Study on air-side performance of air-cooled heat exchangers under large air velocity and wet conditions

被引:1
作者
Wei, Wenjian [1 ,2 ]
Xu, Guoliang [1 ]
Wang, Yanfeng [2 ]
Ding, Ergang [2 ]
机构
[1] Zhejiang Univ Water Resources & Elect Power, Inst Adv Heat Transfer & Energy Applicat, Hangzhou 310018, Zhejiang, Peoples R China
[2] Zhejiang DunAn Themal Tech Co Ltd, Zhuji 311835, Zhejiang, Peoples R China
关键词
Heat transfer; Carryover; High humidity; Fin -and -tube heat exchanger; Microchannel heat exchanger; CONDENSATE DRAINAGE BEHAVIOR; MASS-TRANSFER; FIN; SURFACE;
D O I
10.1016/j.tsep.2024.102389
中图分类号
O414.1 [热力学];
学科分类号
摘要
Humidity condensation and carryover from air-cooled heat exchanger affects human comfort and equipment security in the working environment. Surface treatment with a hydrophilic coating is an effective water drainage and carryover resistance solution. In present study, the condensation carryover and air-side performances of a fin-and-tube heat exchanger (FTHX) and microchannel heat exchanger (MCHX) with different fin pitches and surface treatments were experimentally investigated under large air velocities and different inlet humidity conditions. Hydrophilic treatment of FTHX improved heat transfer and condensation drainage, and reduced air pressure loss. In contrast, with MCHX, hydrophilic treatment did not improve heat transfer and rather increased the air pressure loss. For FTHX, the results showed that, compared with the bare fin, the hydrophilic surface treated fin enhanced the Colburn j factor by 20-60 and 10-40% at inlet air dry/wet bulb temperature of 26.7/ 19.4(degrees)C (normal humidity condition) and 26.7/23.9(degrees)C (high humidity condition), respectively. The air friction factor f was reduced by namely by 10-40 and 20-40% under normal- and high-humidity conditions, respectively. Condensing water flowed or retained over the fin surface in film, which suppressed the formation of a water bridge among fins, improved water carry-over, and increased the critical air velocity by 50%. However, water film formation over the MCHX enlarged the water stagnant around the fin corner, which increased the air resistance by 5-10%, and increased the probability of the continuous water bridge formation and carryover.
引用
收藏
页数:12
相关论文
共 29 条
  • [11] Effect of surface coating on defrosting water drainage characteristics of vertical-fin microchannel frosting evaporator
    Li, Feng
    Wu, Siyuan
    Ma, Zhiheng
    Zhao, Rijing
    Huang, Dong
    [J]. APPLIED THERMAL ENGINEERING, 2022, 208
  • [12] Issues affecting the reliability of dynamic dip testing as a method to assess the condensate drainage behavior from the air-side surface of dehumidifying heat exchangers
    Liu, Liping
    Jacobi, Anthony M.
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2008, 32 (08) : 1512 - 1522
  • [13] Ma X.K., 2008, Dissertation
  • [14] Effects of hydrophilic coating on air side heat transfer and friction characteristics of wavy fin and tube heat exchangers under dehumidifying conditions
    Ma, Xiaokui
    Ding, Guoliang
    Zhang, Yuanming
    Wang, Kaijian
    [J]. ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (09) : 2525 - 2532
  • [15] Mclaughlin W.J., 2000, SAE TECHNICAL PAPER
  • [16] McQuiston F.C., 1994, HEATING VENTILATING, V4th, P594
  • [17] Condensate formation and drainage on typical fin materials
    Min, J
    Webb, RL
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2001, 25 (3-4) : 101 - 111
  • [18] Condensate carryover phenomena in dehumidifying, finned-tube heat exchangers
    Min, JC
    Webb, RL
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2000, 22 (3-4) : 175 - 182
  • [19] Experimental study of cyclic frosting and defrosting on microchannel heat exchangers with different coatings
    Pu, Liang
    Liu, Ran
    Huang, Hai
    Zhang, Shengqi
    Qi, Zhaogang
    Xu, Weidong
    Zhou, Jing
    [J]. ENERGY AND BUILDINGS, 2020, 226 (226)
  • [20] Water retention and drainage on air side of heat exchangers-A review
    Qi, Zhaogang
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2013, 28 : 1 - 10