Experimental validation of the theoretical ejector model in a low-grade waste heat refrigeration system using R1233zdE as a working fluid

被引:7
|
作者
Mastrowski, Mikolaj [1 ,2 ]
Smolka, Jacek [3 ]
Butrymowicz, Dariusz [4 ]
Antczak, Lukasz [2 ]
Gagan, Jerzy [4 ]
Smierciew, Kamil [4 ]
机构
[1] Silesian Tech Univ, PhD Sch, Dept Thermal Technol, Akad 2a, PL-44100 Gliwice, Poland
[2] MARANI Ltd, Szybowa 14c, PL-41808 Zabrze, Poland
[3] Silesian Tech Univ, Dept Thermal Technol, Konarskiego 22, PL-44100 Gliwice, Poland
[4] Bialystok Tech Univ, Dept Thermal Engn, Wiejska 45c, PL-15351 Bialystok, Poland
关键词
Ejector; Refrigeration system; Waste heat; Low GWP refrigerant; Model validation; Experimental results; PERFORMANCE-CHARACTERISTICS; SUBCRITICAL OPERATION; GEOMETRY; DROP;
D O I
10.1016/j.applthermaleng.2023.121716
中图分类号
O414.1 [热力学];
学科分类号
摘要
Rising electricity prices and environmental regulations make it increasingly economically justifiable to utilize low-temperature waste heat, generated as a by-product of many technological processes. One potential application is the conversion of heat into cooling capacity using an ejector refrigeration system, to replace conventional electric-consuming cooling systems. Such systems, despite numerous descriptions in the literature, have not found industrial applications up to date. This work presents experimental results on the first commercial prototype cooling system driven by 200 kW waste heat of ultra-low temperature between 60 degrees C and 70 degrees C coming from the oil system of air compressors operating under real industrial operating conditions. A refrigeration system configuration based on the use of heat recovery downstream of the ejector and splitting the waste heat recovery heat exchanger into two stages was applied. The low GWP and low-pressure HFO R1233zd(E) refrigerant was used as a working fluid. The high-temperature cooling parameters, equivalent to the glycol temperature of 16 degrees C/19 degrees C (outlet/inlet of the evaporator), were examined and the COP of 0,25 was obtained. To obtain such a promising COP value, the critical and subcritical parameters of the ejector were investigated. Based on the experimental results the validation of the ejector theoretical model was performed for low-pressure refrigerant. The ejector component characteristic efficiencies were optimized for the ejector calculation model, and ejector key performance parameters were estimated to a high accuracy. The average relative error in the estimation was 7.1%, 4.5%, and 13.7% for the mass entrainment ratio, pressure ratio and ejector total efficiency, respectively. The resulting accuracy is sufficient from the perspective of refrigeration system design.
引用
收藏
页数:17
相关论文
共 50 条
  • [1] Thermal modelling and optimization of low-grade waste heat driven ejector refrigeration system incorporating a direct ejector model
    Riaz, Fahid
    Lee, Poh Seng
    Chou, Siaw Kiang
    APPLIED THERMAL ENGINEERING, 2020, 167
  • [2] Experimental Study of Hybrid Ejector System with R290 Driven by Low-grade Waste Heat
    Yoshida, Tokitaka
    Elbel, Stefan
    15TH IIR-GUSTAV LORENTZEN CONFERENCE ON NATURAL REFRIGERANTS, 2022, : 702 - 709
  • [3] Experimental study on ejector refrigeration system powered by low grade heat
    Yapici, R.
    Yetisen, C. C.
    ENERGY CONVERSION AND MANAGEMENT, 2007, 48 (05) : 1560 - 1568
  • [4] Experimental study of a low grade heat driven ejector cooling system using the working fluid R245fa
    Hamzaoui, Malek
    Nesreddine, Hakim
    Aidoun, Zine
    Balistrou, Mourad
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2018, 86 : 388 - 400
  • [5] Experimental performance of an ejector refrigeration system using methanol as a working fluid
    Riffat, S.B.
    Omer, S.A.
    Doherty, P.S.
    International Journal of Ambient Energy, 2000, 21 (01) : 3 - 10
  • [6] ENHANCED EJECTOR REFRIGERATION CYCLES POWERED BY LOW-GRADE HEAT .3. EXPERIMENTAL RESULTS
    SOKOLOV, M
    HERSHGAL, D
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 1991, 14 (01): : 24 - 31
  • [7] A full operating conditions ejector model for refrigeration systems driven by low-grade heat sources
    Guo, Haowei
    Wang, Lei
    Wang, Xinli
    CASE STUDIES IN THERMAL ENGINEERING, 2024, 60
  • [8] CFD modelling and experimental investigation of an ejector refrigeration system using methanol as the working fluid
    Riffat, SB
    Omer, SA
    INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2001, 25 (02) : 115 - 128
  • [9] A heat-powered ejector chiller working with low-GWP fluid R1233zd(E) (Part 1: Experimental results)
    Mahmoudian, Jafar
    Rocchetti, Andrea
    Mazzelli, Federico
    Milazzo, Adriano
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 121 (121) : 1 - 9
  • [10] Design and experimental investigation of a 1 kW organic Rankine cycle system using R245fa as working fluid for low-grade waste heat recovery from steam
    Muhammad, Usman
    Imran, Muhammad
    Lee, Dong Hyun
    Park, Byung Sik
    ENERGY CONVERSION AND MANAGEMENT, 2015, 103 : 1089 - 1100