CFD simulations of a semi-transverse ventilation system in a long tunnel

被引:7
作者
Dastan, Alireza [1 ]
Rahiminejad, Mohammad [2 ]
Sabz, Mozhgan [2 ,3 ]
Abbasi, Meisam [2 ]
Mokhtari, Ali [2 ]
Sadrizadeh, Sasan [2 ,4 ]
Abouali, Omid [2 ,4 ]
机构
[1] Univ Isfahan, Fac Engn, Dept Mech Engn, Esfahan 8174673441, Iran
[2] Shiraz Univ, Sch Mech Engn, Shiraz 7193616548, Iran
[3] Univ Alberta, Dept Mech Engn, Edmonton, AB T6G 2R3, Canada
[4] KTH Univ, Dept Civil & Architectural Engn, S-10044 Stockholm, Sweden
关键词
Keywords; CFD; Semi-transverse ventilation; Tunnel; Ceiling duct; Traffic; NATURAL VENTILATION; SMOKE CONTROL; PERFORMANCE; FIRE; SLOPE;
D O I
10.1016/j.undsp.2022.12.004
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
In the present work, a semi-transverse ventilation system in a long tunnel with a length of 4.9 km, as a complex case study, is numerically studied by performing a set of three-dimensional steady incompressible computational fluid dynamics (CFD) simulations. The ventilation system consisted of a ceiling duct connected to two axial fans at the ending portals, and a series of jet fans in the main tunnel for supporting airflow in the desired direction. To focus on what can and cannot be achieved in commissioning tests, the ventilation system's performance in various scenarios is numerically evaluated with two different tunnel states; empty tunnel and complete traffic congestion with 1176 stationary vehicles - which is almost impossible to evaluate during a commissioning test. By considering two hypothetical locations for the extraction zone from the main tunnel (in a distance of 450 and 1000 m from one portal), it is shown that the required number of jet fans in a traffic condition drops from 57 for the first extraction location to 43 (25% decrease) when the ventilation system extracts from the second zone. We show that if only the close axial fan to the extraction zone is activated, the required number of jet fans reduces by 56% and 72% for the first and second extraction locations, respectively. This finding can provide a cheaper and easier controlling scenario for emergency ventilation.
引用
收藏
页码:153 / 170
页数:18
相关论文
共 46 条
  • [1] Almbauer R. A., 2004, P 2 INT C TUNNEL SAF, P32
  • [2] Influence of the slope in the ventilation semi-transversal system of an urban tunnel
    Ballesteros-Tajadura, R
    Santolaria-Morros, C
    Blanco-Marigorta, E
    [J]. TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2006, 21 (01) : 21 - 28
  • [3] Numerical study of the optimization of the pitch angle of an alternative jet fan in a longitudinal tunnel ventilation system
    Betta, Vittorio
    Cascetta, Furio
    Musto, Marilena
    Rotondo, Giuseppe
    [J]. TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2009, 24 (02) : 164 - 172
  • [4] Novel correlation to evaluate the pressure losses for different traffic jam conditions in road tunnel
    Cascetta, Furio
    Musto, Marilena
    Rotondo, Giuseppe
    D'Alessandro, Carmine
    De Maio, Davide
    [J]. TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2019, 86 : 165 - 173
  • [5] Innovative experimental reduced scale model of road tunnel equipped with realistic longitudinal ventilation system
    Cascetta, Furio
    Musto, Marilena
    Rotondo, Giuseppe
    [J]. TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2016, 52 : 85 - 98
  • [6] Longitudinal ventilation for smoke control in a tilted tunnel by scale modeling
    Chow, W. K.
    Wong, K. Y.
    Chung, W. Y.
    [J]. TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2010, 25 (02) : 122 - 128
  • [7] Analysis of the ventilation systems in the Dartford tunnels using a multi-scale modelling approach
    Colella, F.
    Rein, G.
    Carvel, R.
    Reszka, P.
    Torero, J. L.
    [J]. TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2010, 25 (04) : 423 - 432
  • [8] Dastan A., 2019, TUNNELS UNDERGROUND, P4759
  • [9] Performance evaluation of longitudinal and transverse ventilation for thermal and smoke control in a looped urban traffic link tunnel
    Du, Tao
    Yang, Dong
    Peng, Shini
    Liu, Yingli
    Xiao, Yimin
    [J]. APPLIED THERMAL ENGINEERING, 2016, 96 : 490 - 500
  • [10] A method for design of smoke control of urban traffic link tunnel (UTLT) using longitudinal ventilation
    Du, Tao
    Yang, Dong
    Peng, Shini
    Xiao, Yimin
    [J]. TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2015, 48 : 35 - 42