Simultaneous compensation of distorted DC bus and AC side voltage using enhanced virtual synchronous generator in Islanded DC microgrid

被引:6
作者
Mousavi, Mohammad Hossein [1 ]
Moradi, Hassan [1 ]
机构
[1] Razi Univ, Dept Elect Engn, Kermanshah, Iran
关键词
DC bus voltage regulation; unbalanced load compensation; virtual synchronous generator; DDSRF; microgrid; CONTROL STRATEGY; INERTIA CONTROL; MACHINE; SUPPORT;
D O I
10.1080/00207217.2023.2278440
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
There are many effective techniques for virtual inertia emulation in DC microgrids that can help DC bus voltage stability through power exchange with virtual inertia injection. But one of the vexingly complicated challenges in virtual inertia emulation is the connection of unbalanced loads on the AC side of a DC microgrid. Unbalanced AC loads connected to a DC microgrid may cause severe fluctuations in DC bus voltage and battery power, as well as distorting AC side voltage. The need to solve this issue is very important because it can be a threat to the microgrid DC bus voltage stability and feed sensitive loads. One effective method to mimic the real inertia feature and dampen the unfavourable unbalanced conditions is to employ a virtual synchronous generator (VSG) equipped with a decoupled double synchronous reference frame (DDSRF) approach. The DDSRF can extract positive and negative components with high precision and create pure DC signals for the control system to improve accuracy and controllability. Hence, this paper investigates a combination of a VSG structure enhanced with a DDSRF technique to attenuate the fluctuations of DC bus voltage, battery power, and AC-side voltage caused by an unbalanced AC load in an islanded DC microgrid. The simulation results confirm that the unbalanced loads connected to the AC side of the microgrid are destructive for DC bus voltage, battery power, and also create voltage imbalances for AC loads. Furthermore, the proposed DDSRF-based VSG control system that has been implemented on the AC side of the microgrid can strongly dampen the fluctuations on the DC bus, battery, and AC loads.
引用
收藏
页码:151 / 176
页数:26
相关论文
共 35 条
[31]   Improved DC-Link Voltage Sliding Mode Control for Permanent Magnet Synchronous Generator Systems With Three-Phase AC-DC Converters [J].
Zhao, Mingwei ;
Zhang, Shuo ;
Zhang, Chengning ;
Li, Xueping ;
Dong, Yuelin .
IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2025, 13 (02) :2285-2295
[32]   DC voltage-based virtual synchronous generator scheme for eliminating circulating power of two-stage grid-tied converters [J].
Hao, Tianqu ;
Zhu, Jun ;
Gao, Feng ;
Zhao, Xingjian .
FRONTIERS IN ENERGY RESEARCH, 2023, 11
[33]   Resilient virtual synchronous generator approach using DC-link capacitor energy for frequency support of interconnected renewable power systems [J].
Bakeer, Mahmoud ;
Magdy, Gaber ;
Bakeer, Abualkasim ;
Aly, Mohamed M. .
JOURNAL OF ENERGY STORAGE, 2023, 65
[34]   A novel stability index-based virtual synchronous machine droop scheme for performance improvement of hybrid AC/DC microgrid under volatile loading conditions [J].
Jithin, S. ;
Rajeev, T. .
ELECTRIC POWER SYSTEMS RESEARCH, 2023, 214
[35]   Toward Power Quality Management in Hybrid AC-DC Microgrid Using LTC-L Utility Interactive Inverter: Load Voltage-Grid Current Tradeoff [J].
Shahparasti, Mahdi ;
Mohamadian, Mustafa ;
Baboli, Payam Teimourzadeh ;
Yazdian, Ali .
IEEE TRANSACTIONS ON SMART GRID, 2017, 8 (02) :857-867