Study on the influence of buried pipe fault on the operation of ground source heat pump system

被引:8
作者
Zhang, Xueping [1 ]
Li, Gui [1 ]
Han, Zongwei [1 ]
Yang, Ziwei [1 ]
Bi, Weiqiang [1 ]
Li, Xiuming [1 ]
Yang, Lingyan [2 ]
机构
[1] Northeastern Univ, Sch Met, SEP Key Lab Ecoind, Shenyang, Peoples R China
[2] China Acad Bldg Res, Beijing, Peoples R China
基金
中国国家自然科学基金;
关键词
Ground source heat pump; Pipe group; Power consumption; Coefficient of performance; Operation performance; THERMAL RESPONSE TEST; PERFORMANCE; TEMPERATURE; DESIGN; EXCHANGERS; ERROR;
D O I
10.1016/j.renene.2023.04.039
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
In order to analyze the influence of fault buried pipes on the operation of ground source heat pump system, a simulation model of unit considering both the influence of inlet fluid flow and temperature is developed, which is coupled with the three-dimensional dynamic model of 3 x 3 pipe group. The results show that the influence degree caused by different blocked positions is basically same. When one, two and a group of pipes are blocked, the annual power consumption of unit increases by 3.78%, 8.81% and 15.91% respectively. Besides, the system annual average coefficient of performance decreases from 3.28 to 3.21, 3.12 and 2.98. The ratio of cooling to heating load demands studied is 1.44, and the pipe blockage exacerbates the soil thermal imbalance, which cause a continuous deterioration of cooling performance. When the cooling load is high, the system is difficult to meet the demand. Because of design margin of total length, the time for not meeting the cooling demand after blocking one pipe is the same as normal condition, but the time after blocking two and a group of pipes increases 37.5 h and 88.5 h. Moreover, the amount for not meeting the demand increases 25.4%, 52.11% and 129.94% on average respectively.
引用
收藏
页码:12 / 25
页数:14
相关论文
共 29 条
  • [1] Reference data sets for vertical borehole ground heat exchanger models and thermal response test analysis
    Beier, Richard A.
    Smith, Marvin D.
    Spitler, Jeffrey D.
    [J]. GEOTHERMICS, 2011, 40 (01) : 79 - 85
  • [2] Estimation of soil and grout thermal properties through a TSPEP (two-step parameter estimation procedure) applied to TRT (thermal response test) data
    Bozzoli, F.
    Pagliarini, G.
    Rainieri, S.
    Schiavi, L.
    [J]. ENERGY, 2011, 36 (02) : 839 - 846
  • [3] Investigations on the influence of aquifers on the ground temperature in ground-source heat pump operation
    Capozza, Antonio
    De Carli, Michele
    Zarrella, Angelo
    [J]. APPLIED ENERGY, 2013, 107 : 350 - 363
  • [4] Bayesian inference for thermal response test parameter estimation and uncertainty assessment
    Choi, Wonjun
    Kikumoto, Hideki
    Choudhary, Ruchi
    Ooka, Ryozo
    [J]. APPLIED ENERGY, 2018, 209 : 306 - 321
  • [5] Dittus F.W., 1980, P 5 INT HEAT TRANSF, P2275
  • [6] Study on operation strategy of evaporative cooling composite air conditioning system in data center
    Han, Zongwei
    Xue, Da
    Wei, Haotian
    Ji, Qiang
    Sun, Xiaoqing
    Li, Xiuming
    [J]. RENEWABLE ENERGY, 2021, 177 : 1147 - 1160
  • [7] Study on the influence factors of short-time thermal response test based on artificial neural network
    Han, Zongwei
    Zhang, Xueping
    Meng, Xinwei
    Ji, Qiang
    Li, Gui
    Li, Xiuming
    [J]. GEOTHERMICS, 2021, 95
  • [8] Simulation study on performance of data center air-conditioning system with novel evaporative condenser
    Han, Zongwei
    Ji, Qiang
    Wei, Haotian
    Xue, Da
    Sun, Xiaoqing
    Zhang, Xueping
    Li, Xiuming
    [J]. ENERGY, 2020, 210
  • [9] Study on design error of ground source heat pump system and its influencing factors
    Han, Zongwei
    Li, Biao
    Zhang, Shuwei
    Bai, Chenguang
    Hu, Honghao
    [J]. APPLIED THERMAL ENGINEERING, 2018, 144 : 1030 - 1036
  • [10] Life cycle sustainability assessment of ground source heat pump in Shanghai, China
    Huang, Beijia
    Mauerhofer, Volker
    [J]. JOURNAL OF CLEANER PRODUCTION, 2016, 119 : 207 - 214