Fault detection and diagnosis of energy system based on deep learning image recognition model under the condition of imbalanced samples

被引:11
作者
Ruan, Yingjun [1 ]
Zheng, Minghua [2 ]
Qian, Fanyue [1 ]
Meng, Hua [1 ]
Yao, Jiawei [3 ]
Xu, Tingting [1 ]
Pei, Di [1 ]
机构
[1] Tongji Univ, Coll Mech & Energy Engn, Shanghai 200092, Peoples R China
[2] Shenzhen Inovance Technol Co Ltd, Shenzhen 518110, Peoples R China
[3] Tongji Univ, Coll Architecture & Urban Planning, Shanghai 200092, Peoples R China
基金
中国国家自然科学基金;
关键词
Fault detection and diagnosis; Energy system; Deep learning; Image recognition; Samples augment; NETWORK;
D O I
10.1016/j.applthermaleng.2023.122051
中图分类号
O414.1 [热力学];
学科分类号
摘要
Faults in energy systems impact the reliability of the energy supply and cause energy waste. Data-driven fault detection and diagnosis (FDD) methods can detect and diagnose system faults by mining historical operational data. However, the quantitative imbalance between fault and normal samples degrades the performance of the FDD method. Therefore, this study proposes a novel deep learning-based FDD method under the condition of imbalanced samples that converts the time-series signals into an image signal to extract the timing and coupling features, and then applies the improved conditional variational autoencoder-generative adversarial network (CVAE-GAN) to generate fault samples for balancing the training sample set. Subsequently, according to the framework of image recognition, a two-dimensional convolutional neural network was adopted to identify the image samples and achieve FDD. The experimental results showed that, under the condition of imbalanced samples, the proposed method could increase diagnosis accuracy by an average of 5.71% compared with other common data-driven methods. After the samples were augmented with the improved CVAE-GAN, the accuracy improved by an average of 3.79%. Consequently, the feasibility and superiority of the proposed method were demonstrated.
引用
收藏
页数:16
相关论文
共 52 条
  • [11] Chiller fault diagnosis with field sensors using the technology of imbalanced data
    Fan, Yuqiang
    Cui, Xiaoyu
    Han, Hua
    Lu, Hailong
    [J]. APPLIED THERMAL ENGINEERING, 2019, 159
  • [12] Fernandez N., 2009, SELF CORRECTING HVAC
  • [13] Gao J., 2021, J BUILD ENG, V34
  • [14] Enhanced chiller faults detection and isolation method based on independent component analysis and k-nearest neighbors classifier
    Gao, Long
    Li, Donghui
    Liu, Xinyu
    Liu, Gongshang
    [J]. BUILDING AND ENVIRONMENT, 2022, 216
  • [15] Goodfellow IJ, 2014, ADV NEUR IN, V27, P2672
  • [16] Deep learning-based fault diagnosis of variable refrigerant flow air-conditioning system for building energy saving
    Guo, Yabin
    Tan, Zehan
    Chen, Huanxin
    Li, Guannan
    Wang, Jiangyu
    Huang, Ronggeng
    Liu, Jiangyan
    Ahmad, Tanveer
    [J]. APPLIED ENERGY, 2018, 225 : 732 - 745
  • [17] Study on a hybrid SVM model for chiller FDD applications
    Han, H.
    Gu, B.
    Kang, J.
    Li, Z. R.
    [J]. APPLIED THERMAL ENGINEERING, 2011, 31 (04) : 582 - 592
  • [18] Novel chiller fault diagnosis using deep neural network (DNN) with simulated annealing (SA)
    Han, Hua
    Xu, Ling
    Cui, Xiaoyu
    Fan, Yuqiang
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 121 : 269 - 278
  • [19] Least squares support vector machine (LS-SVM)-based chiller fault diagnosis using fault indicative features
    Han, Hua
    Cui, Xiaoyu
    Fan, Yuqiang
    Qing, Hong
    [J]. APPLIED THERMAL ENGINEERING, 2019, 154 : 540 - 547
  • [20] End-to-end chiller fault diagnosis using fused attention mechanism and dynamic cross-entropy under imbalanced datasets
    Han, Songyu
    Shao, Haidong
    Huo, Zhiqiang
    Yang, Xingkai
    Cheng, Junsheng
    [J]. BUILDING AND ENVIRONMENT, 2022, 212