A New-Designed Biological Electric Shock Identification Method in Low-Voltage Distribution Network

被引:3
作者
Yang, Gengjie [1 ]
Quan, Shengxin [1 ]
Gao, Wei [1 ]
机构
[1] Fuzhou Univ, Coll Elect Engn & Automat, Fuzhou 350108, Peoples R China
关键词
Kalman filters; Covariance matrices; Low voltage; Electric shock; Power system reliability; Fibrillation; Distribution networks; Residual current device(RCD); biological electric shock(BES); adaptive startup threshold; weighted sum of deviation; HUMAN-BODY; SAFETY;
D O I
10.1109/TPWRD.2022.3217880
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In general, residual current devices (RCDs) have problems such as protection dead-zone and difficulty in threshold setting. A new method for identification of biological electric shock (BES) in low-voltage distribution network based on threshold method is proposed. Firstly, the total residual current of the circuit is denoised by Kalman filter, and then two threshold methods are investigated to determine the electric shock (ES) event and type respectively. Specifically, the first threshold consists of the maximum and average value of the current changes in the previous period, which is an adaptive value of dynamic change. If the current sampling value exceeds the threshold for 10 times in total within 5 ms, an ES is considered to have occurred. Then considering that the amplitude of the waveform of the first three periods after BES has the characteristics of gradual changes, the sampling values of the three periods are recorded. The second threshold is a fixed threshold which is obtained by weighting the phase point changes corresponding to the second-period and the third-period waveforms, and then the specific ES types are distinguished. The proposed method is implemented on hardware devices and analyzed in various common ES situations. The results show that for the three cycles of waveforms collected after the occurrence of grounding or ES, the accuracy of this method is 97.84% and the recognition time is 2.07 ms. In addition, based on the analysis of the actual BES data, a simple digital model is proposed to simulate the actual biological response, and it can be of great help in the subsequent study of such problems.
引用
收藏
页码:1558 / 1568
页数:11
相关论文
共 33 条
[1]  
[Anonymous], 1996, 61200413 IEC
[2]  
[Anonymous], 2011, 619361 IEC
[3]  
Benias PC, 2018, SCI REP-UK, V8, DOI [10.1038/s41598-018-25732-x, 10.1038/s41598-018-23062-6]
[4]   IMPACT OF RECENT DEVELOPMENTS IN BIOLOGICAL ELECTRICAL SHOCK SAFETY CRITERIA [J].
BRIDGES, JE ;
VAINBERG, M ;
WILLS, MC .
IEEE TRANSACTIONS ON POWER DELIVERY, 1987, 2 (01) :238-248
[5]   Verification of safety in low-voltage power systems without nuisance tripping of residual current devices [J].
Czapp, Stanislaw ;
Borowski, Kornel .
ELECTRIC POWER SYSTEMS RESEARCH, 2019, 172 :260-268
[6]   Polyploidy in Angiosperms: Genetic Insight to the Phenomenon [J].
Datta A.K. ;
Mandal A. ;
Das D. ;
Gupta S. ;
Saha A. ;
Paul R. ;
Sengupta S. ;
Halder S. ;
Biswas S. .
Proceedings of the National Academy of Sciences, India Section B: Biological Sciences, 2016, 86 (3) :513-522
[7]   A Complete Electrical Shock Hazard Classification System and Its Application [J].
Gordon, Lloyd B. ;
Cartelli, Laura ;
Graham, Nicole .
IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2018, 54 (06) :6554-6565
[8]  
[关海鸥 Guan Haiou], 2013, [农业工程学报, Transactions of the Chinese Society of Agricultural Engineering], V29, P187
[9]  
Guan Haiou Guan Haiou, 2018, Transactions of the Chinese Society of Agricultural Engineering, V34, P183
[10]  
Guan Haiou Guan Haiou, 2017, Transactions of the Chinese Society of Agricultural Engineering, V33, P202