Experimental study of a gas-injection refrigeration system using refrigerant mixtures to replace R404A

被引:3
作者
Yoon, Il-Joo [1 ]
Kim, Jinyoung [1 ]
Lee, Dongchan [2 ]
Chung, Hyun Joon [3 ]
Kim, Yongchan [1 ]
机构
[1] Korea Univ Anam, Dept Mech Engn, Anam ro 145, Seoul 02841, South Korea
[2] Univ Seoul, Dept Mech & Informat Engn, 163 Seoulsiripdae ro, Seoul 02504, South Korea
[3] Hoseo Univ, Div Mech & Automot Engn, 79 Hoseo ro Baebang eup, Asan 31499, Chungcheongnamd, South Korea
基金
新加坡国家研究基金会;
关键词
Gas -injection refrigeration system; Ternary refrigerant mixture; Optimal composition ratio; Alternative refrigerant; Life cycle climate performance (LCCP); BOILING HEAT-TRANSFER; PRESSURE-DROP; PERFORMANCE EVALUATION; PUMP; CONDENSATION; R1234YF; BLENDS; R455A;
D O I
10.1016/j.applthermaleng.2022.119350
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, the performance characteristics of a gas-injection refrigeration system using ternary zeotropic mixtures of R32/R744/R1234yf were investigated to replace R404A. The performance of the gas-injection refrigeration system using R32/R744/R1234yf was measured and analyzed at various composition ratios. The test condition was set based on the refrigeration capacity B condition by the AHRI Standard 1251 (Indoor - 23 degrees C, outdoor 15 degrees C). The variation in the mass fraction of R32 affected the changes in latent heat and temperature glide. In addition, the injection pressure increased with an increase in the mass fraction of R744 owing to the low normal boiling point of R744. Based on the test results, the optimal composition ratio of R32/R744/R1234yf was determined to be 52/1/47 wt% considering the coefficient of performance (COP), refrigeration capacity, and global warming potential. R32/R744/R1234yf (52/1/47 wt%) showed a 9.56 % increase in COP and a 9.8 % decrease in life cycle climate performance (LCCP) compared with those of R448A owing to the lower compressor work and indirect emissions. The performance of the gas-injection refrigeration system using the mixture could be further improved by optimizing the system configuration.
引用
收藏
页数:10
相关论文
共 43 条
  • [1] Natural and synthetic refrigerants, global warming: A review
    Abas, Naeem
    Kalair, Ali Raza
    Khan, Nasrullah
    Haider, Aun
    Saleem, Zahid
    Saleem, Muhammad Shoaib
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2018, 90 : 557 - 569
  • [2] Air-Conditioning Heating and Refrigeration Institute (AHRI), 2014, 1251SI AHRI
  • [3] American National Standards Institute,, 2008, 210240 ANSIAHRI
  • [4] [Anonymous], Regulation (EU) No 517/2014 of the European parliament and of the council of 16 2014 on fluorinated greenhouse gases and repealing Regulation (EC) No 842/2006
  • [5] Arami-Niya A., INT J REFRIG, V118, P514
  • [6] Condensation of ternary low GWP zeotropic mixtures inside channels
    Azzolin, Marco
    Berto, Arianna
    Bortolin, Stefano
    Moro, Lorenzo
    Del Col, Davide
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 103 : 77 - 90
  • [7] The hunt for nonflammable refrigerant blends to replace R-134a
    Bell, Ian H.
    Domanski, Piotr A.
    McLinden, Mark O.
    Linteris, Gregory T.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 104 : 484 - 495
  • [8] Measurements and modelling of R455A and R452B flow boiling heat transfer inside channels
    Berto, Arianna
    Azzolin, Marco
    Bortolin, Stefano
    Guzzardi, Costantino
    Del Col, Davide
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2020, 120 : 271 - 284
  • [9] Performance evaluation of a gas injection CO2 heat pump according to operating parameters in extreme heating and cooling conditions
    Chung, Hyun Joon
    Baek, Changhyun
    Kang, Hoon
    Kim, Dongwoo
    Kim, Yongchan
    [J]. ENERGY, 2018, 154 : 337 - 345
  • [10] Coleman H.W., 2018, Experimentation, validation, and uncertainty analysis for engineers, V4th