Research on adaptive state prediction method for the metering error of capacitor voltage transformer

被引:0
作者
Zhu, Zhang [1 ]
Binbin, Li [1 ,2 ]
Jianyi, Xue [1 ]
Lijian, Ding [1 ]
机构
[1] HFUT, Sch Elect Engn & Automat, Hefei 230009, Peoples R China
[2] China & State Grid Anhui Elect Power Co, Elect Power Res Inst, Hefei 230601, Peoples R China
基金
中国国家自然科学基金;
关键词
CALIBRATION; CVT;
D O I
10.1063/5.0162472
中图分类号
TH7 [仪器、仪表];
学科分类号
0804 ; 080401 ; 081102 ;
摘要
A capacitor voltage transformer (CVT) is widely used in high voltage power systems because of its good insulation performance. However, the structure of CVT is more complex and the stability of its metering error is poor, which easily causes the loss of power metering. The conventional evaluation method for the metering error of CVT is to compare and calibrate with a standard transformer under off-line condition in a fixed period. Because of the long evaluation period, it is impossible to accurately predict the state change of CVT metering error, which is of more significance practically. To solve this problem, this paper proposes an adaptive state prediction method: Analyze the measurement data of CVT using principal component analysis method under the constraint of electrical physical relationship, the metering of CVT is mapped to residual and score (CRS) statistic. For this way, the self-evaluation of CVT metering error in real-time is realized without a standard transformer to get the high frequency time series of error data. According to the measurement data of CVT in process, the CRS statistics are batch processed adaptively, and the prediction model of CRS statistics is established based on the time series analysis. Experiments show that the method can accurately predict the state change of CVT metering error, and the prediction error is better than 15%. It is helpful to promote the development of CVT metering error detection into on-demand detection.
引用
收藏
页数:11
相关论文
共 30 条
  • [1] [Anonymous], 2010, GB47032007
  • [2] [Anonymous], 2010, JJG3142010
  • [3] Measurement Error Estimation for Capacitive Voltage Transformer by Insulation Parameters
    Chen, Bin
    Du, Lin
    Liu, Kun
    Chen, Xianshun
    Zhang, Fuzhou
    Yang, Feng
    [J]. ENERGIES, 2017, 10 (03)
  • [4] Note: An improved calibration system with phase correction for electronic transformers with digital output
    Cheng, Han-miao
    Li, Hong-bin
    [J]. REVIEW OF SCIENTIFIC INSTRUMENTS, 2015, 86 (08)
  • [5] [杜林 Du Lin], 2016, [电网技术, Power System Technology], V40, P3958
  • [6] Coupling capacitor voltage transformer: A model for electromagnetic transient studies
    Fernandes, D., Jr.
    Neves, W. L. A.
    Vasconcelos, J. C. A.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2007, 77 (02) : 125 - 134
  • [7] Method to measure CVT transfer function
    Ghassemi, F
    Gale, PF
    Clegg, B
    Cumming, T
    Coutts, C
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2002, 17 (04) : 915 - 920
  • [8] Fast ferroresonance suppression of coupling capacitor voltage transformers
    Graovac, M
    Iravani, R
    Wang, XL
    McTaggart, RD
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (01) : 158 - 163
  • [9] Detection and Correction of Systematic Errors in Instrument Transformers Along With Line Parameter Estimation Using PMU Data
    Khandeparkar, Kedar V.
    Soman, Shreevardhan A.
    Gajjar, Gopal
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2017, 32 (04) : 3089 - 3098
  • [10] Self-Detecting the Measurement Error of Electronic Voltage Transformer Based on Principal Component Analysis-Wavelet Packet Decomposition
    Li, Binbin
    Zhang, Zhu
    Ding, Lijian
    [J]. IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2021, 70