Magnetic state balance technology of transformer based on magnetic field modulation strategy

被引:0
作者
Chen, Zhiwei [1 ]
Ye, Jiaojiao [1 ]
Liu, Xin [1 ,2 ]
Zhou, Qipei [1 ]
Cheng, Tingli [1 ]
Ding, Lijian [1 ]
机构
[1] Hefei Univ Technol, Sch Elect Engn & Automat, Hefei 230009, Peoples R China
[2] State Grid Anhui Elect Power Co Ltd, Hefei, Peoples R China
基金
中国国家自然科学基金;
关键词
Transformer core; Temperature raise; Magnetic state; Modulation; INRUSH CURRENT; POWER TRANSFORMERS; MITIGATION; PLACEMENT;
D O I
10.1016/j.ijepes.2023.109128
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The transformer core is easy to saturate in the half cycle under the influence of the remanent magnetism (RM) and the bias magnetism (BM), then the excitation surge current (ESC) and the DC bias will be generated, causing the transformer excitation current (TEC) distort, leading the winding temperature rise and decreasing the transformer insulation. In this paper, one kind of magnetic balance modulation method for the transformer core is proposed. TEC distortion could be improved by adjusting the transformer magnetic field distribution. Firstly, the AC/DC/DC converter was designed and connected to the auxiliary winding according to the hybrid trans -former topology. Second, the specific modulated signal for the magnetic field modulation (MFM) was generated and output through the AC/DC/DC. The modulated forward and reverse DC current or the stepped AC current would be injected into the transformer winding to achieve the balance of the transformer magnetic state. Finally, in order to verify the correctness of the design scheme, a 1 kVA/380 V/220 V/38 V transformer experiment platform was built. The results showed that this proposed MFM strategy could effectively solve the impact of the transformer ESC, DC bias and prolong the transformer service life, which provides a novel idea to solve the transformer fault.
引用
收藏
页数:11
相关论文
共 15 条
  • [1] Mitigation of transformer-energizing inrush current using grid-connected photovoltaic system
    Ahmed, Abdelsalam A.
    Abdelsalam, Hany A.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 79 : 312 - 321
  • [2] A GDSC-Based Technique to Distinguish Transformer Magnetizing From Fault Currents
    Batista, Ygo Neto
    de Souza, Helber Elias Paz
    dos Santos Neves, Francisco de Assis
    Dias Filho, Roberto Feliciano
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (02) : 589 - 599
  • [3] Controlled energization procedures of power transformers
    Bejmert, Daniel
    Kereit, Matthias
    Boehme, Klaus
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2022, 135
  • [4] Transient DC Bias Elimination of Dual-Active-Bridge DC-DC Converter With Improved Triple-Phase-Shift Control
    Bu, Qinglei
    Wen, Huiqing
    Wen, Jiacheng
    Hu, Yihua
    Du, Yang
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2020, 67 (10) : 8587 - 8598
  • [5] Optimal Placement of GIC Blocking Devices for Geomagnetic Disturbance Mitigation
    Etemadi, Amir H.
    Rezaei-Zare, Afshin
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2014, 29 (06) : 2753 - 2762
  • [6] A new method to identify inrush current based on error estimation
    He, Benteng
    Zhang, Xuesong
    Bo, Zhiqian Q.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2006, 21 (03) : 1163 - 1168
  • [7] Distinguishing Internal Winding Faults From Inrush Currents in Power Transformers Using Jiles-Atherton Model Parameters Based on Correlation Coefficient
    Huang, Sy-Ruen
    Chen, Hong-Tai
    Wu, Chueh-Cheng
    Guan, Chau-Yu
    Cheng, Chiang
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2012, 27 (02) : 548 - 553
  • [8] A start strategy for synchronized connection of MMCs to an AC system
    Li, Haifeng
    Liu, Chongru
    Li, Gengyin
    Guo, Qi
    Luo, Haiyun
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 69 : 380 - 390
  • [9] Off-line coupled simulation method for transformer performance assessment under DC bias condition
    Li, Jinlong
    Li, Jinzhong
    Li, Gang
    Hu, Xiaobo
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 125
  • [10] Optimal Blocking Device Placement for Geomagnetic Disturbance Mitigation
    Liang, Yi
    He, Di
    Zhu, Hao
    Chen, Deming
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (06) : 2219 - 2231