MITIGATION OF HARMONIC CURRENT FOR BALANCED THREE-PHASE POWER SYSTEM BASED ON EXTENDED FRYZE ADAPTIVE NOTCH FILTER

被引:0
|
作者
Mohamad, Syahrul Hisham [1 ,2 ]
Radzi, Mohd Amran Mohd [2 ]
Mailah, Nashiren Farzilah [2 ]
Abd Wahab, Noor Izzri [2 ]
Jidin, Auzani [1 ]
机构
[1] Univ Putra Malaysia UPM, Fac Engn, Adv Lightning Power & Energy Res ALPER, Seri Kembangan, Malaysia
[2] Univ Teknikal Malaysia Melaka UTeM, Fac Elect & Elect Engn Technol, Durian Tunggal, Malaysia
来源
JOURNAL OF ENGINEERING SCIENCE AND TECHNOLOGY | 2023年 / 18卷 / 02期
关键词
Adaptive notch filter; Fryze; Harmonics; Shunt active power filter; FREQUENCY ESTIMATION; ENHANCEMENT; EXTRACTION;
D O I
暂无
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The power quality problem, especially regarding harmonics contamination, has dramatically affected the overall power system stability. In response to this, using an Active Power Filter (APF) is considered one of the compelling methods to overcome harmonics issues. This paper presents the implementation of Shunt APF with an improved adaptive notch filter known as Extended Fryze Adaptive Notch Filter (EFANF) for fundamental signal extraction. The adaptive notch filter has improved the utilization from a single-phase to three-phase application for direct fundamental signal extraction and is designed to cater DC link voltage regulation controllers based on the power loss equation by applying Fryze current control power. This extraction algorithm inherits simple design construction and frequency tracking, eliminating PLL reliance on synchronization. The proposed algorithm also improved the design by eliminating the needs of low pass filter as others time domain algorithms. The algorithm's effectiveness in operation for the Shunt APF is validated through simulation using MATLAB/Simulink and experiment work by integrating the algorithm with DSPACE RS1104. Based on both evaluations, the results obtained show a satisfactory and reasonable agreement in mitigating the harmonics for multi-load conditions. Simulation and experimentally proven harmonics mitigation managed to reduce under 5% following the IEE standard, and the algorithm function within expectation for both steady and transient state conditions. In comparison between the simulation and experimental results, both results show almost similar results in terms of waveform for source voltage, source current, load current, and filter current in both steady state and transient state. In terms of THD values, both simulations and experimental results recorded that the THD values for both conditions are below 5%, where the range is 1.45% to 2.46% for simulation and 2.88% to 3.65% for experimental results. Furthermore, the DC link also tended to be maintained by the algorithm.
引用
收藏
页码:1339 / 1362
页数:24
相关论文
共 50 条
  • [1] Shunt active power filter control for compensating current power quality problems in three-phase three-wire systems based on an adaptive notch filter
    Tabatabaei, Seyed Hossein
    Moslehi Bajestan, Mehran
    Jalilian, Alireza
    TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES, 2016, 24 (04) : 2539 - 2555
  • [2] Single-phase Hybrid Active Power Filter with Adaptive Notch Filter for Harmonic Current Estimation
    Mekhilef, Saad
    Tarek, Messikh
    Rahim, Nasrudin Abd
    IETE JOURNAL OF RESEARCH, 2011, 57 (01) : 20 - 28
  • [3] SELECTIVE HARMONIC CURRENTS SUPPRESSING APPLIED TO A THREE-PHASE SHUNT ACTIVE POWER FILTER BASED ON ADAPTIVE FILTERS
    Bacon, Vinicius Dario
    Oliveira da Silva, Sergio Augusto
    2015 IEEE 13TH BRAZILIAN POWER ELECTRONICS CONFERENCE AND 1ST SOUTHERN POWER ELECTRONICS CONFERENCE (COBEP/SPEC), 2015,
  • [4] Power system Frequency estimation Based on Adaptive Notch Filter
    Jiang Chaochao
    Su Yixin
    Zhang Huajun
    Liu Shilin
    2016 2ND INTERNATIONAL CONFERENCE ON INDUSTRIAL INFORMATICS - COMPUTING TECHNOLOGY, INTELLIGENT TECHNOLOGY, INDUSTRIAL INFORMATION INTEGRATION (ICIICII), 2016, : 191 - 194
  • [5] A Current Harmonic Suppression Method for PMSM Based on Harmonic Prediction Adaptive Notch Filter
    Zhang, Qiushi
    Fan, Ying
    Chen, Junlei
    Yang, Can
    Cheng, Ming
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2022, 37 (03) : 2107 - 2118
  • [6] Application of Direct Current Control in a Three-phase Parallel Active Power Filter
    Nedeljkovic, David
    Nemec, Mitja
    Ambrozic, Vanja
    ELEKTROTEHNISKI VESTNIK-ELECTROCHEMICAL REVIEW, 2009, 76 (03): : 85 - 91
  • [7] An Adaptive Clarke Transform Based Estimator for the Frequency of Balanced and Unbalanced Three-Phase Power Systems
    Aboutanios, Elias
    2017 25TH EUROPEAN SIGNAL PROCESSING CONFERENCE (EUSIPCO), 2017, : 1001 - 1005
  • [8] A three-phase shunt active power filter for damping of harmonic propagation in power distribution systems
    Rahmani, Salem
    Al-Haddad, Kamal
    Fnaiech, Farhat
    2006 IEEE INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS, VOLS 1-7, 2006, : 1760 - +
  • [9] A Three-phase Active Power Filter Based on PARK Transformation
    Cai, Changqing
    Wang, Liping
    Yin, Guohui
    ICCSSE 2009: PROCEEDINGS OF 2009 4TH INTERNATIONAL CONFERENCE ON COMPUTER SCIENCE & EDUCATION, 2009, : 1221 - +
  • [10] Study on the Current Detecting Method for Reactive Power and Harmonic of the three-phase circuits
    Wu Jianhua
    Fu Wei
    Yao Liqiang
    He Lihong
    Dong Zhongwen
    CCDC 2009: 21ST CHINESE CONTROL AND DECISION CONFERENCE, VOLS 1-6, PROCEEDINGS, 2009, : 2048 - 2051