Heat transfer and pressure drops during high heat flux flow boiling of low-GWP refrigerants in 200 μm-wide multi-microchannels

被引:3
作者
Criscuolo, Gennaro [1 ]
Colombo, Luigi Pietro Maria [2 ]
Kanbur, Baris Burak [1 ]
Markussen, Wiebke Brix [1 ]
Kaern, Martin Ryhl [1 ]
机构
[1] Tech Univ Denmark, Dept Mech Engn, DK-2800 Kongens Lyngby, Denmark
[2] DOE, Politecn Milano, I-20156 Milan, Italy
关键词
High heat flux; Low GWP; Pressure drops; Flow boiling; Microchannel; Thermal management; R1234yf; R1234ze(E); 2-PHASE FLOW; TRANSFER COEFFICIENT; GENERAL CORRELATION; FUNDAMENTAL ISSUES; UNIVERSAL APPROACH; R1234YF; R134A; VISUALIZATION; R1234ZE(E); FRICTION;
D O I
10.1016/j.ijheatmasstransfer.2023.124882
中图分类号
O414.1 [热力学];
学科分类号
摘要
Thermal management of electronics is continuously challenged by increasing heat fluxes to be dissipated at minimum power consumption. This study investigated the pressure drops and the heat transfer coefflcient of two low-GWP refrigerants, R1234yf and R1234ze(E), during flow boiling at high heat fluxes. The test geometry comprised 25 parallel microchannels, 200 mu m wide, 1200 mu m deep and 1 cm long, nominally. Inlet orifices were used to stabilize the flow. A parametric analysis involving the mass flux and heat flux was conducted for nominal saturation temperatures of 30.5 degrees C and 40.5 degrees C, resulting in a maximum confinement number NConf of 2.16 for R1234yf and 2.52 for R1234ze(E). As the applied heat flux was increased from low to near-critical values, the two-phase heat transfer transitioned from a heat-flux-dominated mode to a convection-dominated one. The flow finally approached dryout, which led to the critical heat flux upon further heating. The experimental results were analysed through a regression with relevant non-dimensional groups, in particular the confinement number, NConf, the equivalent wall Biot number, Bi, the boiling number, Bo, the convection number, Co, and the Weber number, We. It was shown that Bo and Bi had a major influence in the heat-flux-dominated region, while Co and NConf determined the performance in the convective region, mainly due to the establishment of an intermittent annular flow. The total channel pressure drops were evaluated through the experimental measurement of the pressure drops in the inlet-outlet manifold, and the orifices. Due to the short channel length and the high heat fluxes, the pressure drops were dominated by the momentum change contribution, which accounted for at least 60% of the total pressure drops in the lowest case. The flow-wise heat transfer coefflcients and the channel pressure drops were compared with the predictions of existing correlations, showing generally a fair agreement.
引用
收藏
页数:17
相关论文
共 68 条
  • [1] High heat flux flow boiling in silicon multi-microchannels - Part III: Saturated critical heat flux of R236fa and two-phase pressure drops
    Agostini, Bruno
    Revellin, Remi
    Thome, John Richard
    Fabbri, Matteo
    Michel, Bruno
    Calmi, Daniele
    Kloter, Urs
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2008, 51 (21-22) : 5426 - 5442
  • [2] Flow boiling in copper and aluminium microchannels
    Al-Zaidi, Ali H.
    Mahmoud, Mohamed M.
    Karayiannis, Tassos G.
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2022, 194
  • [3] Effect of aspect ratio on flow boiling characteristics in microchannels
    Al-Zaidi, Ali H.
    Mahmoud, Mohamed M.
    Karayiannis, Tassos G.
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2021, 164
  • [4] Flow boiling of HFE-7100 in microchannels: Experimental study and comparison with correlations
    Al-Zaidi, Ali H.
    Mahmoud, Mohamed M.
    Karayiannis, Tassos G.
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2019, 140 : 100 - 128
  • [5] [Anonymous], 2014, Official Journal of the European Union
  • [6] Flow boiling heat transfer, pressure drop and dryout characteristics of R1234yf: Experimental results and predictions
    Anwar, Zahid
    Palm, Bjorn
    Khodabandeh, Rahmatollah
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2015, 66 : 137 - 149
  • [7] A composite heat transfer correlation for saturated flow boiling in small channels
    Bertsch, Stefan S.
    Groll, Eckhard A.
    Garimella, Suresh V.
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2009, 52 (7-8) : 2110 - 2118
  • [8] A novel time strip flow visualisation technique for investigation of intermittent dewetting and dryout in elongated bubble flow in a microchannel evaporator
    Borhani, Navid
    Agostini, Bruno
    Thome, John Richard
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2010, 53 (21-22) : 4809 - 4818
  • [9] Pressure drop caused by flow area changes in capillaries under low flow conditions
    Chalfi, Toufik Y.
    Ghiaasiaan, S. M.
    [J]. INTERNATIONAL JOURNAL OF MULTIPHASE FLOW, 2008, 34 (01) : 2 - 12
  • [10] Fundamental issues, mechanisms and models of flow boiling heat transfer in microscale channels
    Cheng, Lixin
    Xia, Guodong
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 108 : 97 - 127