Influence of the Environment on the Efficiency of the Cooling System of the Power Unit of the Belarusian NPP

被引:0
作者
Lukashevich, A. G. [1 ]
Kuzmin, A., V [1 ]
Sinkevich, A. E. [1 ]
机构
[1] Joint Inst Power & Nucl Res Sosny Natl Acad Sci Be, POB 119, Minsk 220109, BELARUS
来源
NONLINEAR PHENOMENA IN COMPLEX SYSTEMS | 2023年 / 26卷 / 02期
关键词
cooling tower; condenser; turbine power; climatic conditions;
D O I
10.33581/1561-4085-2023-26-2-139-147
中图分类号
O4 [物理学];
学科分类号
0702 ;
摘要
The paper presents studies that describe the influence of external conditions on the operation of the cooling system of the power unit of the Belarusian NPP, the main elements of which are a condenser and an evaporative cooling tower. The impact of ambient temperature on the performance of the cooling tower has been assessed. Calculation substantiation of thermotechnical and hydrodynamic parameters of the cooling system has been carried out, allowing to estimate turbine power losses when the heat removal from the cooling tower changes. It is shown how much the turbine power decreases with an increase in the water temperature at the condenser inlet, and, accordingly, an increase in the pressure in the condenser.
引用
收藏
页码:139 / 147
页数:9
相关论文
共 7 条
  • [1] [Anonymous], 2018, 7 INT C NUCL EN NUCL
  • [2] [Anonymous], 1985, HDB DESIGN COOLING T
  • [3] [Anonymous], 1973, VSN, V14
  • [4] [Anonymous], 2016, REPORTS-BASEL
  • [5] Aronson K.E., 2015, HEAT EXCHANGERS POWE, V3rd
  • [6] Klimenko RAS A.V., 2007, THERMAL NUCL POWER P
  • [7] RD, GUIDELINES OPERATION