Self-Measurement of the Admittance Matrix of AC-DC Power Converter by Internal Harmonic Injection

被引:4
|
作者
Sun, Chu [1 ]
Ding, Xiaofeng [1 ]
Zhang, Lei [1 ]
Guo, Hong [1 ]
Chen, Jikai [2 ]
机构
[1] Beihang Univ, Sch Automat Sci & Elect Engn, Beijing 100191, Peoples R China
[2] Northeast Elect Power Univ, Sch Elect Engn, Jilin 132011, Peoples R China
基金
中国国家自然科学基金;
关键词
Phase locked loops; Impedance; Harmonic analysis; Admittance; Voltage measurement; Voltage control; Power harmonic filters; Harmonic injection; impedance stability model; phase-locked loop (PLL); superposition principle; voltage source converter; IMPEDANCE MEASUREMENT; STABILITY ANALYSIS; SYSTEMS;
D O I
10.1109/TIE.2022.3225794
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
Frequency-domain impedance or admittance model is widely applied to analyze the harmonic stability of power electronic converters. Conventionally, the converter impedance is modeled holistically, without exhibiting the sole effect of different control and phase-locked loop (PLL). Besides, harmonic voltage or current injection external to the converter is usually adopted, which involves dedicated equipment and introduces unexpected inner impedance. In this article, the response of voltage perturbation upon ac-dc power converters along various voltage signal flow paths is analyzed, based on the superposition principle. Each part of admittance and its effect on stability can therefore be quantified explicitly. By injecting harmonic perturbation through the identified paths within the converter controller, each part of the admittances, with and without the concerned control or PLL blocks, is measured and summed to be the total admittance. Harmonic voltage mitigation control implemented on a grid-forming converter creates an ideal grid with constant voltage and nearly zero inner impedance at the injected harmonic frequency. The proposed admittance analysis and measurement are successfully applied to the power converter with different PLL, voltage feedforward, output power control, dc voltage control, and grid-forming cascaded control. The effectiveness of the analysis and the proposed admittance measurement approach is validated by comprehensive simulation and hardware tests.
引用
收藏
页码:1503 / 1513
页数:11
相关论文
共 33 条
  • [31] Modelling and analysis of LCC-HVDC converter station for harmonic coupling of AC/DC power grid during geomagnetic storm
    Yang, Peihong
    Han, Xiaoyong
    Jiang, Hui
    Shi, Xizhi
    Zhang, Zilei
    Liu, Chunming
    Liu, Lianguang
    IET POWER ELECTRONICS, 2023, 16 (14) : 2423 - 2434
  • [32] New Third-Harmonic Injection Modulation Reducing the DC-Link Energy Buffer Requirement of Phase-Modular Three-Phase Isolated PFC AC/DC Converter Systems
    Menzi, David
    Kolar, Johann W.
    Anderson, Jon Azurza
    Kasper, Matthias J.
    2021 IEEE 22ND WORKSHOP ON CONTROL AND MODELLING OF POWER ELECTRONICS (COMPEL), 2021,
  • [33] A High-Power-Density High-Efficiency Soft-Switched Single-Phase Universal Input to 28-V Isolated AC-DC Converter Module Designed for Paralleled Operation
    Shahzad, Danish
    Farooq, Maida
    Pervaiz, Saad
    Afridi, Khurram K.
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2022, 37 (07) : 8262 - 8280