Tower-foot grounding model for EMT programs based on transmission line theory and Marti's model

被引:5
作者
Alipio, Rafael [1 ]
De Conti, Alberto [2 ]
Vasconcellos, Felipe [3 ]
Moreira, Fernando [3 ]
Duarte, Naiara [1 ]
Marti, Jose [4 ]
机构
[1] Swiss Fed Inst Technol Lausanne EPFL, Electromagnet Compatibil Lab, CH-1015 Lausanne, Switzerland
[2] Univ Fed Minas Gerais, Dept Elect Engn, Belo Horizonte, MG, Brazil
[3] Univ Fed Bahia, Dept Elect & Comp Engn, Salvador, BA, Brazil
[4] Univ British Columbia, Elect & Comp Engn Dept, Vancouver, BC, Canada
关键词
Lightning transients; Transmission lines; EMT programs; Grounding; Transmission line theory; RATIONAL APPROXIMATION; SYSTEM;
D O I
10.1016/j.epsr.2023.109584
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper proposes a tower-foot grounding system model compatible with EMT programs which might be useful for the simulation of lightning transients in overhead lines. The proposed model is based on the solution of the telegrapher's equations and the application of the classical Marti's transmission line model. The model is implemented in the Alternative Transients Program (ATP) and validated considering a benchmark electromag-netic model. Its accuracy is evaluated and shown both in terms of the simulated ground potential rise (GPR) and line overvoltages developed through the insulator strings due to lightning currents. Finally, the model accuracy is also demonstrated in terms of the line backflashover outage rate.
引用
收藏
页数:8
相关论文
共 35 条
[1]   Wide-Band Modeling of Tower-Footing Grounding Systems for the Evaluation of Lightning Performance of Transmission Lines [J].
Alemi, Mohamad Reza ;
Sheshyekani, Kehyan .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2015, 57 (06) :1627-1636
[2]   Influence of a lossy ground on the lightning performance of overhead transmission lines [J].
Alipio, Rafael ;
De Conti, Alberto ;
Duarte, Naiara ;
Rachidi, Farhad .
ELECTRIC POWER SYSTEMS RESEARCH, 2023, 214
[3]   A comprehensive analysis of the effect of frequency-dependent soil electrical parameters on the lightning response of wind-turbine grounding systems [J].
Alipio, Rafael ;
Conceicao, Daiane ;
De Conti, Alberto ;
Yamamoto, Kazuo ;
Dias, Rosilene N. ;
Visacro, Silverio .
ELECTRIC POWER SYSTEMS RESEARCH, 2019, 175
[4]   Modeling the Frequency Dependence of Electrical Parameters of Soil [J].
Alipio, Rafael ;
Visacro, Silverio .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2014, 56 (05) :1163-1171
[5]   A method of a lightning surge analysis recommended in Japan using EMTP [J].
Ametani, A ;
Kawamura, T .
IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (02) :867-875
[6]  
[Anonymous], 1997, 12431997 IEEE
[7]  
Berger K., 1975, ELECTRA, V80, P223
[8]   A conductor arrangement that overcomes the effective length issue in transmission line grounding [J].
Caetano, C. E. F. ;
Lima, A. B. ;
Paulino, J. O. S. ;
Boaventura, W. C. ;
Cardoso, E. N. .
ELECTRIC POWER SYSTEMS RESEARCH, 2018, 159 :31-39
[9]   Closed-Form Expressions for the Estimation of the Minimum Backflashover Current of Overhead Transmission Lines [J].
Datsios, Zacharias G. ;
Mikropoulos, Pantelis N. ;
Tsovilis, Thomas E. .
IEEE TRANSACTIONS ON POWER DELIVERY, 2021, 36 (02) :522-532
[10]   Analytical representation of single- and double-peaked lightning current waveforms [J].
De Conti, Alberto ;
Visacro, Silverio .
IEEE TRANSACTIONS ON ELECTROMAGNETIC COMPATIBILITY, 2007, 49 (02) :448-451