Anti-Freezing Study of High-Level Water-Collecting Natural Draft Wet-Cooling Tower Based on Its Water Temperature Distribution Characteristics

被引:2
|
作者
Wang, Zhonghua [1 ]
Yue, Zenggang [1 ]
Wang, Wei [1 ]
Ma, Chenghui [1 ]
Li, Xiaoguang [2 ]
Guo, Changmin [2 ]
Zhao, Yuanbin [3 ]
机构
[1] Jining Huayuan Thermal Power Co Ltd, Jining 272113, Peoples R China
[2] Jinan Lanchen Energy Technol Co, Jinan 250101, Peoples R China
[3] Shandong Univ, Sch Energy & Power Engn, Jinan 250061, Peoples R China
关键词
high-level water-collecting natural draft wet cooling tower; anti-freezing; numerical simulation; water temperature distribution; INTAKE FLOW-RATE; NUMERICAL-ANALYSIS; PERFORMANCE; WIND; SIMULATION; CROSSWIND; DESIGN;
D O I
10.3390/en17030651
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Thermal power units play a crucial role in the deep peak regulation of power generation. During deep peak regulation, the load of the unit changes significantly, causing fluctuations in the inlet water temperature of the cooling tower and the water temperature in the filler. Therefore, in cold regions in winter, cooling towers have a high risk of freezing, which threatens the economic and safe operation of the unit. This paper establishes a three-dimensional numerical model based on constant heat dissipation and explores the average and minimum water temperatures at the bottom of filler under different water distribution methods, crosswind velocities, and ambient temperatures. The results show that the water distribution method has a significant impact on the water temperature at the filler bottom. Reducing the water distribution area can significantly increase the minimum water temperature at the filler bottom and reduce the risk of freezing. Although the presence of crosswind is not conducive to the cooling performance of the cooling tower, the higher the crosswind velocity, the higher the minimum outlet water temperature at the filler bottom and the lower the risk of freezing. The minimum water temperature at the filler bottom is approximately linearly related to the ambient temperature and is less affected by the unit load at the same temperature.
引用
收藏
页数:13
相关论文
共 23 条
  • [21] INVESTIGATING THE EFFECTS OF FLUE GAS INJECTION AND HOT WATER DISTRIBUTION AND THEIR INTERACTION ON NATURAL DRAFT WET COOLING TOWER PERFORMANCE
    Eldredge, Tom V.
    Stapleton, John M.
    PROCEEDINGS OF THE ASME POWER CONFERENCE, 2019, 2019,
  • [22] The efficiency of high-level water collecting cooling tower with the installation of cross wall affect by the evolution of aerodynamic field
    Chen, Guangan
    Zhao, Yuanbin
    Li, Wendong
    Ge, Wenjing
    APPLIED THERMAL ENGINEERING, 2019, 161
  • [23] Crosswind influence on cooling capacity in different zones for high level water collecting wet cooling towers based on field test
    Dang, Zhigang
    Gao, Ming
    Long, Guoqing
    Zou, Jian
    He, Suoying
    Sun, Fengzhong
    JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 2019, 190 : 134 - 142