Effect of oxygen on pitting corrosion of copper pipe in fire sprinkler system

被引:6
|
作者
Lee, Yun-Ho [1 ]
Byun, Ji-Hae [1 ]
Ko, Sang-Jin [1 ]
Park, Eun-Ha [1 ]
Kim, Jung-Gu [1 ]
机构
[1] Sungkyunkwan Univ, Sch Adv Mat Sci & Engn, 2066 Seobu Ro, Suwon 440746, Gyeonggi Do, South Korea
基金
新加坡国家研究基金会;
关键词
Copper pipe; Pitting corrosion; Dissolved oxygen; Flow visualization; Oxygen consumption; CU-XZN ALLOYS; WATER; CHLORIDE; BEHAVIOR; RESISTANCE; TUBES; PH;
D O I
10.1016/j.matchemphys.2023.127584
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In this study, pitting corrosion in copper pipe used for sprinkler according to dissolved oxygen (DO) concen-tration was investigated through failure analyses, flow visualization test, DO consumption rate analysis, elec-trochemical tests, surface analyses, and corrosion simulation test. As a result of the failure analysis, all 10 leaks were due to pitting corrosion, and 8 leaks occurred in the branch pipe at the end of sprinkler system. As a result of flow visualization test, there were air pockets occupying 20% of the maximum total volume at the end of the branch pipe due to pressure drops. DO consumption rate analysis showed that air pocket acted as the oxygen source to maintain high DO concentration. As a result of electrochemical tests, surface analyses, and corrosion simulation, the corrosion rate of the higher DO concentration is about 10 times higher than that of lower DO concentration due to the increased oxygen reduction reaction. Through these results, it was confirmed that an air pocket was formed at the end of the pipe in the sprinkler system, and this air pocket became an oxygen source and accelerated galvanic corrosion between inside and outside of the pit during pitting propagation. This can be used as a guideline to prevent water leakage for pitting corrosion on copper pipe.
引用
收藏
页数:11
相关论文
共 50 条
  • [1] Pitting corrosion of copper tubes for fire sprinkler system
    Ko, Sang-Jin
    Lee, Yun-Ho
    Nam, Ki-Seok
    Park, Eun-Ha
    Kim, Jung-Gu
    ENGINEERING FAILURE ANALYSIS, 2022, 141
  • [2] Analysis of pitting corrosion failure of copper tubes in an apartment fire sprinkler system
    Suh, Sang Hee
    Suh, Youngjoon
    Yoon, Hyung Goog
    Oh, Jeong Han
    Kim, Youngjun
    Jung, Kimin
    Kwon, HyukSang
    ENGINEERING FAILURE ANALYSIS, 2016, 64 : 111 - 125
  • [3] Pitting Failure of Copper Pipings for Emergency Fire Sprinkler in Ground Water
    Baek, Seung-won
    Lee, Jong-kwon
    Kim, Jong-jip
    Kim, Kyung-ja
    METALS AND MATERIALS INTERNATIONAL, 2015, 21 (03) : 479 - 484
  • [4] Pitting failure of copper pipings for emergency fire sprinkler in ground water
    Seung-won Baek
    Jong-kwon Lee
    Jong-jip Kim
    Kyung-ja Kim
    Metals and Materials International, 2015, 21 : 479 - 484
  • [5] Inhibition of Pitting Corrosion Failure of Copper Tubes in Wet Sprinkler Systems
    Suh, Sang Hee
    Suh, Youngjoon
    Lee, Jonghyuk
    Kwon, HyukSang
    CORROSION SCIENCE AND TECHNOLOGY-KOREA, 2020, 19 (02): : 89 - 99
  • [6] Effect of benzotriazole on the existing pits of copper tube in fire sprinkler system
    Park, Eun-Ha
    Ko, Sang-Jin
    Kim, Jung-Gu
    HELIYON, 2023, 9 (12)
  • [7] In situ lining of a pre-action fire suppression system to prevent pitting corrosion of the carrier pipe
    Marshall, Orange
    CORROSION IN THE MILITARY II, 2008, 38 : 201 - 210
  • [8] Pitting corrosion of copper
    Cohen, A
    MATERIALS PERFORMANCE, 1996, 35 (07) : 6 - 7
  • [9] Pitting corrosion of copper
    Edwards, Marc, 1600, (86):
  • [10] THE PITTING CORROSION OF COPPER
    EDWARDS, M
    FERGUSON, JF
    REIBER, SH
    JOURNAL AMERICAN WATER WORKS ASSOCIATION, 1994, 86 (07): : 74 - 90