Thermal management in legacy air-cooled data centers: An overview and perspectives

被引:14
作者
Isazadeh, Amin [1 ]
Ziviani, Davide [2 ]
Claridge, David E. [1 ]
机构
[1] Texas A&M Univ, Sch Mech Engn, Energy Syst Lab, College Stn, TX 77840 USA
[2] Purdue Univ, Sch Mech Engn, Ray W Herrick Labs, W Lafayette, IN 47907 USA
关键词
Data center; Air-cooled systems; Hard-floor design; Raised-floor design; Cold/hot aisle configuration; Aisle containment; Exhaust chimney; Evaporative cooling; Desiccant wheel; Thermal energy storage; RAISED-FLOOR; PERFORMANCE; SYSTEMS; HEAT;
D O I
10.1016/j.rser.2023.113707
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Depletion of fossil fuel reservoirs, greenhouse gas emissions' impact on global warming, and rising energy costs are pushing the data center sector to reduce energy use. This paper reviews strategies for improving the energy performance of air-cooled systems in datacom facilities and enhancing temperature and flow distribution in white space by analyzing different airflow delivery architectures (hard floor and raised floor designs), eliminating cold and hot air mixing by incorporating cold/hot aisle containment or exhaust chimneys, and potential energy savings achievable by utilizing evaporative cooling systems. It was found that the optimal ventilation system is hard-floor architecture with locally-ducted supply and return air. Hard floor is less complicated than raised floor design, and overhead supply air can minimize hot spots at the top of racks. Airflow management strategies including cold and hot aisle formation, aisle containment, and exhaust chimneys can reduce annual cooling energy usage by 10-50% in conjunction with air-side and water-side economizers, minimize hot spots, and enhance thermal performance during cooling system failure. Hot-Aisle Containment or exhaust chimneys provide better thermal and energy performance than open and/or cold-aisle containment, but they require new ducting in traditional data centers. Depending on the climate and geographical location, evaporative cooling can reduce annual cooling energy usage by 20-70% and lead to Power Usage Effectiveness as low as 1.06. Evaporative coolers are more suitable for dry climates, but this limitation can be ameliorated by incorporating desiccant wheels and thermal energy storage.
引用
收藏
页数:18
相关论文
共 75 条
  • [1] Ahuja N, 2013, P IEEE SEMICOND THER, P243, DOI 10.1109/SEMI-THERM.2013.6526836
  • [2] Al Khazraji A, 2018, INTSOC CONF THERMAL, P971, DOI 10.1109/ITHERM.2018.8419611
  • [3] Chip to Chiller Experimental Cooling Failure Analysis of Data Centers: The Interaction Between IT and Facility
    Alissa, Husam A.
    Nemati, Kourosh
    Sammakia, Bahgat G.
    Seymour, Mark J.
    Tipton, Russell
    Mendo, David
    Demetriou, Dustin W.
    Schneebeli, Ken
    [J]. IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY, 2016, 6 (09): : 1361 - 1378
  • [4] Chip to Facility Ramifications of Containment Solution on IT Airflow and Uptime
    Alissa, Husam A.
    Nemati, Kourosh
    Sammakia, Bahgat G.
    Schneebeli, Ken
    Schmidt, Roger R.
    Seymour, Mark J.
    [J]. IEEE TRANSACTIONS ON COMPONENTS PACKAGING AND MANUFACTURING TECHNOLOGY, 2016, 6 (01): : 67 - 78
  • [5] Experimentally Validated Computational Fluid Dynamics Model for a Data Center With Cold Aisle Containment
    Alkharabsheh, Sami A.
    Sammakia, Bahgat G.
    Shrivastava, Saurabh K.
    [J]. JOURNAL OF ELECTRONIC PACKAGING, 2015, 137 (02)
  • [6] [Anonymous], 2021, Cambridge Bitcoin electricity consumption index
  • [7] Anthes G, 2005, Power play
  • [8] Thermal Characteristics of Open and Contained Data Center Cold Aisle
    Arghode, Vaibhav K.
    Sundaralingam, Vikneshan
    Joshi, Yogendra
    Phelps, Wally
    [J]. JOURNAL OF HEAT TRANSFER-TRANSACTIONS OF THE ASME, 2013, 135 (06):
  • [9] ASHRAE, 2019, HVAC applications - chapter 20: data Centers and telecommunication facilities, SI
  • [10] Beghi A, 2019, 2019 3RD IEEE CONFERENCE ON CONTROL TECHNOLOGY AND APPLICATIONS (IEEE CCTA 2019), P424, DOI [10.1109/ccta.2019.8920603, 10.1109/CCTA.2019.8920603]