摘要
This study conducts a detailed numerical study upon the effect of chevron angle on the thermofluids characteristics of shell-and-plate heat exchangers. The plate diameter is 215 mm and the chevron angles (beta) are 30 degrees, 45 degrees, 60 degrees, and 75 degrees. Simulations are performed with Reynolds number ranging from 200 to 1000. The heat transfer and frictional performance are termed as Nusselt number (Nu) and friction factor (f), and results for both shell and plate side are reported. The Nusselt number and friction factor in the shell side are increased with the rise of chevron angle. For the same inlet flowrate, the pressure profile in the shell side changes significantly with the chevron angle, from uniform (beta = 30 degrees) to concave (beta = 45 degrees similar to 60 degrees) and finally to slightly convex (beta = 75 degrees) while the pressure profile in the plate side is always convex. In the plate side, the Nusselt number increases with the rise of chevron angle. But the lowest friction factor occurs when beta = 45 degrees due to a better flow distribution. The heat transfer performance in the shell side is superior to the plate side due to the presence of the inlet/outlet manifold in association with the chevron angles. Based on the performance evaluation criteria, it is found that the best overall performance occurs at a chevron angle of 45 degrees. This angle is applicable in both shell side and plate side. For the shell side, the index is about 25 %, 60 %, and 340 % higher than those of beta = 75 degrees, 60 degrees, and 30 degrees, respectively at a Reynolds number of 300 at the shell side. For the plate side, the index amid beta = 75 degrees, 60 degrees, and 45 degrees is roughly the same when the Reynolds number is lower than 500, and the index is about 220 % for beta = 45 degrees when compared to beta = 30 degrees at a Reynolds number of 300.
引用
收藏
页数:11
相关论文
共 50 条
  • [21] Comparative evaluation of the evaporation heat transfer characteristics of a low-GWP refrigerant R-1234ze(E) between shell-and-plate and plate heat exchangers
    Jo, ChangUk
    Lee, DongChan
    Chung, Hyun Joon
    Kang, Yubi
    Kim, Yongchan
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2020, 153
  • [22] Experimental investigation of heat transfer and effectiveness in corrugated plate heat exchangers having different chevron angles
    Bayram Kılıç
    Osman İpek
    Heat and Mass Transfer, 2017, 53 : 725 - 731
  • [23] Influence of chevron angle and MWCNT/distilled water nanofluid on the thermo-hydraulic performance of compact plate heat exchanger: An experimental and numerical study
    Singh, Shiva
    Ghosh, Subrata Kumar
    POWDER TECHNOLOGY, 2022, 405
  • [24] Flow statistics in plate and shell heat exchangers measured with PTV
    Beckedorff, L.
    Nieuwenhuizen, R.
    Bolwerk, T. M. A. J.
    Monteiro, A. S.
    de Paiva, K. V.
    Kuerten, J. G. M.
    van der Geld, C. W. M.
    Oliveira, J. L. G.
    INTERNATIONAL JOURNAL OF HEAT AND FLUID FLOW, 2019, 79
  • [25] The characteristics of condensation in brazed plate heat exchangers with different chevron angles
    Han, DH
    Lee, KJ
    Kim, YH
    JOURNAL OF THE KOREAN PHYSICAL SOCIETY, 2003, 43 (01) : 66 - 73
  • [26] Effect of geometrical parameters on the performance of chevron type plate heat exchanger'
    Kumar, Bhupal
    Soni, Akhilesh
    Singh, S. N.
    EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2018, 91 : 126 - 133
  • [27] Friction and Colburn factor correlations and shape optimization of chevron-type plate heat exchangers
    Lee, Jonghyeok
    Lee, Kwan-Soo
    APPLIED THERMAL ENGINEERING, 2015, 89 : 62 - 69
  • [28] Numerical study of the air inlet angle influence on the air-side performance of plate-fin heat exchangers
    Liu, Zhiying
    Li, Hui
    Shi, Lin
    Zhang, Yangjun
    APPLIED THERMAL ENGINEERING, 2015, 89 : 356 - 364
  • [29] Effect of Corrugation Angle on Heat Transfer Studies of Viscous Fluids in Corrugated Plate Heat Exchangers
    Rao, B. Sreedhara
    Gajanan, Surywanshi D.
    Varun, S.
    Krishna, M. V. S. Murali
    Sastry, R. C.
    INTERNATIONAL JOURNAL OF ENGINEERING AND TECHNOLOGY INNOVATION, 2015, 5 (02) : 99 - 107
  • [30] Numerical investigation of hydrothermal performance of double pipe heat exchangers with corrugation configuration
    Jafari, Leila
    Mobadersani, Farrokh
    Almasi, Mohammad
    APPLIED THERMAL ENGINEERING, 2025, 261