Effects of different water-cooled heat sinks on the cooling system performance in a data center

被引:21
|
作者
He, Wei [1 ]
Zhang, Jifang [1 ]
Li, Hailong [1 ]
Guo, Rui [1 ]
Liu, Shengchun [1 ]
Wu, Xiaohui [2 ]
Wei, Jie [1 ]
Wang, Yulin [1 ]
机构
[1] Tianjin Univ Commerce, Tianjin Key Lab Refrigerat Technol, Tianjin 300134, Peoples R China
[2] China Inst Bldg Stand Design & Res, Beijing 100048, Peoples R China
关键词
Liquid cooling; Fin -type heat sinks; Server heat dissipation; Energy consumption; Data center; FLUID; PIPE;
D O I
10.1016/j.enbuild.2023.113162
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Data center, as a special building form, has attracted much attention because of its increasing energy consumption. In order to reduce the energy consumption of data center caused by cooling system, research on the water-cooled heat sinks used to cool chips has become increasingly important with the steep increase in the heat flux density of data centers. To explore the effect of different water-cooled heat sinks on cooling system performance, a server water-cooled system for the server cabinet was built, and the chip heat dissipation performance, optimal thermal management, and system energy consumption were simulated by equipping a cooling tower and two types of fin-type water-cooled heat sinks (A-type and B-type). By comparing the effects of A- and B-type heat sinks on the server water-cooled system performance, the optimal water working condition was obtained under different atmospheric conditions by minimizing the system power consumption to guarantee that the chip temperature is no higher than 70 degrees C. It was found that the optimal cooling water flow rate fluctuates in a large range under different atmospheric conditions. A server water-cooled system equipped with B-type can achieve significant energy savings compared to those from A-type system when the atmospheric relative humidity and temperature are high. Considering a case study from Tianjin, China, it is shown that the monthaveraged power usage effectiveness in June is 1.2 for A-type and 1.14 for B-type systems.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] Thermal performance of water-cooled heat sinks
    Salem, TE
    Bayne, SB
    Porschet, D
    Chen, Y
    APEC 2005: TWENTIETH ANNUAL IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION, VOLS 1-3, 2005, : 129 - 133
  • [2] Thermal performance of water-cooled heat sinks: A comparison of two different designs
    Salem, TE
    Porschet, D
    Bayne, SB
    TWENTY-FIRST ANNUAL IEEE SEMICONDUCTOR THERMAL MEASUREMENT AND MANAGEMENT SYMPOSIUM, PROCEEDINGS 2005, 2005, : 264 - 269
  • [3] Experimental investigation of the cooling performance of 3-D printed hybrid water-cooled heat sinks
    Gonzalez-Valle, C. Ulises
    Samir, Saurabh
    Ramos-Alvarado, Bladimir
    APPLIED THERMAL ENGINEERING, 2020, 168
  • [4] Cooling Performance Analysis of Water-Cooled Heat Sinks with Circular and Rectangular Minichannels Using Finite Volume Method
    Ghasemi, Seyed Ebrahim
    Ranjbar, Ali Akbar
    Hosseini, Seiyed Mohammad Javad
    IRANIAN JOURNAL OF CHEMISTRY & CHEMICAL ENGINEERING-INTERNATIONAL ENGLISH EDITION, 2018, 37 (02): : 231 - 239
  • [5] HOT WATER COOLED HEAT SINKS FOR EFFICIENT DATA CENTER COOLING: TOWARDS ELECTRONIC COOLING WITH HIGH EXERGETIC UTILITY
    Kasten, Peter
    Zimmermann, Severin
    Tiwari, Manish K.
    Michel, Bruno
    Poulikakos, Dimos
    FRONTIERS IN HEAT AND MASS TRANSFER, 2010, 1 (02):
  • [6] Effects of pulse frequency on performance of electrochemical cooling water treatment for cooling tower of water-cooled chiller
    Nhut L.M.
    Nhut D.H.M.
    Renewable Energy and Power Quality Journal, 2021, 19 : 619 - 623
  • [7] A SIMPLER, SAFER, HIGHER PERFORMANCE COOLING SYSTEM ARRANGEMENT FOR WATER-COOLED DIVERTORS
    CARELLI, MD
    KOTHMANN, RE
    GREEN, L
    ZHAN, NJ
    STEFANI, F
    ROIDT, RM
    FUSION TECHNOLOGY, 1994, 26 (03): : 611 - 617
  • [8] Efficacy of a water-cooled garment for auxiliary body cooling in heat
    Ergonomics Division, Natl. Inst. of Occupational Health, Ahmedabad 380 016, India
    Ergonomics, 2 (179-187):
  • [9] Efficacy of a water-cooled garment for auxiliary body cooling in heat
    Nag, PK
    Pradhan, CK
    Nag, A
    Ashtekar, SP
    Desai, H
    ERGONOMICS, 1998, 41 (02) : 179 - 187
  • [10] POWER SOURCE AND COOLING SYSTEM FOR WATER-COOLED MAGNETS
    HOSHI, A
    NAKAGAWA, Y
    MIURA, S
    KUDO, M
    SAI, K
    ISHIKAWA, Y
    TANABE, M
    TANOUE, Y
    IKEDA, H
    YONEDA, N
    SCIENCE REPORTS OF THE RESEARCH INSTITUTES TOHOKU UNIVERSITY SERIES A-PHYSICS CHEMISTRY AND METALLURGY, 1986, 33 (02): : 271 - 280