Regenerator performance using freezing concentration for heat source tower heat pump system

被引:5
|
作者
Han, Chong [1 ,2 ]
Yu, Muyang [1 ,2 ]
Hou, Chongchong [1 ,2 ]
Jiang, Huimin [3 ]
Chen, Chuanbao [3 ]
Yao, Yang [1 ,2 ]
Ni, Long [1 ,2 ]
机构
[1] Harbin Inst Technol, Sch Architecture, Harbin 150090, Peoples R China
[2] Minist Ind & Informat Technol, Key Lab Cold Reg Urban & Rural Human Settlement En, Harbin, Peoples R China
[3] Nanjing Wuzhou Refrigerat Grp Co Ltd, Nanjing, Peoples R China
基金
中国国家自然科学基金;
关键词
Heat source tower heat pump; Freeze concentration; Refrigeration; Heat transfer; Freezing process; DESICCANT;
D O I
10.1016/j.applthermaleng.2023.121053
中图分类号
O414.1 [热力学];
学科分类号
摘要
Freeze concentration has a good regeneration effect and is easy for latent heat utilization. The electronic expansion valve opening has a great impact on the icing process. Hence, to investigate variations in the freezing process and gain the optimum regeneration effect, a solution regenerator was tested under different system-side control strategies. The solution volume flow was 5 m3/h and the electronic expansion valve opening degree (OEEV) was from 100% to 50%. For ice-covering growth, ice in low opening degree spent a long time to cover the plate. The area of ice under 100% to 65% OEEV was 1.43 times that under 50% OEEV. Peak velocities from 100% to 50% OEEV all appeared in the early stage of icing development. Moreover, the low opening degree made the ice distribute unevenness. The percentage slope of 100% OEEV was 1.23% and that of 50% OEEV was 3.46%. In addition, decreasing ice thickness uniformity was beneficial to the separation process. The separation ratio from 100% to 50% OEEV was 49.51%, 51.67%, 57.88%, and 74.54%, respectively. Both the low average thickness growth rate and high separation ratio were beneficial to increase the regeneration concentration. The effective specific ice production rate was from 100% to 50% OEEV was 5.99 kg/kWh, 6.18 kg/kWh, 6.94 kg/kWh, and 6.88 kg/kWh, respectively. Results showed that 65% OEEV operation was optimum for the solution regenerator unit using freeze concentration.
引用
收藏
页数:15
相关论文
共 50 条
  • [41] Improvement of the performance of metal hydride pump by using phase change heat exchanger
    Miled, A.
    Mellouli, S.
    Ben Maad, H.
    Askri, F.
    INTERNATIONAL JOURNAL OF HYDROGEN ENERGY, 2017, 42 (42) : 26343 - 26361
  • [42] Experimental study of heat transfer of buried finned pipe for ground source heat pump applications
    Koyun, Ahmet
    Demir, Hakan
    Torun, Zakir
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2009, 36 (07) : 739 - 743
  • [43] Numerical study on heat and mass transfer characteristics of the counter-flow heat-source tower (CFHST)
    Lu, Jun
    Li, Wuyan
    Li, Yongcai
    Zeng, Liyue
    Yang, Lulu
    Xie, Ling
    Li, Qianru
    Wang, Meilin
    ENERGY AND BUILDINGS, 2017, 145 : 318 - 330
  • [44] Effects of heat reservoir temperatures on the performance of thermoelectric heat pump driven by thermoelectric generator
    Meng, Fankai
    Chen, Lingen
    Sun, Fengrui
    INTERNATIONAL JOURNAL OF LOW-CARBON TECHNOLOGIES, 2010, 5 (04) : 273 - 282
  • [45] Experimental Investigation for Heat Transfer Performance of Heat Pump Water Tank Containing PCM
    Wu Jianghong
    You Shaofang
    2011 3RD WORLD CONGRESS IN APPLIED COMPUTING, COMPUTER SCIENCE, AND COMPUTER ENGINEERING (ACC 2011), VOL 3, 2011, 3 : 313 - 320
  • [46] Predicting heat pump performance by thermodynamic generalizations of fluid flow and heat transfer data
    Soumerai, H.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1986, 9 (02): : 113 - 120
  • [47] Heat transfer in a reaction-diffusion system with a moving heat source
    Chatterjee, Ajay
    Chaturvedi, Sidharth
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2011, 54 (1-3) : 326 - 337
  • [48] Thermal performance in latent heat thermal energy storage with annular heat source using different shape fins
    Kong, Xiangqiang
    Hou, Wanke
    Miao, Xichun
    Zhang, Yijian
    Li, Ying
    Li, Jianbo
    SOLAR ENERGY, 2025, 291
  • [49] Reversely-variable circuitry for finned-tube heat exchanger in air source heat pump to enhance its overall energy performance
    Wang, Fei
    Zhao, Rijing
    Ma, Changming
    Huang, Dong
    Qu, Zhiguo
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2022, 142 : 48 - 57
  • [50] Effect of seawater intake methods on the performance of seawater source heat pump systems in cold climate areas
    Xin, Jia
    Lin, Duanmu
    Shu Haiwen
    ENERGY AND BUILDINGS, 2017, 153 : 317 - 324