Cooling Technologies for Internet Data Center in China: Principle, Energy Efficiency, and Applications

被引:6
|
作者
Huang, Xiaofei [1 ,2 ]
Yan, Junwei [1 ,2 ]
Zhou, Xuan [1 ,2 ]
Wu, Yixin [1 ,2 ]
Hu, Shichen [1 ]
机构
[1] South China Univ Technol, Sch Mech & Automot Engn, 381, Wushan Rd, Guangzhou 510640, Peoples R China
[2] Guangdong Artificial Intelligence & Digital Econ L, 70, Yuean Rd, Guangzhou 510640, Peoples R China
关键词
internet data center; PUE; energy efficiency; cooling technologies; energy saving rate; AIR-SIDE ECONOMIZERS; COOLED DATA CENTERS; BASE STATIONS TBSS; HEAT-PIPE SYSTEM; THERMAL MANAGEMENT; FLOW; PERFORMANCE; CHALLENGES; LEAKAGE; FLUID;
D O I
10.3390/en16207158
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The highlighted energy consumption of Internet data center (IDC) in China has become a pressing issue with the implementation of the Chinese dual carbon strategic goal. This paper provides a comprehensive review of cooling technologies for IDC, including air cooling, free cooling, liquid cooling, thermal energy storage cooling and building envelope. Firstly, the environmental requirements for the computer room and the main energy consumption items for IDC are analyzed. The evaluation indicators and government policies for promoting green IDC are also summarized. Next, the traditional cooling technology is compared to four new cooling technologies to find effective methods to maximize energy efficiency in IDC. The results show that traditional cooling consumes a significant amount of energy and has low energy efficiency. The application of free cooling can greatly improve the energy efficiency of IDC, but its actual implementation is highly dependent on geographical and climatic conditions. Liquid cooling, on the other hand, has higher energy efficiency and lower PUE compared to other cooling technologies, especially for high heat density servers. However, it is not yet mature and its engineering application is not widespread. In addition, thermal energy storage (TES) based cooling offers higher energy efficiency but must be coupled with other cooling technologies. Energy savings can also be achieved through building envelope improvements. Considering the investment and recovery period for IDC, it is essential to seek efficient cooling solutions that are suitable for IDC and take into account factors such as IDC scale, climate conditions, maintenance requirements, etc. This paper serves as a reference for the construction and development of green IDC in China.
引用
收藏
页数:31
相关论文
共 50 条
  • [21] Technologies for the energy-efficient data center
    Cader, Tahir
    Westra, Levi
    Marquez, Andres
    IPACK 2007: PROCEEDINGS OF THE ASME INTERPACK CONFERENCE 2007, VOL 1, 2007, : 791 - 802
  • [22] Performance and energy efficiency analysis of data center cooling plant by using lake water source
    Ling, Li
    Zhang, Quan
    Zeng, Liping
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 3096 - 3103
  • [23] Data Transactions in Energy Internet: Architecture and Key Technologies
    Guo Q.
    Wang B.
    Tian N.
    Sun H.
    Wen B.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2020, 35 (11): : 2285 - 2295
  • [24] Flexible Optical Modulation Technologies for Data Center Applications
    Ohlendorf, Simon
    Rosenkranz, Werner
    2017 19TH INTERNATIONAL CONFERENCE ON TRANSPARENT OPTICAL NETWORKS (ICTON), 2017,
  • [25] Internet of Things in energy: technologies, applications, challenges and future trends
    Tudora, Eleonora
    Tirziu, Eugenia
    Gheorghe-Moisii, Maria
    ROMANIAN JOURNAL OF INFORMATION TECHNOLOGY AND AUTOMATIC CONTROL-REVISTA ROMANA DE INFORMATICA SI AUTOMATICA, 2021, 31 (02): : 45 - 58
  • [26] Improving energy efficiency of dedicated cooling system and its contribution towards meeting an energy-optimized data center
    Cho, Jinkyun
    Kim, Yundeok
    APPLIED ENERGY, 2016, 165 : 967 - 982
  • [27] FROM CHIP TO COOLING TOWER DATA CENTER MODELING: CHIP LEAKAGE POWER AND ITS IMPACT ON COOLING INFRASTRUCTURE ENERGY EFFICIENCY
    Breen, Thomas J.
    Walsh, Ed J.
    Punch, Jeff
    Shah, Amip J.
    Bash, Cullen E.
    Kumari, Niru
    Cader, Tahir
    PROCEEDINGS OF THE ASME PACIFIC RIM TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC SYSTEMS, MEMS AND NEMS 2011, VOL 2, 2012, : 433 - +
  • [28] From Chip to Cooling Tower Data Center Modeling: Chip Leakage Power and Its Impact on Cooling Infrastructure Energy Efficiency
    Breen, Thomas J.
    Walsh, Ed J.
    Punch, Jeff
    Shah, Amip J.
    Bash, Cullen E.
    Kumari, Niru
    Cader, Tahir
    JOURNAL OF ELECTRONIC PACKAGING, 2012, 134 (04)
  • [29] Thermodynamics energy efficiency analysis and thermal modeling of data center cooling using open and closed-loop cooling systems
    Heydari, Ali
    IPACK 2007: PROCEEDINGS OF THE ASME INTERPACK CONFERENCE 2007, VOL 1, 2007, : 859 - 870
  • [30] HIGHER-EFFICIENCY REDUNDANCY STRATEGY FOR DATA CENTER COOLING
    Cho, Jinkyun
    Lee, Jinyoung
    ASHRAE Journal, 2024, 66 (02) : 42 - 44