Improved control of virtual synchronous generator under unbalance of grid voltage

被引:1
作者
Wen, Chunxue [1 ]
Huang, Yijun [1 ]
Li, Jianlin [1 ]
Wang, Peng [1 ]
机构
[1] Northern Univ Technol, Beijing Power Elect & Elect Dr Engn Res Ctr, Energy Storage Technol Engn Res Ctr, Beijing 100144, Peoples R China
基金
国家重点研发计划;
关键词
Virtual synchronous generator; Unsymmetrical fault; Current unbalance; Power oscillation;
D O I
10.1016/j.egyr.2023.05.206
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Asymmetric faults in the power grid will lead to unbalanced grid voltage. When the traditional VSG control operates under unbalanced grid voltage, the output current will be unbalanced, resulting in output power oscillation. This article first establishes a mathematical model for traditional VSG control, and then analyzes the problems that arise when traditional VSG operates under unbalanced voltage in the power grid. The main reason is that there are too many negative sequence components in the system. In response to these issues, this article proposes a positive and negative sequence independent control strategy, which improves the adaptability of VSG under asymmetric faults in the power grid by adding a negative sequence current loop and transient current suppression, and can output different control objectives. The proposed control strategy does not change the VSG characteristics and can operate normally connected to the grid. Finally, the effectiveness of the proposed strategy was verified through MATLAB/simulink simulation. (c) 2023 The Author(s). Published by Elsevier Ltd. This is an open access article under theCCBYlicense (http://creativecommons.org/licenses/by/4.0/).
引用
收藏
页码:824 / 834
页数:11
相关论文
共 13 条
  • [1] Virtual synchronous machine
    Beck, Hans-Peter
    Hesse, Ralf
    [J]. PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON ELECTRICAL POWER QUALITY AND UTILISATION, VOLS 1 AND 2, 2007, : 107 - +
  • [2] Chen M, 2017, IEEE ENER CONV, P2881, DOI 10.1109/ECCE.2017.8096533
  • [3] Driesen J, 2008, IEEE POW ENER SOC GE, P1323
  • [4] Guo J, 2019, CHIN CONTR DEC C
  • [5] Transient Characteristics of Synchronverters Subjected to Asymmetric Faults
    He, Lili
    Shuai, Zhikang
    Zhang, Xin
    Liu, Xuan
    Li, Zuyi
    Shen, Z. John
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (03) : 1171 - 1183
  • [6] Li F, 2018, 2018 IEEE 4TH SOUTHERN POWER ELECTRONICS CONFERENCE (SPEC)
  • [7] Liang D, 2018, 2018 IEEE 8 ANN INT
  • [8] Multiresonant Frequency-Locked Loop for Grid Synchronization of Power Converters Under Distorted Grid Conditions
    Rodriguez, Pedro
    Luna, Alvaro
    Candela, Ignacio
    Mujal, Ramon
    Teodorescu, Remus
    Blaabjerg, Frede
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2011, 58 (01) : 127 - 138
  • [9] A Comprehensive Review on a Virtual-Synchronous Generator: Topologies, Control Orders and Techniques, Energy Storages, and Applications
    Shadoul, Myada
    Ahshan, Razzaqul
    AlAbri, Rashid S.
    Al-Badi, Abdullah
    Albadi, Mohammed
    Jamil, Mohsin
    [J]. ENERGIES, 2022, 15 (22)
  • [10] Wang L, 2019, Nat Rev Cancer, V19