Empirical Study of the Effect of Thermal Loading on the Heating Efficiency of Variable-Speed Air Source Heat Pumps

被引:2
作者
Marsik, Tom [1 ,2 ,3 ,4 ]
Stevens, Vanessa [3 ,4 ]
Garber-Slaght, Robbin [3 ,4 ]
Dennehy, Conor [3 ,4 ]
Strunk, Robby Tartuilnguq [2 ,3 ,4 ]
Mitchell, Alan [5 ]
机构
[1] Univ Alaska Fairbanks, Bristol Bay Campus, Dillingham, AK 99576 USA
[2] Univ Alaska Fairbanks, Alaska Ctr Energy & Power, Fairbanks, AK 99775 USA
[3] Natl Renewable Energy Lab, Golden, CO 80401 USA
[4] Cold Climate Housing Res Ctr, Fairbanks, AK 99775 USA
[5] Anal North, Anchorage, AK 99516 USA
基金
美国国家科学基金会;
关键词
air source heat pump; efficiency; coefficient of performance (COP);
D O I
10.3390/su15031880
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Heating buildings with air source heat pumps (ASHPs) has the potential to save energy compared to utilizing conventional heat sources. Accurate understanding of the efficiency of ASHPs is important to maximize the energy savings. While it is well understood that, in general, ASHP efficiency decreases with decreasing outdoor temperature, it is not well understood how the ASHP efficiency changes with different levels of thermal loading, even though it is an important consideration for sizing and controlling ASHPs. The goal of this study was to create an empirical model of the ASHP efficiency as a function of two independent variables-outside temperature and level of thermal loading. Four ductless mini-split ASHPs were evaluated in a cold chamber where the temperature (representing the outdoor temperature) was varied over a wide range. For each temperature, the ASHP performance data were collected at several levels of thermal loading. The data for all four ASHPs were combined and approximated with an analytical function that can be used as a general model for the ASHP steady-state efficiency as a function of the outside temperature and level of thermal loading. To the knowledge of the authors, no such empirical model that is solely based on third-party test data has been published before. While limitations exist, the model can be used to help guide future selection and operation of ASHPs.
引用
收藏
页数:15
相关论文
共 50 条
  • [31] Experimental Study on Air Source Heat Pump Heating System Based on Phase Change Heat Storage
    Guo, Jianhong
    Yu, Jinxiang
    Wang, Yibo
    Zhang, Xiaoyu
    IEEE ACCESS, 2023, 11 : 110878 - 110887
  • [32] Experimental study of defrosting control method based on image processing technology for air source heat pumps
    Zheng, Xuejing
    Shi, Rui
    You, Shijun
    Han, Yong
    Shi, Kaiyu
    SUSTAINABLE CITIES AND SOCIETY, 2019, 51
  • [33] Optimal dispatching of household air-source heat pump heating system considering thermal comfort
    Qi, Yan
    Du, Lijia
    Mu, Yunfei
    Jia, Hongjie
    Wang, Xudong
    Li, Guodong
    RENEWABLE ENERGY INTEGRATION WITH MINI/MICROGRID, 2019, 159 : 491 - 496
  • [34] Field experimental research on retarding frosting and improving defrosting performance of air source heat pumps through variable frequency technology
    Wu, Chunling
    Wang, Zhichao
    Li, Xiaofeng
    Xu, Zhaowei
    Xu, Ce
    Yang, Yingxia
    Zhao, Wenyuan
    Wang, Yichao
    JOURNAL OF BUILDING ENGINEERING, 2023, 64
  • [35] A novel integrated heating system of solar energy and air source heat pumps and its optimal working condition range in cold regions
    Qiu, Guodong
    Wei, Xinghua
    Xu, Zhenfei
    Cai, Weihua
    ENERGY CONVERSION AND MANAGEMENT, 2018, 174 : 922 - 931
  • [36] Experimental study on heat storage air source heat pump system with"no frost effect"
    Zhao H.
    Yu S.
    Qiu G.
    Shen C.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2021, 42 (04): : 61 - 67
  • [37] The variable water temperature control strategy of the air-source heat pump compatible with floor heating system for an apartment
    Liu, Yanrong
    Nan, Xiaohong
    Han, Han
    Li, Jie
    JOURNAL OF BUILDING ENGINEERING, 2024, 90
  • [38] Theoretical Study and Experimental Validation on the Applicable Refrigerant for Space Heating Air Source Heat Pump
    Nie, Jinzhe
    Wang, Kaiqiao
    Kong, Xiangrui
    Zhang, Han
    Zhang, Shuai
    SUSTAINABILITY, 2023, 15 (12)
  • [39] DEFROST PERFORMANCE STUDY OF CONTINUOUS HEATING AIR SOURCE HEAT PUMP SYSTEM WITH SEGMENTED DEFROST
    Liu X.
    Chen H.
    Feng R.
    Huang T.
    He S.
    Tang L.
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2023, 44 (11): : 1 - 8
  • [40] Study the performance of air-source heat pump assisted solar water heating system
    Ding, Defeng
    Chen, Wu
    PROCEEDINGS OF THE 2017 GLOBAL CONFERENCE ON MECHANICS AND CIVIL ENGINEERING (GCMCE 2017), 2017, 132 : 396 - 400