Study on IEEE 2800-2022 standard benefits for transmission line protection in the presence of inverter-based resources

被引:5
作者
Davi, Moises J. B. B. [1 ]
Oleskovicz, Mario [1 ]
Lopes, Felipe, V [2 ]
机构
[1] Univ Sao Paulo, EESC USP, Sao Carlos, SP, Brazil
[2] Fed Univ Paraiba UFPB, Joao Pessoa, PB, Brazil
基金
巴西圣保罗研究基金会;
关键词
Directional protection; Distance protection; IEEE; 2800-2022; Inverter-based generators; Phase-selection functions; Renewable energy;
D O I
10.1016/j.epsr.2023.109304
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents an Electromagnetic Transient (EMT)-based study about the IEEE 2800-2022 standard benefits for transmission line protection functionalities in the presence of Inverter-Based Resources (IBR). Seven functions are evaluated, namely: (1) Self-polarized distance protection, (2) Memory-polarized distance protection, (3) Memory-Cross-polarized distance protection, (4) Negative sequence-based directional function, (5) Zero sequence-based directional function, (6) Incremental phasor-based phase-selection function, and (7) Current angle-based phase-selection function. To do so, massive EMT simulations are carried out in the PSCAD environment to emulate contingency scenarios in a typical transmission circuit that interconnects an IBR to a synchronous power grid. The evaluated protection functions are implemented and validated with the routines applied in commercial relays, providing a practical perspective on the importance of recent advances in IBR control standards, such as the IEEE 2800-2022. The results demonstrate that the IEEE 2800-2022 significantly improves the transmission line protection performance, being the EMT-based analysis crucial to provide a detailed study on these benefits.
引用
收藏
页数:9
相关论文
共 29 条
  • [1] [Anonymous], 2022, IEEE Standard 2800, DOI [10.1109/IEEESTD.2022.9762253, DOI 10.1109/IEEESTD.2022.9762253]
  • [2] Resilience Enhancement of Microgrids With Inverter-Interfaced DGs by Enabling Faulty Phase Selection
    Azzouz, Maher Abdelkhalek
    Hooshyar, Ali
    El-Saadany, Ehab F.
    [J]. IEEE TRANSACTIONS ON SMART GRID, 2018, 9 (06) : 6578 - 6589
  • [3] A Control-Based Solution for Distance Protection of Lines Connected to Converter-Interfaced Sources During Asymmetrical Faults
    Banaiemoqadam, Amin
    Hooshyar, Ali
    Azzouz, Maher A.
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (03) : 1455 - 1466
  • [4] A combined directional and faulted phase selector element based on incremental quantities
    Benmouyal, G
    Mahseredjian, J
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2001, 16 (04) : 478 - 484
  • [5] CHAVEZ J, 2019, P EUR PM2019 MAT BIO, P1
  • [6] S-Transform based fault detection algorithm for enhancing distance protection performance
    Chavez, Jose J.
    Popov, Marjan
    Lopez, David
    Azizi, Sadegh
    Terzija, Vladimir
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2021, 130
  • [7] Costa J.S, 2020, 15 INT C DEV POWER S, DOI [10.1049/cp.2020.0012, DOI 10.1049/CP.2020.0012]
  • [8] Costello D., 2010, 63rd Annual Conference for Protective Relay Engineers, College Station, TX, USA, P1, DOI [DOI 10.1109/CPRE.2010.5469523, 10.1109/CPRE.2010.5469523]
  • [9] Feng YL, 2019, 2019 4TH INTERNATIONAL CONFERENCE ON INTELLIGENT GREEN BUILDING AND SMART GRID (IGBSG 2019), P512, DOI [10.1109/igbsg.2019.8886184, 10.1109/IGBSG.2019.8886184]
  • [10] Guzman A., 1997, 50 ANN C PROT REL EN