Performance improvement of air-source heat pump via optimum control based on artificial neural network

被引:3
作者
Chae, Soowon [1 ]
Bae, Sangmu [1 ]
Nam, Yujin [1 ]
机构
[1] Pusan Natl Univ, Dept Architectural Engn, 2 Busandaehak Ro 63, Busan 46241, South Korea
基金
新加坡国家研究基金会;
关键词
Air source heat pump; Optimum control logic; Artificial neural network; Dynamic simulation; PARAMETERS;
D O I
10.1016/j.egyr.2023.06.051
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The use of air source heat pump (ASHP) systems is an economically viable strategy for building decarbonization. However, the ASHP energy performance deteriorates under severe conditions around a building. Researchers have conducted studies for optimal compressor control to overcome these limitations. Despite these efforts, users can seldom perform the optimal regulation of heat pump systems because manufacturers are reluctant to relinquish control to them. Therefore, we developed an artificial neural network (ANN)-based optimum control logic (OCL) system such that users can directly control and optimize heat pump systems without a compressor. The developed ANN-based OCL controls the secondary-side working fluid of the heat pump considering general building conditions, and its practical applicability has been verified using dynamic simulation. The improvement in the energy performance of the optimum models with respect to the conventional models was: 1.52% and 3.58% for the cooling and heating system COP, respectively, and 0.76% and 0.81% for the heat pump COP. These results demonstrate the potential for reduction in the carbon footprint of a building while maintaining comfort by enabling the energy-efficient operation and stable load response of the heating and cooling system.& COPY; 2023 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
引用
收藏
页码:460 / 472
页数:13
相关论文
共 42 条
  • [1] Effects of dead-band and set-point settings of on/off controllers on the energy consumption and equipment, switching frequency of a residential HVAC system
    Afram, Abdul
    Janabi-Sharifi, Farrokh
    [J]. JOURNAL OF PROCESS CONTROL, 2016, 47 : 161 - 174
  • [2] Agarap A. F., 2018, THE J
  • [3] Optimal control strategies of eight parallel heat pumps using Gaussian process emulator
    Ahn, Ki Uhn
    Park, Sung Ho
    Hwang, Seungho
    Choi, Sunkyu
    Park, Cheol Soo
    [J]. JOURNAL OF BUILDING PERFORMANCE SIMULATION, 2019, 12 (05) : 650 - 662
  • [4] [Anonymous], 2019, 6222019 ASHRAE
  • [5] [Anonymous], 2013, 1692013 ASHRAE
  • [6] [Anonymous], 2019, ASHRAE Handbook
  • [7] [Anonymous], 2014, MEASUREMENT ENERGY D
  • [8] [Anonymous], 2019, Energy Standard for Buildings Except Low-Rise Residential Buildings
  • [9] [Anonymous], 2023, SPECIFIC NEEDS SHOUL
  • [10] ASHRAE, 2019, STANDARD 621 2019 VE