-load tap changer
    Peng, Zhiwei
    Hu, Guogen
    Han, Zhenxiang
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 1998, 18 (06): : 408 - 412
  • [37] REVERSE ACTION OF ON-LOAD TAP CHANGER IN ASSOCIATION WITH VOLTAGE COLLAPSE
    OHTSUKI, H
    YOKOYAMA, A
    SEKINE, Y
    IEEE TRANSACTIONS ON POWER SYSTEMS, 1991, 6 (01) : 300 - 306
  • [38] Diagnosis of Degradation Effects of On-load Tap Changer in Power Transformers
    Jongen, Rogier
    Gulski, Edward
    Siodla, Krzysztof
    Parciak, Jaroslaw
    Erbrink, Jur
    2014 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2014,
  • [39] Acoustic emission signal analysis of On-Load Tap Changer (OLTC)
    Shanker, T. Bhavani
    Nagamani, H. N.
    Punekar, Gururaj S.
    2013 IEEE 1ST INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2013, : 347 - 352
  • [40] A STUDY ON THE CONDITION OF REVERSE CONTROL ACTION OF TAP CHANGER IN A SINGLE ON-LOAD TAP CHANGER POWER-SYSTEM
    YORINO, N
    FUNAHASHI, A
    SASAKI, H
    KUBOKAWA, J
    ELECTRICAL ENGINEERING IN JAPAN, 1994, 114 (07) : 44 - 55