A Study on the Simulation and Experiment of Evaporative Condensers in an R744 Air Conditioning System

被引:0
|
作者
Dang, Thanhtrung [1 ]
Nguyen, Hoangtuan [1 ]
机构
[1] HCMC Univ Technol & Educ, Dept Thermal Engn, Ho Chi Minh City 71307, Vietnam
关键词
evaporative condenser; heat transfer; R744; subcritical; air conditioning; REFRIGERATION CYCLE; CO2; PERFORMANCE; WORKING;
D O I
10.3390/mi14101826
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
The heat transfer characteristics of evaporative condensers in an R744 air conditioning system were evaluated using the numerical and the experimental methods. Two configurations of condensers were studied: Case 1 with five layers of tubes and Case 2 with eight layers of tubes. In order to evaluate the heat transfer characteristics, the temperature field, the phase change, the pressure distribution, and thermodynamic parameters were considered. For Case 2, it indicated the capability of R744 condensation from the superheated status to the liquified status by analyzing the outlet temperature of the condenser changed from 28.7 degrees C to 30.3 degrees C with a change in condensation pressure from 72.6 bar to 68.5 bar. In this study, R744 mass flow rate increases from 14.34 kg/h to 46.08 kg/h, and the pressure drop also increases from 0.23 bar to 0.47 bar for the simulation and 0.4 bar to 0.5 bar for the experiment, respectively. The results indicate that the five-layer configuration causes a higher pressure drop and lower COP than those obtained from the eight-layer one (splitting into two sets for smaller pressure drop). Furthermore, the evaporative condensers using mini tubes that are flooded in the cooling water tank are suitable for the subcritical R744 air conditioning system. In addition, the results obtained from the experimental data are in good agreement with those obtained from the numerical results, with a deviation of less than 5%.
引用
收藏
页数:15
相关论文
共 50 条
  • [1] Coupling Effect of Air Flow Rate and Operating Conditions on the Performance of Electric Vehicle R744 Air Conditioning System
    Wang, Anci
    Fang, Jianmin
    Yin, Xiang
    Song, Yulong
    Cao, Feng
    Gullo, Paride
    APPLIED SCIENCES-BASEL, 2021, 11 (11):
  • [2] Experimental study of the heat transfer in R744/R600a mixtures below the R744 triple point temperature
    Sobieraj, Michal
    Rosinski, Marian
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 103 : 243 - 252
  • [3] Characteristic Evaluation on the Cooling Performance of an Electrical Air Conditioning System Using R744 for a Fuel Cell Electric Vehicle
    Lee, Moo-Yeon
    Lee, Ho-Seong
    Won, Hong-Phil
    ENERGIES, 2012, 5 (05): : 1371 - 1383
  • [4] Studies on a transcritical R744 based summer air-conditioning unit: Impact of refrigerant charge on system performance
    Hazarika, Mihir M.
    Ramgopal, Maddali
    Bhattacharyya, Souvik
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 89 : 22 - 39
  • [5] Performance and economic evaluation of CO2 (R744) air conditioning system driven by compressed air engine
    Wang, Lei
    Zhu, Shi-Liang
    Zhang, Xin-Rong
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 135 : 189 - 197
  • [6] Modeling and Simulation of a Transcritical R744 Heat Pump System
    Wang, Fengkun
    Fan, Xiaowei
    Zhang, Xianping
    Lian, Zhiwei
    ICIEA: 2009 4TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS, VOLS 1-6, 2009, : 3183 - 3187
  • [7] Studies on an R-744 based air conditioning system operating near critical point
    Sharma, Devendra Kumar
    Pegallapati, Aaditya Saikiran
    Ramgopal, Maddali
    SADHANA-ACADEMY PROCEEDINGS IN ENGINEERING SCIENCES, 2023, 48 (03):
  • [8] CFD CASE STUDY OF R744 EJECTORS
    Banasiak, K.
    Hafner, A.
    Eikevik, T.
    Haddal, O.
    11TH IIR GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS (2014): NATURAL REFRIGERANTS AND ENVIRONMENTAL PROTECTION, 2014, : 791 - 798
  • [9] Experimental evaluation of a cascade refrigeration system with the natural refrigerants R290/R744, R1270/R744 and R600a/R744
    Cabello, R.
    Sanchez, D.
    Andreu-Nacher, A.
    Llopis, R.
    Nebot-Andres, L.
    Calleja-Anta, D.
    Vidan-Falomir, F.
    15TH IIR-GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS, 2022, : 616 - 626
  • [10] Theoretical and experimental investigation on the effects of internal heat exchangers on a reversible automobile R744 air-conditioning system under various operating conditions
    Zhang, Wenying
    Li, Wenzhe
    Cernicin, Vladimir
    Hrnjak, Pega
    APPLIED THERMAL ENGINEERING, 2024, 236