Thermodynamic analysis of usage of R134a, R1234yf, R450A, R513A and R515B in the mechanical vapor compression refrigeration system

被引:0
作者
Bilen, Kemal [1 ]
Isik, Bilal [1 ]
Dagidir, Kayhan [2 ]
Arcaklioglu, Erol [1 ]
机构
[1] Ankara Yildirim Beyazit Univ, Fac Engn & Nat Sci, Dept Mech Engn, TR-06010 Ankara, Turkiye
[2] Tarsus Univ, Fac Engn, Dept Mech Engn, TR-33400 Mersin, Turkiye
来源
JOURNAL OF THE FACULTY OF ENGINEERING AND ARCHITECTURE OF GAZI UNIVERSITY | 2024年 / 39卷 / 01期
关键词
R134a; Global warming potential; Alternative refrigerants; Refrigeration system; Thermodynamic analysis; LOWER GWP; REPLACEMENT; PERFORMANCE;
D O I
暂无
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
R134a, which is used as a working fluid in Vapor Compression Refrigeration Systems (VCRS), is one of the refrigerants that is planned to be discontinued the usage due to the global warming. For this reason, researchers have tended to developing alternatives to R134a. In this context, in this study, the usage of R134a and its alternatives R1234yf, R450A, R513A, and R515B refrigerants were theoretically examined with the help of a theoretical model developed in the Engineering Equation Solver (EES) program using experimental data in terms of first and second laws of thermodynamics in a mechanical vapor compression refrigeration system. Analyses were performed for constant cooling capacity at various evaporation and condensation temperatures. In this study, the effects of the refrigerant type on the compressor power, heat rejection rate from the condenser, Coefficient of Performance (COP), second law efficiency, and mass flow rate of the refrigerant were determined. In addition, the results obtained under the same conditions for R134a and its alternatives were compared. As a result, compressor power increased by 5.62% for R1234yf, 2.35% for R450A, 3.41% for R513A, and 2.88% for R515B compared to R134a. Thus, it was observed that COP decreased by 5.32% for R1234yf, 2.30% for R450A, 3.30% for R513A, and 2.80% for R515B compared to R134a. Similarly, it was observed that the second law efficiency decreased by 5.32% in case of the usage of R1234yf, 2.30% in case of the usage of R450A, 3.29% in case of the usage of R513A, and 2.80% in case of the usage of R515B compared to R134a. Hence, it has been determined that the closest refrigerant to R134a in terms of the COP and the second law efficiency is R450A.
引用
收藏
页码:161 / 175
页数:15
相关论文
共 50 条
  • [31] Comparative Energetic, Exergetic, Environmental and Enviroeconomic Analysis of Vapour Compression Refrigeration Systems Using R515B as Substitute for R134a
    Yildirim, Ragip
    Sahin, Arzu Sencan
    Dikmen, Erkan
    INTERNATIONAL JOURNAL OF THERMODYNAMICS, 2022, 25 (01) : 125 - 133
  • [32] Thermodynamic Analysis of a Refrigeration System Operating with R1234yf Refrigerant
    Oruc, Vedat
    Devecioglu, Atilla G.
    ROLE OF EXERGY IN ENERGY AND THE ENVIRONMENT, 2018, : 113 - 124
  • [33] Drop-in analysis of R450A and R513A as low-GWP alternatives to R134a in a water-to-water heat pump
    Molinaroli, Luca
    Lucchini, Andrea
    Colombo, Luigi Pietro Maria
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 135 : 139 - 147
  • [34] Experimental and Numerical Studies on an Automobile Air Conditioning System With the Refrigerants R134a, R1234yf, and R1234ze(E)
    Gurudatt, H. M.
    Narasimham, G. S. V. L.
    Sadashive Gowda, B.
    JOURNAL OF THERMAL SCIENCE AND ENGINEERING APPLICATIONS, 2024, 16 (01)
  • [35] R1234yf and R744 as alternatives to R134a at mobile air conditioners
    Onan C.
    Erdem S.
    Journal of Energy Systems, 2021, 5 (04): : 284 - 295
  • [36] Performance comparison of ejectors in ejector-based refrigeration cycles with R1234yf, R1234ze(E) and R134a
    Li, Shizhen
    Liu, Yingxin
    Liu, Yanjun
    Zhang, Jingzhi
    ENVIRONMENTAL SCIENCE AND POLLUTION RESEARCH, 2021, 28 (40) : 57166 - 57182
  • [37] Performance analysis of refrigerants R134a and R1234yf two stage compression cycle with two condensers
    Wang, Hongli
    Tang, Qilong
    Jia, Ning
    Zhang, Qinghua
    MATERIALS PROCESSING AND MANUFACTURING III, PTS 1-4, 2013, 753-755 : 2778 - +
  • [38] Experimental study of R1234yf as a drop-in replacement for R134a in an oil-free refrigeration system
    Li, Zhaohua
    Liang, Kun
    Jiang, Hanying
    APPLIED THERMAL ENGINEERING, 2019, 153 : 646 - 654
  • [39] Experimental Evaluation of an Automotive Heat Pump System with R1234yf as an Alternative to R134a
    Direk, Mehmet
    Yuksel, Fikret
    ARABIAN JOURNAL FOR SCIENCE AND ENGINEERING, 2020, 45 (02) : 719 - 728
  • [40] EMPIRICAL CORRELATIONS FOR THE PERFORMANCE OF AN AUTOMOTIVE AIR CONDITIONING SYSTEM USING R1234yf AND R134a
    Aral, Mumin Celil
    Hosoz, Murat
    Subermanto, Mukhamad
    ISI BILIMI VE TEKNIGI DERGISI-JOURNAL OF THERMAL SCIENCE AND TECHNOLOGY, 2017, 37 (01) : 127 - 137