Identification of broken conductor faults in interconnected transmission systems based on discrete wavelet transform

被引:1
|
作者
Rashad, Basem Abd-Elhamed [1 ]
Ibrahim, Doaa K. [2 ]
Gilany, Mahmoud I. [2 ]
Abdelhamid, Ahmed Sayed [1 ]
Abdelfattah, Wael [1 ]
机构
[1] El Shorouk Acad, Higher Inst Engn El Shorouk City, Dept Elect Power & Machines Engn, Cairo, Egypt
[2] Cairo Univ, Fac Engn, Dept Elect Power Engn, Giza, Egypt
来源
PLOS ONE | 2024年 / 19卷 / 01期
关键词
LINE; SCHEME;
D O I
10.1371/journal.pone.0296773
中图分类号
O [数理科学和化学]; P [天文学、地球科学]; Q [生物科学]; N [自然科学总论];
学科分类号
07 ; 0710 ; 09 ;
摘要
Interconnected transmission systems are increasingly spreading out in HV networks to enhance system efficiency, decrease reserve capacity, and improve service reliability. However, the protection of multi-terminal lines against Broken Conductor Fault (BCF) imposes significant difficulties in such networks as the conventional distance relays cannot detect BCF, as the BCF is not associated with a significant increase in current or reduction in voltage Traditionally, the earth fault relays in transmission lines may detect such fault; Nonetheless, it suffers from a long delay time. Moreover, many of the nearby earth fault relays detect the BCF causing unnecessary trips and badly affecting the system stability. In this article, a novel single-end scheme based on extracting transient features from current signals by discrete wavelet transform (DWT) is proposed for detecting BCFs in interconnected HV transmission systems. The suggested scheme unit (SSU) is capable of accurately detecting all types of BCFs and shunt high impedance faults (SHIFs). It also adaptively calculates the applied threshold values. The accurate selectivity in multi-terminal lines is achieved based on a fault directional element by analyzing transient power polarity. The SSU discriminates between internal/external faults effectively utilizing the time difference observed between the first spikes of aerial and ground modes in the current signals. Different fault scenarios have been simulated on the IEEE 9-Bus, 230 kV interconnected system. The achieved results confirm the effectiveness, robustness, and reliability of SSU in detecting correctly BCFs as well as the SHIFs within only 24.5 ms. The SSU has confirmed its capability to be implemented in interconnected systems without any requirement for communication or synchronization between the SSU installed in multi-terminal lines.
引用
收藏
页数:25
相关论文
共 50 条
  • [31] Identification of commutation failures in HVDC systems based on wavelet transform
    Lin, Lingxue
    Zhang, Yao
    Zhong, Qing
    Wen, Fushuan
    2007 INTERNATIONAL CONFERENCE ON INTELLIGENT SYSTEMS APPLICATIONS TO POWER SYSTEMS, VOLS 1 AND 2, 2007, : 208 - 212
  • [32] Wavelet-packet-transform-based identification of motor systems
    Huang, Zhengfeng
    Gong, Beili
    MECHATRONICS, 2024, 104
  • [33] The Combination of Discrete Wavelet Transform and Self Organizing Map for Identification of Fault Location on Transmission Line
    Pothisarn, C.
    Ngaopitakkul, A.
    INTERNATIONAL MULTICONFERENCE OF ENGINEERS AND COMPUTER SCIENTIST, IMECS 2012, VOL II, 2012, : 1083 - 1086
  • [34] A comparison of Fourier transform and wavelet transform methods for detection and classification of faults on transmission lines
    Das, D.
    Singh, N. K.
    Sinha, A. K.
    2006 IEEE POWER INDIA CONFERENCE, VOLS 1 AND 2, 2006, : 815 - +
  • [35] Efficient fault identification scheme of compensated transmission grid based on correlated reactive power measurements and discrete wavelet transform
    Zaki, Mohamed, I
    El-Sehiemy, Ragab A.
    Amer, Ghada M.
    JOURNAL OF ELECTRICAL ENGINEERING-ELEKTROTECHNICKY CASOPIS, 2021, 72 (04): : 217 - 228
  • [36] A Load Identification Method Based on Active Deep Learning and Discrete Wavelet Transform
    Guo, Luyang
    Wang, Shouxiang
    Chen, Haiwen
    Shi, Qingyuan
    IEEE ACCESS, 2020, 8 : 113932 - 113942
  • [37] Identification of Marine Oil Spills by Fisher Discriminant Based on Discrete Wavelet Transform
    Liu Xiao-xing
    Wei Qi-gong
    Wang Si-tong
    Huang Yi
    Zhang Ting-ting
    Qi Chao-yue
    Li Jia
    SPECTROSCOPY AND SPECTRAL ANALYSIS, 2017, 37 (11) : 3479 - 3484
  • [38] Real time multiple objects tracking and identification based on discrete wavelet transform
    Cheng, FH
    Chen, YL
    PATTERN RECOGNITION, 2006, 39 (06) : 1126 - 1139
  • [39] Integrated Discrete Wavelet Transform-Based Faulted Phase Identification for Multi-Terminals Power Systems
    Zaki, Mohamed, I
    El Sehiemy, Ragab A.
    Amer, Ghada M.
    El Enin, Fathy M. Abo
    2017 NINETEENTH INTERNATIONAL MIDDLE-EAST POWER SYSTEMS CONFERENCE (MEPCON), 2017, : 503 - 509
  • [40] Transmission Line Fault Classification Using Discrete Wavelet Transform
    Choudhury, Mousam
    Ganguly, Amrita
    2015 INTERNATIONAL CONFERENCE ON ENERGY, POWER AND ENVIRONMENT: TOWARDS SUSTAINABLE GROWTH (ICEPE), 2015,