Holistic non-linear optimization of the layout, sizing, and operation of a district heating plant

被引:5
|
作者
Hassan, Muhammed A. [1 ,2 ,3 ]
Serra, Sylvain [1 ]
Sochard, Sabine [1 ]
Viot, Hugo [4 ]
Marias, Frederic [1 ]
Reneaume, Jean-Michel [1 ]
机构
[1] Univ Pau & Pays de Adour, E2S UPPA, LaTEP, Pau, France
[2] Cairo Univ, Fac Engn, Mech Power Engn Dept, Giza 12613, Egypt
[3] Univ Waterloo, Sch Architecture, 7 Melville St S, Cambridge, ON N1S 2H4, Canada
[4] obatek INEF4,67 rue Mirambeau, F-64600 Anglet, France
关键词
District heating; Thermal energy storage; Optimization; Sizing; Flexible operation; Life cycle assessment; SYSTEM-DESIGN; STORAGE TANK; NETWORK; COST; METHODOLOGY; SELECTION;
D O I
10.1016/j.enconman.2024.118079
中图分类号
O414.1 [热力学];
学科分类号
摘要
A large fraction of district heating networks in Europe are still operating without thermal energy storage. While offering operational flexibility, the presence of energy storage complicates the problems of optimal sizing and control of the heat production plant. This necessitates a novel approach to system sizing based on non-linear programming in order to capture the system's thermal response and inertia. Therefore, the present study focuses on such a typical plant in France and describes a holistic approach to optimize the capacities/parameters of system components, positions of the energy sources, as well as hourly flow rates. Such a simultaneous tuning of the system parameters and operating variables is essential to maximize the cost savings over the system's lifetime. The proposed framework here maintains the original non-linear form of the objective function and the constraints for more accuracy while allowing precise modeling of the thermally stratified storage tank by decoupling its calculations at a lower simulation level. Hence, the computation time in MATLAB (R) R2020A is mostly below 20 min on a typical personal computer. The lowest levelized cost of heat (57.259 EUR/MWh) is achieved when placing the gas boiler on a parallel line between the biomass boiler and the storage tank while sizing the two boilers using fractions of 0.33 and 0.73 of the maximum hourly demand, respectively, as well as a storage volume of 318.9 m3. Such relatively small storage reduces the lifecycle costs by a maximum of 1.34 % while reducing the specific carbon emissions by 17.33 %. Besides, it dampens the fluctuations in supply flow rates, minimizes unnecessary flow recirculation, and ensures a stable heat supply. Overall, thermal storage has a reasonable positive impact from an economic perspective, but a substantial impact on operational flexibility and mitigated carbon emissions.
引用
收藏
页数:24
相关论文
共 50 条
  • [1] Hierarchical optimization of district heating plants by integrating evolutionary and non-linear programming algorithms
    Hassan, Muhammed A.
    Araji, Mohamad T.
    APPLIED ENERGY, 2024, 373
  • [2] Optimising urban energy systems: Simultaneous system sizing, operation and district heating network layout
    Morvaj, Boran
    Evins, Ralph
    Carmeliet, Jan
    ENERGY, 2016, 116 : 619 - 636
  • [3] Operation optimization of existing district heating systems
    Jie, Pengfei
    Zhu, Neng
    Li, Deying
    APPLIED THERMAL ENGINEERING, 2015, 78 : 278 - 288
  • [4] Optimized Operation and Sizing of Solar District Heating Networks with Small Daily Storage
    Delubac, Regis
    Sadr, Mohammad
    Sochard, Sabine
    Serra, Sylvain
    Reneaume, Jean-Michel
    ENERGIES, 2023, 16 (03)
  • [5] Calibration of pipe networks for district heating using the non-linear optimisation method
    Dobersek, D
    Goricanec, D
    Krope, J
    INTERNATIONAL JOURNAL OF NONLINEAR SCIENCES AND NUMERICAL SIMULATION, 2006, 7 (02) : 225 - 228
  • [6] Sizing and control optimization of thermal energy storage in a solar district heating system
    Saloux, Etienne
    Candanedo, Jose A.
    ENERGY REPORTS, 2021, 7 : 389 - 400
  • [7] Improving the district heating operation by innovative layout and control strategy of the hot water storage tank
    Yang, Xiaochen
    Svendsen, Svend
    ENERGY AND BUILDINGS, 2020, 224
  • [8] A two-phase nonlinear optimization method for routing and sizing district heating systems
    Lambert, Jerry
    Spliethoff, Hartmut
    ENERGY, 2024, 302
  • [9] Optimization Tool for the Strategic Outline and Sizing of District Heating Networks Using a Geographic Information System
    Resimont, Thibaut
    Louveaux, Quentin
    Dewallef, Pierre
    ENERGIES, 2021, 14 (17)
  • [10] RESEARCH AND APPLICATION OF SYNCHRONIZED LAYOUT AND OPTIMIZATION MODEL FOR RENEWABLE ENERGY STATIONS IN DISTRICT HEATING SYSTEMS
    Wang, Jinda
    Kong, Fansi
    Jin, Yufei
    Zhang, Bishan
    Taiyangneng Xuebao/Acta Energiae Solaris Sinica, 2024, 45 (10): : 266 - 275