Response Characteristics of Smoke Detection for Reduction of Unwanted Fire Alarms in Studio-Type Apartments

被引:2
作者
Hwang, Euy-hong [1 ]
Choi, Han-bit [1 ]
Choi, Don-mook [1 ]
机构
[1] Gachon Univ, Dept Equipment Syst & Fire Protect Engn, 1342 Seongnam Daero, Seongnam Si 13120, South Korea
来源
FIRE-SWITZERLAND | 2023年 / 6卷 / 09期
关键词
carbon monoxide; particulate matter; photoelectric smoke detector; studio-type apartment; unwanted fire alarm;
D O I
10.3390/fire6090362
中图分类号
Q14 [生态学(生物生态学)];
学科分类号
071012 ; 0713 ;
摘要
Photoelectric smoke detectors (SDs) often emit false alarms in studio-type apartments, where fire prevention is crucial. This study investigates the response characteristics of conventional and analog smoke detection factors to reduce false positives in studio-type apartments. A mock-up was tested based on relevant domestic laws, standards, statistical data, and experimental cases. A simulation of a cooking scenario involving burned food items was conducted, and optical density, particulate matter (PM), and carbon monoxide levels were measured and compared with actual smoke detection at six different locations. The measured values of conventional smoke detectors (CSDs) and analog smoke detectors (ASDs) at these locations were used to derive the activation time of CSDs and ASDs for the entire mock-up space. The results showed that the CSD activated at 7.42 min, while the ASD activated at 11.57 min. PM10.0, CO, and CO2 showed similar activation time trends. The PM10.0, CO, and CO2 concentrations at the time of SD activation were estimated. The findings suggest that a sensor with a consistent coefficient of variation, such as PM10.0 and CO, should be recommended.
引用
收藏
页数:18
相关论文
共 19 条
  • [1] [Anonymous], 2011, ISO 7240-6:2011(E)
  • [2] [Anonymous], 1993, ISO 9705:1993(E)
  • [3] Backstrom B., 2015, UL Research Report
  • [4] Indoor Air Quality Sensor Utilization for Unwanted Fire Alarm Improvement in Studio-Type Apartments
    Choi, Han-bit
    Hwang, Euy-hong
    Choi, Don-mook
    [J]. FIRE-SWITZERLAND, 2023, 6 (07):
  • [5] Cleary T.G., 2013, Smoke Alarm Performance in Kitchen Fires and Nuisance Alarm Scenarios
  • [6] Cleary T.G., 2016, A Study on the Performance of Current Smoke Alarms to the New Fire and Nuisance Tests Prescribed in ANSI/UL, V2015
  • [7] Festag S., 2022, False Alarm Study: Increase Fire Safety by Understanding False Alarms-Analysis of False Alarms from Fire Detection and Fire Alarm Systems in Europe, V2nd ed., DOI [10.37307/b.978-3-503-20969-9, DOI 10.37307/B.978-3-503-20969-9]
  • [8] Fire Protection Association, 2018, Automatic Fire Alarm Detection Systems. ABI Work Programme-Work Steam Two Final Version
  • [9] Hurley M.J., 2016, SFPE Handbook of Fire Protection Engineering, V5th, DOI DOI 10.1007/978-1-4939-2565-0
  • [10] Jeong Choi Yoo, 2021, [Fire Science and Engineering, 한국화재소방학회 논문지], V35, P67