Estimation of Symmetrical Component Phasors and Frequency of Three-Phase Voltage Signals Using Transformations

被引:2
|
作者
Anirudh, C. V. S. [1 ]
Kumar, V. Seshadri Sravan [1 ]
机构
[1] Indian Inst Technol IIT, Dept Elect Engn, Hyderabad 502285, India
关键词
Frequency estimation; Estimation; Phase locked loops; Time-domain analysis; Frequency conversion; Time-frequency analysis; Voltage; symmetrical component phasors; transformations; unbalanced systems; SYSTEM; LOOP;
D O I
10.1109/TPWRD.2022.3183017
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a simple and computationally efficient algorithm for estimating the frequency and symmetrical component phasors from three-phase time-domain voltage signals utilizing the concept of transformation. A simple least-squares algorithm is proposed to extract the frequency of the signal based on its components in the rotating reference frame. Further, it is shown that the positive and negative sequence component phasors can also be extracted by utilizing the trajectory of the three-phase voltage signals in two rotating reference frames. Unlike the existing approaches, the proposed algorithm estimates the frequency and symmetrical component phasors without utilizing any phase-locked loop or complex transformations. The proposed approach is validated using simulation studies carried out on (a) three-phase test signals that comprise of harmonics, off-nominal frequencies, and unbalances and (b) standard test signals indicated in IEEE Std. C37.118.
引用
收藏
页码:189 / 199
页数:11
相关论文
共 50 条
  • [31] Amplitude-Phase-Locked Loop: Estimator of Three-Phase Grid Voltage Vector
    Shang, Lei
    Hu, Jiabing
    Yuan, Xiaoming
    Tang, Wenming
    Hou, Xinwen
    2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2015,
  • [32] Widely Linear State Space Models for Frequency Estimation in Unbalanced Three-Phase Systems
    Dini, Dahir H.
    Xia, Yili
    Douglas, Scott C.
    Mandic, Danilo P.
    2012 IEEE 7TH SENSOR ARRAY AND MULTICHANNEL SIGNAL PROCESSING WORKSHOP (SAM), 2012, : 9 - 12
  • [33] RECURSIVE TOTAL LEAST-SQUARES ESTIMATION OF FREQUENCY IN THREE-PHASE POWER SYSTEMS
    Arablouei, Reza
    Dogancay, Kutluyil
    Werner, Stefan
    2014 PROCEEDINGS OF THE 22ND EUROPEAN SIGNAL PROCESSING CONFERENCE (EUSIPCO), 2014, : 2330 - 2334
  • [34] Three-phase algorithm for independent single-phase grid frequency estimation under grid disturbances
    Reza, Md. Shamim
    Hossain, Md. Maruf
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (02) : 438 - 447
  • [35] Adaptive Estimation of Three-Phase Grid Voltage Parameters Under Unbalanced Faults and Harmonic Disturbances
    Dai, Zhiyong
    Lin, Wei
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (07) : 5613 - 5627
  • [36] A novel PLL for unbalanced three-phase grid voltage
    Wang, Lujun (wanglujun@zju.edu.cn), 1600, Science Press (35):
  • [37] Frequency Estimation of Three-Phase Power System Using Weighted-Least-Square Algorithm and Adaptive FIR Filtering
    Kusljevic, Miodrag D.
    Tomic, Josif J.
    Jovanovic, Ljubisa D.
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2010, 59 (02) : 322 - 329
  • [38] Formulation of the Phasors of Apparent Harmonic Power: Application to Non-Sinusoidal Three-Phase Power Systems
    Blasco, Pedro A.
    Montoya-Mira, Rafael
    Diez, Jose M.
    Montoya, Rafael
    Reig, Miguel J.
    ENERGIES, 2018, 11 (07)
  • [39] A New Voltage Compensation Philosophy for Dynamic Voltage Restorer to Mitigate Voltage Sags Using Three-Phase Voltage Ellipse Parameters
    Li, Peng
    Xie, Lili
    Han, Jiawei
    Pang, Shilin
    Li, Peihao
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2018, 33 (02) : 1154 - 1166
  • [40] Three-phase Harmonic State Estimation for Distribution Systems by Using the SVD Technique
    Breda, Jader F. D.
    Vieira, Jose C. M.
    Oleskovicz, Mario
    2016 IEEE POWER AND ENERGY SOCIETY GENERAL MEETING (PESGM), 2016,