Low-temperature ammonia absorption refrigeration system based on the temperature difference uniformity principle: Optimization analysis

被引:4
作者
Zhang, Shuaishuai [1 ]
Liu, Yuanbo [1 ]
Chen, Yansong [1 ]
Zheng, Tong [1 ]
Lan, Zhong [1 ]
Wen, Rongfu [1 ]
Ma, Xuehu [1 ]
机构
[1] Dalian Univ Technol, Frontier Sci Ctr Smart Mat, State Key Lab Fine Chem, Liaoning Key Lab Clean Utilizat Chem Resources, Dalian 116024, Peoples R China
基金
中国国家自然科学基金;
关键词
Low -temperature heat source; Temperature difference uniformity; ECOP; ox; Optimum match; INTERNAL HEAT-RECOVERY; SMALL-CAPACITY; WATER; PERFORMANCE; DRIVEN; OPERATION; PROTOTYPE; MIXTURE; DESIGN;
D O I
10.1016/j.applthermaleng.2024.122584
中图分类号
O414.1 [热力学];
学科分类号
摘要
AARS (ammonia absorption refrigeration system) is one of the effective ways to utilize low-temperature waste heat below 100 degrees C for industrial applications. This novel system of LT-AARS is designed based on the principle of temperature difference uniformity for improving the overall COP. The partial condenser at the distillation section is adopted to achieve the purity of ammonia to more than 99.9 % with a small reflux ratio. A thermodynamic model is established to analyze the influence of the optimized distillation process on system performance and exergy loss. These modifications reduce the temperature difference uniformity factor from 1.12 to 1.025 and improve the COP from 0.414 to 065. Meanwhile, it is proved that the LT-AARS protocol is reasonable and effective by comparing the experimental values with the theoretical model. The exergy loss of the absorber and distiller accounts for about 55 % of the total exergy losses of LT-AARS. With the increases in refrigeration temperature from -15 to 5 degrees C and heat source temperature from 80 to 100 degrees C, the COP can reach a maximum of 0.77. ECOP first increases sharply and then decreases slowly with the increase of refrigeration and heat source temperature, and ECOP has a maximum value. The optimal range of ox for LT-AARS varies from 5 % to 10 %. The COP and ECOP of the LT-AARS are more than 0.6 and 0.3, respectively.
引用
收藏
页数:13
相关论文
共 40 条
  • [1] Modelling and experimental analysis of a GAX NH3-H2O gas-driven absorption heat pump
    Aprile, Marcello
    Scoccia, Rossano
    Toppi, Tommaso
    Guerra, Marco
    Motta, Mario
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2016, 66 : 145 - 155
  • [2] Experimental and numerical analysis of an air-cooled double-lift NH3-H2O absorption refrigeration system
    Aprile, Marcello
    Toppi, Tommaso
    Guerra, Marco
    Motta, Mario
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2015, 50 : 57 - 68
  • [3] Yearly investigation of a solar-driven absorption refrigeration system with ammonia-water absorption pair
    Bellos, Evangelos
    Chatzovoulos, Ion
    Tzivanidis, Christos
    [J]. THERMAL SCIENCE AND ENGINEERING PROGRESS, 2021, 23
  • [4] Thermodynamic analysis of an ammonia/water absorption-resorption refrigeration system
    Berdasco, M.
    Valles, M.
    Coronas, A.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 103 : 51 - 60
  • [5] Theoretical and experimental study of the ammonia/water absorption process using a flat sheet membrane module
    Berdasco, M.
    Coronas, A.
    Valles, M.
    [J]. APPLIED THERMAL ENGINEERING, 2017, 124 : 477 - 485
  • [6] Uniformity factor of temperature difference in heat exchanger networks
    Chen, Shang
    Cui, Guo-min
    [J]. APPLIED THERMAL ENGINEERING, 2016, 102 : 1366 - 1373
  • [7] Industrial trigeneration using ammonia-water absorption refrigeration systems (AAR)
    Colonna, P
    Gabrielli, S
    [J]. APPLIED THERMAL ENGINEERING, 2003, 23 (04) : 381 - 396
  • [8] Development and experimental study of an ammonia water absorption refrigeration prototype driven by diesel engine exhaust heat
    Du, S.
    Wang, R. Z.
    Chen, X.
    [J]. ENERGY, 2017, 130 : 420 - 432
  • [9] Graphical analysis on internal heat recovery of a single stage ammonia-water absorption refrigeration system
    Du, S.
    Wang, R. Z.
    Xia, Z. Z.
    [J]. ENERGY, 2015, 80 : 687 - 694
  • [10] Optimal ammonia water absorption refrigeration cycle with maximum internal heat recovery derived from pinch technology
    Du, S.
    Wang, R. Z.
    Xia, Z. Z.
    [J]. ENERGY, 2014, 68 : 862 - 869