Optimal Sizing of a Photovoltaic/Battery Energy Storage System to Supply Electric Substation Auxiliary Systems under Contingency

被引:3
|
作者
Goncalves, Ailton [1 ]
Cavalcanti, Gustavo O. [1 ]
Feitosa, Marcilio A. F. [1 ]
Dias Filho, Roberto F. F. [1 ]
Pereira, Alex C. [2 ]
Jatoba, Eduardo B. [2 ]
de Melo Filho, Jose Bione [2 ]
Marinho, Manoel H. N. [1 ]
Converti, Attilio [3 ]
Gomez-Malagon, Luis A. [1 ]
机构
[1] Univ Pernambuco, Polytech Sch Pernambuco, Dept Syst Engn, Postgrad Program Syst Engn, BR-50720001 Recife, PE, Brazil
[2] Sao Francisco Hydroelect Co Chesf, BR-50761901 Recife, PE, Brazil
[3] Univ Genoa, Dept Civil Chem & Environm Engn, Pole Chem Engn, Via Opera Pia 15, I-16145 Genoa, Italy
关键词
auxiliary systems; battery management systems; microgrids; photovoltaic systems; substation; WIND HYBRID SYSTEM; PV-BATTERY SYSTEMS; MULTIOBJECTIVE OPTIMIZATION; DESIGN; CAPACITY;
D O I
10.3390/en16135165
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Electric substations (ESS) are important facilities that must operate even under contingency to guarantee the electrical system's performance. To achieve this goal, the Brazilian national electricity system operator establishes that alternating current (AC) auxiliary systems of ESS must have, at least, two power supplies, and in the case of failure of these sources, an emergency generator (EG) must at least supply energy to the essential loads. In order to improve the availability of auxiliary systems, a microgrid with other sources, such as photovoltaic (PV) systems and Battery Energy Storage Systems (BESS), can be an alternative. In this case, an economical optimization of the PV/BESS system must be addressed considering the costs associated with the installation and maintenance of equipment, and the gains from the credits generated by the photovoltaic system in the net metering scheme. In this paper, the size of the BESS system was determined to supply energy to the load of auxiliary systems of an ESS, as well as a PV system to achieve a null total cost. Furthermore, multi-objective optimization using the genetic algorithm technique was employed to optimize the size of the hybrid PV/BESS to minimize the investment cost and time when the demand was not met. Simulations under different scenarios of contingency were allowed to obtain the Pareto frontier for the optimal sizing of a PV/BESS system to supply energy to AC auxiliary systems in an ESS under contingency.
引用
收藏
页数:17
相关论文
共 50 条
  • [1] Optimal Capacity Sizing for the Integration of a Battery and Photovoltaic Microgrid to Supply Auxiliary Services in Substations under a Contingency
    Tabares, Alejandra
    Martinez, Norberto
    Ginez, Lucas
    Resende, Jose F.
    Brito, Nierbeth
    Franco, John Fredy
    ENERGIES, 2020, 13 (22)
  • [2] Optimal sizing of grid-connected rooftop photovoltaic and battery energy storage for houses with electric vehicle
    Merrington, Sarah
    Khezri, Rahmat
    Mahmoudi, Amin
    IET SMART GRID, 2023, 6 (03) : 297 - 311
  • [3] Optimal sizing and energy scheduling of photovoltaic-battery systems under different tariff structures
    Talent, Orlando
    Du, Haiping
    RENEWABLE ENERGY, 2018, 129 : 513 - 526
  • [4] Optimal investment timing and sizing for battery energy storage systems
    Kelly, Joseph J.
    Leahy, Paul G.
    JOURNAL OF ENERGY STORAGE, 2020, 28 (28):
  • [5] Battery Storage System Sizing in Distribution Feeders with Distributed Photovoltaic Systems
    Venu, Chandu
    Riffonneau, Yann
    Bacha, Seddik
    Baghzouz, Yahia
    2009 IEEE BUCHAREST POWERTECH, VOLS 1-5, 2009, : 1099 - +
  • [6] Lead-Acid Battery Sizing for a DC Auxiliary System in a Substation by the Optimization Method
    Ribic, Janez
    Pihler, Joze
    Marusa, Robert
    Kokalj, Filip
    Kitak, Peter
    ENERGIES, 2019, 12 (22)
  • [7] Optimal Sizing of Battery Energy Storage Systems Considering Cooperative Operation with Microgrid Components
    Takano, Hirotaka
    Hayashi, Ryosuke
    Asano, Hiroshi
    Goda, Tadahiro
    ENERGIES, 2021, 14 (21)
  • [8] Multiobjective Optimal Sizing of Hybrid Energy Storage System for Electric Vehicles
    Zhang, Lei
    Hu, Xiaosong
    Wang, Zhenpo
    Sun, Fengchun
    Deng, Junjun
    Dorrell, David. G.
    IEEE TRANSACTIONS ON VEHICULAR TECHNOLOGY, 2018, 67 (02) : 1027 - 1035
  • [9] Optimal sizing of battery energy storage system for local multi-energy systems: The impact of the thermal vector
    Gluecker, Philipp
    Pesch, Thiemo
    Benigni, Andrea
    APPLIED ENERGY, 2024, 372
  • [10] A universal optimal sizing for hybrid energy storage system of electric vehicles
    Nguyen-Minh, Tien
    Nguy, Bao-Huy
    Vo-Duy, Thanh
    Ta, Minh C.
    Trovao, Joao Pedro F.
    Antunes, Carlos Henggeler
    JOURNAL OF ENERGY STORAGE, 2024, 92