Fluid Dynamics Calculation in SF6 Circuit Breaker during Breaking as a Prerequisite for the Digital Twin Creation

被引:4
作者
Popovtsev, Vladislav V. [1 ]
Khalyasmaa, Alexandra I. [1 ]
Patrakov, Yurii V. [1 ]
机构
[1] Ural Fed Univ, Ural Power Engn Inst, Ekaterinburg 620002, Russia
关键词
computational fluid dynamics; SF6 circuit breaker; switching arc; moving mesh; ALE; arc quenching; BOX ARC MODEL; GAS; INTERRUPTION; PERFORMANCE; SIMULATION;
D O I
10.3390/axioms12070623
中图分类号
O29 [应用数学];
学科分类号
070104 ;
摘要
The requirements to switching the capacities of SF6 circuit breakers submitted by Russian Grid companies are difficult to satisfy. The first limitation is related to material and financial costs in order to create a new requirement-satisfying switching device. The second limitation is dictated by the necessity of calculating complex physical processes in a circuit braker interrupter during fault-current making or breaking before creating a prototype. The latter task is reduced to the problem of simulating the processes of interaction between the switching arc and the SF6 gas flow. This paper deals with the solution of the problem both analytically by a special method and numerically by a numerical software package through the creation of a mathematical model of the interaction process. The switching arc is taken into account as a form of a temperature source, based on experimental data on measuring the temperature of the arc column. The key feature of the research is to use the finite element method based on a moving mesh-the Arbitrary Lagrangian Eulerian (ALE) method. Such a problem statement allows us to take the contact separation curve of the circuit breaker into account as the input data of the model. The calculations were carried out during fault-current breaking by a 110 kV SF6 dead-tank circuit breaker. The calculations of pressure and mass flow in the under-piston volume change, gas flow speed, and temperature depending on the contact separation are given. The proposed model of the switching arc was used to simulate the process of 25 kA symmetrical fault-current breaking and was compared with an experiment.
引用
收藏
页数:30
相关论文
共 83 条
[21]   Arc Gas-Flow Simulation Algorithm Considering the Effects of Nozzle Ablation in a Self-Blast GCB [J].
Choi, Young Kil ;
Shin, Jae Kyoung .
IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (04) :1663-1668
[22]  
Chunikhin A., 1985, HIGH VOLTAGE APPARAT
[23]  
Dhotre M.T., 2017, P 2017 IEEE EL INS C, P201, DOI [10.1109/EIC.2017.8004627, DOI 10.1109/EIC.2017.8004627]
[24]   SIMULATION OF TRANSIENT AND ZERO CURRENT BEHAVIOR OF ARCS STABILIZED BY FORCED-CONVECTION [J].
ELAKKARI, FR ;
TUMA, DT .
IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (06) :1784-1788
[25]  
Engelsht V., 1990, ELECT ARC COLUMN THE
[26]  
Eroshenko S., 2019, CALCULATION SHORT CI
[27]  
Fridman A., 2004, Plasma Physics and Engineering, DOI [10.1201/9781482293630, DOI 10.1201/9781482293630]
[28]  
Golovin S.V., 2009, THESIS NOVOSIBIRSK S
[29]   PTFE Vapor Contribution to Pressure Changes in High-Voltage Circuit Breakers [J].
Gonzalez, Jean-Jacques ;
Freton, Pierre ;
Reichert, Frank ;
Petchanka, Arkadz .
IEEE TRANSACTIONS ON PLASMA SCIENCE, 2015, 43 (08) :2703-2714
[30]  
Ha M.J., 2009, TRANSMISSION DISTRIB, DOI [10.1109/TD-ASIA.2009.5356810, DOI 10.1109/TD-ASIA.2009.5356810]