The role of opened fire doors in enhanced heat exchange of long-distance utility tunnels

被引:3
作者
Wang, Shuoyan [1 ,2 ]
Yin, Haiguo [1 ]
Kang, Yunfei [1 ]
Deng, Xin [3 ]
Yang, Changqing [1 ]
Li, Angui [1 ]
机构
[1] Xian Univ Architecture & Technol, Sch Bldg Serv Sci & Engn, Xian 710055, Shaanxi, Peoples R China
[2] Xian Univ Architecture & Technol, Sch Architecture, Xian 710055, Shaanxi, Peoples R China
[3] Xian West Heat Boiler Environm Protect Engn Co, Xian 710061, Shaanxi, Peoples R China
基金
国家重点研发计划;
关键词
Long-distance utility tunnel; Opened fire door; ACH; Heat exchange; Numerical simulation; NATURAL VENTILATION; REDUCED-SCALE; AIR-FLOW; PERFORMANCE; MODEL; SIMULATION; RESISTANCE; TURBULENCE; VELOCITY; BLOCKAGE;
D O I
10.1016/j.tust.2024.105592
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Due to their distinctive structural attributes, fire compartments in utility tunnels result in regions of increased temperature concentration and thermal dissipation, notably influencing heat exchange phenomena. Investigating airflow diffusion and thermal exchange principles of fire compartments is important when optimizing heat transfer processes in extensive utility tunnels. In this study, we employed numerical simulations and rigorous experimental validation to compare velocity and temperature field attributes between conventional tunnels and those augmented with fire compartments under diverse boundary conditions. The findings revealed that sub-stantial ventilation exchange, reduced cable-based thermal exchange, diminished wall temperatures, and incorporation of opened fire doors are effective measures in improving the thermal environment in utility tunnels. During the summer season, it was observed that the temperature prerequisites were adequately met in a 400-m-long utility tunnel featuring cross-fire compartments at a ventilation rate of 4 air changes per hour (ACH), while tunnels surpassing a length of 600 m required a ventilation rate of 2 ACH, and single-fire compartment tunnels required a ventilation rate of 6 ACH for similar thermal control. Specifically, at a rate of 2 ACH, the temperature in the tunnel exhibited an average reduction of 3.25 C-degrees with the addition of one additional opened fire door. In comparison, a decrease of 1.91( degrees)C was observed when maintaining a rate of 4 ACH. Finally, the airflow characteristics of tunnels with normally opened fire doors were summarized via a finite forced jet model, and the specific ranges of the potential flow core region, characteristic attenuation region and radial attenuation region were obtained
引用
收藏
页数:17
相关论文
共 62 条
  • [1] A review on effect of geometrical, flow and soil properties on the performance of Earth air tunnel heat exchanger
    Agrawal, Kamal Kumar
    Das Agrawal, Ghanshyam
    Misra, Rohit
    Bhardwaj, Mayank
    Jamuwa, Doraj Kamal
    [J]. ENERGY AND BUILDINGS, 2018, 176 : 120 - 138
  • [2] [Anonymous], 2009, TECHNICAL MANUAL DES
  • [3] CFD modeling of air flow, humidity, CO2 and NH3 distributions in a caged laying hen house with tunnel ventilation system
    Babadi, Keyvan Ahmadi
    Khorasanizadeh, Hossein
    Aghaei, Alireza
    [J]. COMPUTERS AND ELECTRONICS IN AGRICULTURE, 2022, 193
  • [4] Criticality and threat analysis on utility tunnels for planning security policies of utilities in urban underground space
    Canto-Perello, Julian
    Curiel-Esparza, Jorge
    Calvo, Vicente
    [J]. EXPERT SYSTEMS WITH APPLICATIONS, 2013, 40 (11) : 4707 - 4714
  • [5] Monitoring and analysis of the temperature field of a cold-region highway tunnel considering the traffic-induced thermal effect
    Chang, Hongtao
    Ren, Rui
    Yang, Shaopeng
    Wang, Yaqiong
    [J]. CASE STUDIES IN THERMAL ENGINEERING, 2022, 40
  • [6] Chen K., 2021, Shield Construction Techniques in Tunneling
  • [7] ANALYSIS OF COOL STORAGE FOR AIR-CONDITIONING
    CHEN, SL
    KE, MT
    SUNG, PS
    HUANG, CW
    YEN, JL
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1992, 16 (06) : 553 - 563
  • [8] Using CFD to assess the influence of ceiling deflector design on airflow distribution in hen house with tunnel ventilation
    Cheng, Qiongyi
    Li, Hao
    Rong, Li
    Feng, Xiaolong
    Zhang, Guoqiang
    Li, Baoming
    [J]. COMPUTERS AND ELECTRONICS IN AGRICULTURE, 2018, 151 : 165 - 174
  • [9] Field measurement and assessment on airflow thermodynamic parameters in hot and humid underground tunnelling: A case study
    Chu, Zhaoxiang
    Zhou, Guoqing
    Rao, Zhonghao
    Wang, Yijiang
    Zhao, Xiaodong
    [J]. TUNNELLING AND UNDERGROUND SPACE TECHNOLOGY, 2022, 121
  • [10] Computational Fluid Dynamics aided investigation and optimization of a tunnel-ventilated poultry house in China
    Du, Longhuan
    Yang, Chaowu
    Dominy, Robert
    Yang, Li
    Hu, Chenming
    Du, Huarui
    Li, Qingyun
    Yu, Chunlin
    Xie, Lingzhi
    Jiang, Xiaosong
    [J]. COMPUTERS AND ELECTRONICS IN AGRICULTURE, 2019, 159 : 1 - 15