A Study on the Simulation and Experiment of Evaporative Condensers in an R744 Air Conditioning System

被引:0
|
作者
Dang, Thanhtrung [1 ]
Nguyen, Hoangtuan [1 ]
机构
[1] HCMC Univ Technol & Educ, Dept Thermal Engn, Ho Chi Minh City 71307, Vietnam
关键词
evaporative condenser; heat transfer; R744; subcritical; air conditioning; REFRIGERATION CYCLE; CO2; PERFORMANCE; WORKING;
D O I
10.3390/mi14101826
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
The heat transfer characteristics of evaporative condensers in an R744 air conditioning system were evaluated using the numerical and the experimental methods. Two configurations of condensers were studied: Case 1 with five layers of tubes and Case 2 with eight layers of tubes. In order to evaluate the heat transfer characteristics, the temperature field, the phase change, the pressure distribution, and thermodynamic parameters were considered. For Case 2, it indicated the capability of R744 condensation from the superheated status to the liquified status by analyzing the outlet temperature of the condenser changed from 28.7 degrees C to 30.3 degrees C with a change in condensation pressure from 72.6 bar to 68.5 bar. In this study, R744 mass flow rate increases from 14.34 kg/h to 46.08 kg/h, and the pressure drop also increases from 0.23 bar to 0.47 bar for the simulation and 0.4 bar to 0.5 bar for the experiment, respectively. The results indicate that the five-layer configuration causes a higher pressure drop and lower COP than those obtained from the eight-layer one (splitting into two sets for smaller pressure drop). Furthermore, the evaporative condensers using mini tubes that are flooded in the cooling water tank are suitable for the subcritical R744 air conditioning system. In addition, the results obtained from the experimental data are in good agreement with those obtained from the numerical results, with a deviation of less than 5%.
引用
收藏
页数:15
相关论文
共 50 条
  • [31] Experimental study of the refrigeration cycle performance for the R744/R290 mixtures
    Niu, Baolian
    Zhang, Yufeng
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2007, 30 (01): : 37 - 42
  • [32] STUDY ON EVAPORATIVE COOLING ASSISTED DESICCANT AIR CONDITIONING SYSTEM FOR LIVESTOCK APPLICATION IN PAKISTAN
    Niaz, Hassan
    Sultan, Muhammad
    Khan, Alamgir A.
    Miyazaki, Takahiko
    Feng, Yongqiang
    Khan, Zahid M.
    Niaz, Yasir
    Mahmood, Muhammad H.
    Ali, Imran
    Imran, Muhammad A.
    FRESENIUS ENVIRONMENTAL BULLETIN, 2019, 28 (11A): : 8623 - 8633
  • [33] R744 ejector simulation based on homogeneous equilibrium model and its application in trans-critical refrigeration system
    Liu, Guangdi
    Wang, Zheng
    Zhao, Hongxia
    Abdulwahid, AL-hasan Ali
    APPLIED THERMAL ENGINEERING, 2022, 201
  • [34] Studies on an R-744 based air conditioning system operating near critical point
    Devendra Kumar Sharma
    Aaditya Saikiran Pegallapati
    Maddali Ramgopal
    Sādhanā, 48
  • [36] A numerical simulation on heat transfer process of the cascade heat exchanger in a cascade refrigeration system using R134a/R744
    Hoangtuan Nguyen
    Thanhtrung Dang
    Pracha Yeunyongkul
    International Journal of Air-Conditioning and Refrigeration, 33 (1)
  • [37] Study on a novel thermally driven air conditioning system with desiccant dehumidification and regenerative evaporative cooling
    La, Dong
    Dai, Yanjun
    Li, Yong
    Ge, Tianshu
    Wang, Ruzhu
    BUILDING AND ENVIRONMENT, 2010, 45 (11) : 2473 - 2484
  • [38] Performance Analysis of an R744 Supermarket Refrigeration System Integrated with an Organic Rankine Cycle
    Sengupta, Ayan
    Gullo, Paride
    Dasgupta, Mani Sankar
    Khorshidi, Vahid
    ENERGIES, 2023, 16 (22)
  • [39] PERFORMANCE OF REFRIGERATION & HEAT PUMP SYSTEM BY USING BINARY MIXTURES OF R32/R744
    Sun, Zhili
    Li, Minxia
    Ma, Yitai
    Wang, Pai
    11TH IIR GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS (2014): NATURAL REFRIGERANTS AND ENVIRONMENTAL PROTECTION, 2014, : 551 - 561
  • [40] Comparison of a R744 cascade refrigeration system with R404A and R22 conventional systems for supermarkets
    da Silva, Alessandro
    Bandarra Filho, Enio Pedone
    Pontes Antunes, Arthur Heleno
    APPLIED THERMAL ENGINEERING, 2012, 41 : 30 - 35