Pearson Correlation in Determination of Quality of Current Transformers

被引:15
作者
Burgund, Davorin [1 ]
Nikolovski, Srete [2 ]
Galic, Dario [3 ]
Maravic, Nedeljko [4 ]
机构
[1] Elektrogen d o o, Zagreb 10000, Croatia
[2] Univ Osijek, Fac Elect Engn Comp Sci & Informat Technol, Power Engn Dept, Osijek 31000, Croatia
[3] Univ Osijek, Fac Dent Med & Hlth, Osijek 31000, Croatia
[4] Higher Tech Sch, SFB Educ Ctr Technol & Management, CH-8953 Zurich, Switzerland
关键词
Pearson correlation; current transformer; temperature; frequency; partial correlation;
D O I
10.3390/s23052704
中图分类号
O65 [分析化学];
学科分类号
070302 ; 081704 ;
摘要
The article elaborates on the accuracy of current transformers (CT) in interaction with temperature and frequency using Pearson's correlation. The first part of the analysis compares the accuracy of the mathematical model of the current transformer and the result of the measurement on the real CT using the Pearson correlation calculation. The mathematical model of CT is determined by deriving the formula of the functional error with the display of the accuracy of the measured value. The accuracy of the mathematical model is affected by the accuracy of current transformer model parameters and the calibration characteristic of the ammeter used to measure the CT current. Variables that cause deviation in the accuracy of CT are temperature and frequency. The calculation shows the effects on accuracy in both cases. The second part of the analysis refers to the calculation of the partial correlation of three quantities: (1) CT accuracy, (2) temperature, and (3) frequency on a set of 160 measurements. First, the influence of temperature on the correlation of CT accuracy and frequency is proven, following the proof of the influence of frequency on the correlation of CT accuracy and temperature. In the end, the analysis is combined by comparing the measured results of the first and second part of the analysis.
引用
收藏
页数:17
相关论文
共 11 条
[1]  
[Anonymous], 2018, CT AN TEST CERT NR 1
[2]   New statistical approach to interpret power transformer frequency response analysis: non-parametric statistical methods [J].
Behjat, Vahid ;
Mahvi, Mojtaba ;
Rahimpour, Ebrahim .
IET SCIENCE MEASUREMENT & TECHNOLOGY, 2016, 10 (04) :364-369
[3]  
Galic R., 1999, VJEROJATNOST STAT
[4]   Algorithm for transformer differential protection based on wavelet correlation modes [J].
Guillen, Daniel ;
Esponda, Hector ;
Vazquez, Ernesto ;
Idarraga-Ospina, Gina .
IET GENERATION TRANSMISSION & DISTRIBUTION, 2016, 10 (12) :2871-2879
[5]  
Herceg D., 1989, NUMERICKE STAT METOD
[6]  
Luchka A.Y., 1963, METHOD AVERAGING FUN
[7]  
Peric N., 2002, IDENTIFIKACIJA PROCE
[8]   Proposed diagnostic methodology using the cross-correlation coefficient factor technique for power transformer fault identification [J].
Saleh, Saber M. ;
EL-Hoshy, Salah Hamdy ;
Gouda, Osama E. .
IET ELECTRIC POWER APPLICATIONS, 2017, 11 (03) :412-422
[9]   Diagnosis of solid insulation deterioration for power transformers with dissolved gas analysis-based time series correlation [J].
Wang, Xuelei ;
Li, Qingmin ;
Yang, Rui ;
Li, Chengrong ;
Zhang, Ying .
IET SCIENCE MEASUREMENT & TECHNOLOGY, 2015, 9 (04) :393-399
[10]   Estimate of Correlation between Transformer Diagnostic Variables with a Time Lag [J].
Yachikov, I. M. ;
Nikolaev, A. A. ;
Zhuravlev, P. Yu. ;
Karandaeva, O. I. .