Pool boiling heat transfer characteristics of R-1233zd(E) on smooth tube subject to POEC-220 lubricant oil

被引:10
作者
Kumar, Abhishek [1 ]
Shafiq, Qadir Nawaz [1 ]
Wang, Chi -Chuan [1 ,2 ]
机构
[1] Natl Yang Ming Chiao Tung Univ, Dept Mech Engn, Hsinchu 300, Taiwan
[2] 1001 Univ Rd, Hsinchu 300, Taiwan
关键词
Low GWP; R-1233zd(E); POE oil; Pool boiling; HTC; Smooth surface; Faible PRP; Huile POE; E; bullition libre; HTC (coefficient de transfert de chaleur); Surface lisse; EXCESS SURFACE-DENSITY; ENHANCED TUBES; TRANSFER PERFORMANCE; REFRIGERANT; VISCOSITY; MIXTURES; R134A; R1234ZE(E); R-123; PLAIN;
D O I
10.1016/j.ijrefrig.2022.09.037
中图分类号
O414.1 [热力学];
学科分类号
摘要
Pool boiling heat transfer characteristics of low pressure and low GWP refrigerant R-1233zd(E) alternative to R-123 and R-245fa on a smooth copper tube are investigated with the influence of POE (polyolester)-lubricant oil POEC-220 (220 cSt). The experiments were conducted at a saturation temperature of 10 degrees C, and 26.7 degrees C in 10-90 kWm- 2 heat flux range. The mass concentration of POEC-220 oil varied from 1-10%. The obtained results exhibit that the addition of POE lubricant to the pure low-pressure refrigerant R-1233zd(E) degraded the heat transfer performance. The average degradation of heat transfer coefficients (HTCs) for mass concentration of oil 1%, 3%, 5%, and 10% are 9.40%, 7.16%, 15.31%, and 42.87% respectively when compared to that of pure refrigerant. It is found that the nucleation sites are especially reduced at the bottom part of the test tube. Yet, either Augmentation or reduction of HTC with the presence of lubricant oil is mainly attributed to the absolute pressure (low/medium/high) of the working refrigerant/fluid/system/evaporator, the mass concentration of oil, boiling surface, and applied heat flux. However, augmentation in the HTC with less oil addition (e.g., less than 5%) can be seen for absolute pressures between 150 and 700 kPa.
引用
收藏
页码:233 / 242
页数:10
相关论文
共 36 条
  • [1] [Anonymous], 1990, RP601, P120
  • [2] Pool boiling performance of enhanced tubes on low GWP refrigerants
    Byun, Ho-Won
    Kim, Dong Ho
    Yoon, Seok Ho
    Song, Chan Ho
    Lee, Kong Hoon
    Kim, Ook Joong
    [J]. APPLIED THERMAL ENGINEERING, 2017, 123 : 791 - 798
  • [3] Cooper M. G., 1984, First U.K. National Conference on Heat Transfer, P785
  • [4] Fritz W, 1936, PHYS Z, V37, P391
  • [5] Nucleate boiling of low GWP refrigerants on highly enhanced tube surface
    Gorgy, Evraam
    [J]. INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2016, 96 : 660 - 666
  • [6] Average Heat Transfer Coefficient for Pool Boiling of R-134a and R-123 on Smooth and Enhanced Tubes (RP-1316)
    Gorgy, Evraam
    Eckels, Steven
    [J]. HVAC&R RESEARCH, 2010, 16 (05): : 657 - 676
  • [7] Influence of saturation temperature and heat flux on pool boiling of R245fa
    Halon, Stanislawa
    Gil, Bartosz
    Bialko, Boguslaw
    Zajaczkowski, Bartosz
    [J]. EXPERIMENTAL HEAT TRANSFER, 2021, 34 (07) : 587 - 604
  • [8] Hartnett J.P., 1986, J APPL MECH, V53, P12
  • [9] Nucleate pool boiling heat transfer coefficients of distilled water (H2O) and R-134a/oil mixtures from rib-roughened surfaces
    Hsieh, SS
    Weng, CJ
    [J]. JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 1997, 119 (01): : 142 - 151
  • [10] Ji WT, 2021, INT J REFRIG, V122, P122, DOI [10.1016/j.ijrefrig.2020.11.0020, 10.1016/j.ijrefrig.2020.11.002]