Study of the Prevention Method of ±800 kV Transmission Tower Foundation Deviation

被引:6
|
作者
Dong, Xinsheng [1 ]
Wen, Guanru [2 ]
Zhao, Mingguan [1 ]
Yang, Yang [1 ]
Li, Meng [1 ]
Zhao, Long [2 ]
机构
[1] State Grid Xinjiang Elect Power Co Ltd, Elect Power Res Inst, Urumqi 830000, Peoples R China
[2] Xian Polytech Univ, Sch Elect & Informat, Xian 710048, Peoples R China
关键词
transmission tower; foundation deviation; finite element analysis; wind-driven response; LINES;
D O I
10.3390/en16062557
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The stability of transmission tower bases is key to ensuring the safe operation of power lines. This paper proposes a joint displacement-control technique for foundation-inclined piles and prestressed foundation tie beams to address the problem of tower base displacement and durability degradation caused by environmental factors. A finite element model of an exposed-pile transmission tower conforming to the structural characteristics of the actual line tower was established based on the current situation of Tower 292 of the +/- 800 kV Tianzhong line in Xinjiang, China. Three different displacement-control schemes were analyzed under the combined effects of tower line load, ice-cover load, and wind load, including changing exposed pile height, changing inclined pile tilt angle, and increasing the prestressed foundation tie beam. The analysis shows that the combined displacement-control technology of foundation-inclined piles and prestressed foundation tie beams can reduce the horizontal displacement of EHV tower foundations by more than 50%, which greatly reduces safety problems caused by tower displacement and effectively improves tower durability.
引用
收藏
页数:17
相关论文
共 50 条
  • [31] The True Type Test and Analysis of ± 800 kV Dc Tension Tower
    Li, Yongping
    Zhang, Wenbo
    2015 3RD ASIAN PACIFIC CONFERENCE ON MECHATRONICS AND CONTROL EINGINEERING (APCMCE 2015), 2015, : 40 - 44
  • [32] Study on Electrical Transient Protection for ±800kV UHVDC Transmission Lines
    Liu, Kezhen
    Yu, Jilai
    Shu, Hongchun
    Chen, Zhiyu
    2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,
  • [33] Stability Analysis of Transmission Tower Foundation on Hill Slope
    Mughees, Mohd Ammar
    Singh, Balram
    Mohammad, Zaid
    Sadique, Md. Rehan
    INTERNATIONAL CONFERENCE ON ADVANCES IN CIVIL ENGINEERING, ICACE 2022, 2024, 3010
  • [34] Development of methodology for refurbishment of transmission line tower foundation
    Scientists of Structural Engineering Research Centre, CSIR Campus, Taramani, Chennai 600113, India
    J Struct Eng, 2008, 1 (66-72):
  • [35] Research Progress of Transmission Tower Foundation in Permafrost Regions
    Kong, Wei
    Zhu, Zhuangzhuang
    Dai, Yonglin
    2016 3RD INTERNATIONAL CONFERENCE ON POWER AND ENERGY SYSTEMS (PES 2016), 2016, 4 : 56 - 58
  • [36] An Urgent Slope Reinforcement for a Power Transmission Tower Foundation
    Lin, JiSheng
    ADVANCED RESEARCH ON CIVIL ENGINEERING, MATERIALS ENGINEERING AND APPLIED TECHNOLOGY, 2014, 859 : 289 - 292
  • [37] Comparison analysis of micropile and slab foundation for transmission tower
    Wang Hua Juan
    PROCEEDINGS OF THE 2016 INTERNATIONAL FORUM ON ENERGY, ENVIRONMENT AND SUSTAINABLE DEVELOPMENT (IFEESD), 2016, 75 : 356 - 359
  • [38] Lightning performance and its prevention for quadruple-circuit transmission line with 220kV/110kV voltage in a tower
    Chunhua, L. (sjyouxiang@sohu.com), 2013, Universitas Ahmad Dahlan, Jalan Kapas 9, Semaki, Umbul Harjo,, Yogiakarta, 55165, Indonesia (11):
  • [39] 800-KV D-C TRANSMISSION
    ANNESTRAND, SA
    HARRINGT.EJ
    MARJERRI.MN
    STEVENS, RF
    POWER ENGINEERING, 1968, 72 (07) : 46 - +
  • [40] 800-KV D-C TRANSMISSION
    ANNESTRA.SA
    HARRINGT.EJ
    MARJERRI.MM
    STEVENS, RF
    POWER ENGINEERING, 1968, 72 (06) : 50 - &