Hollow waveguide CO2 laser sensing system for rapid detection of trace sulfur hexafluoride (SF6) gas

被引:2
|
作者
Zhu, Yizhen [1 ]
Li, Guishun [2 ]
Liu, Sheng [1 ]
Yu, Shuoying [1 ]
Hou, Guangning [1 ]
Zha, Zhipeng [1 ]
Zhang, Qingtian [1 ]
Liu, Shaohua [1 ]
Jing, Chengbin [1 ]
Chu, Junhao [1 ]
机构
[1] East China Normal Univ, Engn Res Ctr Nanophoton & Adv Instrument, Sch Phys & Elect Sci, Minist Educ,Dept Mat, 500 Dongchuan Rd, Shanghai 200241, Peoples R China
[2] Jiangsu Second Normal Univ, Sch Phys & Informat Engn, Nanjing 211200, Peoples R China
基金
中国国家自然科学基金;
关键词
Hollow waveguide; Gas sensing; Sulfur hexafluoride (SF6); CO2; laser;
D O I
10.1016/j.infrared.2023.105045
中图分类号
TH7 [仪器、仪表];
学科分类号
0804 ; 080401 ; 081102 ;
摘要
Sulfur hexafluoride (SF6) has been widely applied in electrical facilities due to its excellent electrical insulation and high-voltage arc extinguishing properties, although it is a potent greenhouse gas. Rapid detection of trace SF6 gas is significant for monitoring the operation safety of high-voltage power grid facilities and greenhouse gas emissions. In this work, a SF6 gas sensing system was proposed and built using a CO2 laser as the light source and a 700 mu m bore Ag/AgI hollow glass waveguide (HGW) as the gas chamber and laser transmission channel. Sensing performances of the SF6 gas HGW sensors with different lengths were investigated. The gas sensing sensitivity and standard deviation (SD) of blank increase as the waveguide length increases. The limit of detection (LOD) decreases with waveguide length increase but the decline becomes less pronounced after the length exceeds 120 cm. The HGW length exhibits minor effect on the response and recovery time of the sensor system. The sensor sensitivity undergoes a slight reduction as the HGW is bent. Optimization of the sensing performance was achieved based on the straight 120 cm-length HGW SF6 gas sensor system. Its sensitivity reaches 0.384 dB/ppm and the LOD is 148 ppb with good cyclic response characteristics (response and recovery time 2-3 s). The present work provides a feasible idea for building up a trace SF6 gas sensing system with simple structure, easy operation and high performances.
引用
收藏
页数:8
相关论文
共 50 条
  • [1] Comparison of SF6/N2 and SF6/CO2 gas mixtures as alternatives to SF6 gas
    Qiu, Y
    Kuffel, E
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1999, 6 (06) : 892 - 895
  • [2] The increasing atmospheric burden of the greenhouse gas sulfur hexafluoride (SF6)
    Simmonds, Peter G.
    Rigby, Matthew
    Manning, Alistair J.
    Park, Sunyoung
    Stanley, Kieran M.
    McCulloch, Archie
    Henne, Stephan
    Graziosi, Francesco
    Maione, Michela
    Arduini, Jgor
    Reimann, Stefan
    Vollmer, Martin K.
    Muhle, Jens
    O'Doherty, Simon
    Young, Dickon
    Krummel, Paul B.
    Fraser, Paul J.
    Weiss, Ray F.
    Salameh, Peter K.
    Harth, Christina M.
    Park, Mi-Kyung
    Park, Hyeri
    Arnold, Tim
    Rennick, Chris
    Steele, L. Paul
    Mitrevski, Blagoj
    Wang, Ray H. J.
    Prinn, Ronald G.
    ATMOSPHERIC CHEMISTRY AND PHYSICS, 2020, 20 (12) : 7271 - 7290
  • [3] ABSORPTION OF CO2 LASER LINES BY SF6
    SHIMIZU, F
    APPLIED PHYSICS LETTERS, 1969, 14 (12) : 378 - &
  • [4] ABSORPTION OF CO2 LASER LINES BY SF6
    SHIMIZU, F
    BULLETIN OF THE AMERICAN PHYSICAL SOCIETY, 1969, 14 (04): : 619 - &
  • [5] USE OF A NEW GAS, SULFUR HEXAFLUORIDE, SF6, IN PNEUMOPERITONEUM - TREATMENT FOR TUBERCULOSIS
    SWALBACH, WG
    SCHWARTZ, SI
    RAHN, H
    HODGE, HC
    AMERICAN REVIEW OF TUBERCULOSIS AND PULMONARY DISEASES, 1957, 76 (06): : 1063 - 1070
  • [6] Swarm parameters in SF6 and CO2 gas mixtures
    Xiao, DM
    Li, XG
    Xu, X
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2001, 34 (24) : L133 - L135
  • [7] GAS-PHASE FLUORINATION OF CO2 BY SF6
    MALATESTA, V
    HACKETT, PA
    WILLIS, C
    JOURNAL OF THE CHEMICAL SOCIETY-CHEMICAL COMMUNICATIONS, 1981, (05) : 247 - 248
  • [8] Situation and Analysis of Sulfur Hexafluoride ( SF6) Byproducts of Gas Insulated Switchgear in Guangdong
    Fu, Qiang
    Wang, Yu
    Li, Zhi
    Yao, Weijian
    Zhuang, Xiansheng
    2010 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2010,
  • [9] Perforated corneal hydrops treated with sulfur hexafluoride (SF6) gas and tissue adhesive
    Sii, F
    Lee, GA
    Gole, GA
    CORNEA, 2005, 24 (04) : 503 - 504
  • [10] A laser photoacoustic system for detection of SF6 in gas insulated systems
    Shwehdi, MH
    Gondal, MA
    2001 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2001, : 104 - 109