A novel method to measure the energy efficiency and performance of an auto-cascade refrigeration cycle

被引:19
作者
Llopis, Rodrigo [1 ]
Martinez-Angeles, Manel [1 ]
Garcia-Valero, Marc [1 ]
机构
[1] Jaume I Univ, Mech Engn & Construct Dept, Thermal Engn Grp, Castellon de La Plana, Spain
关键词
Auto-cascade; Measurement; COP; Ultra-low temperature; Energy efficiency; SYSTEM;
D O I
10.1016/j.applthermaleng.2023.121146
中图分类号
O414.1 [热力学];
学科分类号
摘要
Auto-cascade refrigeration systems are the most used cycles to maintain spaces at ultra-low temperature conditions (-80 to -60 & DEG;C). The interest in these systems has risen due to the need to maintain and distribute COVID19 vaccines. However, there is a lack of experimental validation of the theoretical models that are used to analyse and optimize them. In this work, a novel method to calculate the thermodynamic performance, circulating compositions, and energy efficiency of an auto-cascade refrigeration system is presented. The method is based on the measurements of an experimental auto-cascade plant at temperatures from -83.0 to -59.9 & DEG;C. The results of the study showed that the proposed calculation method was able to accurately predict the thermodynamic performance, circulating compositions and energy efficiency of an auto-cascade system. The uncertainty of the predictions was found to be below 1% for circulating compositions and 5.2% for the cooling capacity and COP.
引用
收藏
页数:11
相关论文
共 25 条
[1]   Thermodynamic analysis of auto-cascade refrigeration cycles, with and without ejector, for ultra low temperature freezing using a mixture of refrigerants R600a and R1150 [J].
Angel Rodriguez-Jara, Enrique ;
Jose Sanchez-de-la-Flor, Francisco ;
Antonio Exposito-Carrillo, Jose ;
Manuel Salmeron-Lissen, Jose .
APPLIED THERMAL ENGINEERING, 2022, 200
[2]  
[Anonymous], 2014, Resolution no. 76 of the Council of Ministers of 29 April 2014 on the establishment of the National Programme for the Prevention of Domestic Violence for 2014-2020
[3]   Autocascade refrigeration system: Experimental results in achieving ultra low temperature [J].
Aprea, C. ;
Maiorino, A. .
INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2009, 33 (06) :565-575
[4]   Experimental research on the pull-down performance of an ejector enhanced auto-cascade refrigeration system for low-temperature freezer [J].
Bai, Tao ;
Yan, Gang ;
Yu, Jianlin .
ENERGY, 2018, 157 :647-657
[5]   Experimental investigation of an ejector-enhanced auto-cascade refrigeration system [J].
Bai, Tao ;
Yan, Gang ;
Yu, Jianlin .
APPLIED THERMAL ENGINEERING, 2018, 129 :792-801
[6]   On the construction of binary mixture p-x and T-x diagrams from isochoric thermodynamics [J].
Bell, Ian H. ;
Deiters, Ulrich K. .
AICHE JOURNAL, 2018, 64 (07) :2745-2757
[7]   Comparative study on four autocascade refrigeration cycles based on energy, exergy, economic and environmental (4E) analyses [J].
Chen, Jiaheng ;
Zhang, Zhenya ;
Wang, Dingbiao ;
Wang, Guanghui ;
Peng, Xu ;
Qin, Xiang ;
Li, Hang .
ENERGY CONVERSION AND MANAGEMENT, 2023, 288
[8]  
Chen Q., 2022, Energies, V15
[9]   A study on the cycle characteristics of an auto-cascade refrigeration system [J].
Du, Kai ;
Zhang, Shaoqian ;
Xu, Weirong ;
Niu, Xiaofeng .
EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2009, 33 (02) :240-245
[10]   Theoretical performance comparison for a regenerator-enhanced three-stage auto-cascade refrigeration system using different zeotropic mixed refrigerants [J].
He, Yongning ;
Wu, Huihong ;
Xu, Ke ;
Zhang, Yeqiang ;
Wang, Tao ;
Wu, Xuehong ;
Cheng, Chuanxiao ;
Jin, Tingxiang .
ENERGY AND BUILDINGS, 2023, 283